Download CONTROLLER MANUAL SPINCHILLER C.D.A - mark-off
Transcript
SET POINT CORRECTION IN HEATING The current set point in heating is defined by the parameter SetHeat and by the following corrections: • OutsideT correction: value of the correction based on the outside temperature (between 0 and MaxCextH). • WR correction: value of the Water Reset correction according to the external signal (between 0 and MaxCWRH). The current set point will therefore be defined as follows: Current set point = SetHeat + OutsideT correction + WR correction In any case, the value calculated in this way is automatically limited between the two values set for the parameters MinSetH and MAXSetH, that is: MinSetH > current set point < MAXSetH Data creazione 10/09/03 DS03I009GB--00 Pagina 54 di 59