Download Ematic EVH528BU Digital Camera User Manual
Transcript
WLCA/WLHA HIGH WALL EVAPORATOR Installation Instructions Refrigerant Processing ! Warning ! It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when installing or servicing this unit. Finish all pipe connecting before proceeding to charging the system. Follow the instructions in the outdoor unit for line evacuation, opening service valves, and final charge adjustments. Operation charts and charge tables can be found in the EMI Condenser IOMs. 4. Braze tubing into fittings. 5. Attach manifold set. manifold Vacuum Pump Micron Gage Top discharge condeser shown Manifold Setup For Evacuation 1. Clean the ends of tubing and insert into fittings. 6. Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks. Top discharge condeser shown 2. Protect the valves by wrapping with a wet rag "heat sink" before brazing. heat sink shield Top discharge condeser shown 7. Once certain of a good evacuation and leak free joints, back-seat the valves (counter-clockwise) to open and allow factory charge to fill lines and indoor unit. Refer to Charts in condenser manual to “fine tune” the refrigerant charge. 3. We recommend the use of a shield (can be made from some scrap metal) to protect the paint. WLCA/WLHA High Wall Evaporator WLCA30 & WLCA36 utilize a TXV (Thermo Expansion Valve), which should be set at 10°F superheat. 12 www.enviromaster.com