10.5 Anchor the 431A Cabinet The 431A Cabinet has four mounting holes to anchor the unit after is has been set in place. See Figure 10-4. Verify the Right Side Access Plate of the 431A and the corresponding left side access plate of the 431M or 4300 UPS is removed before anchoring the unit. NOTE: Ensure the 431A can be joined to the UPS/431M before final anchoring of the 431A. See below. Install the anchor bolts to secure the UPS on the floor. See Figure 9-4 for anchor bolt installation detail. Use 1/2” (12 mm) diameter anchor bolts. There are four 0.63” (16 mm) diameter holes provided in the UPS base. See Figure 8.3 for the hole locations and dimensions for the specified UPS models Anchor Bolt (1/2 in (12 mm) 4 bolt holes (Side View) 4 x 0.63 in. (16 mm) diameter bolt holes Figure 10-3 Anchor Bolt Installation Detail If the 431A is joining to the: 4300 UPS, go to section 10.6 431M, go to section 10.7 4 x 0.63 in. Dia. (16 mm) Figure 10-4 - 431A Base Anchor Points Back 26.7 in.. (677 mm) Front 19.0 in. (483 mm) 4300 Series Ancillary Cabinets Installation and Operation Manual 27