Download Siemens RDG400KN Technical data
Transcript
3.6.6 Single duct with radiator or floor heating On single-duct applications with radiator or floor heating, the thermostat controls a valve plus an auxiliary electrical heater. Parameter P01 is not available. The output signal for the air flow can be limited to a minimum and maximum value if required (see section 3.5 "Additional features"). Radiator, active in cooling mode The air flow starts to rise depending on the acquired room temperature, the current supply air temperature (if available) and the setpoint. The radiator receives an ON command when the acquired room temperature drops below setpoint (= setpoint for radiator). Note: “Setpoint for radiator” is limited by parameter “Maximum heating setpoint” (P10). Floor heating The radiator sequence can also be used for floor heating. The "Floor temperature limitation function" is described on page 26. Sequences 2-position radiator / floor heating H Changeover air Y XpC C max Vmax 100% H XpC XpH Vmax YV min Vmin 0% YV Vmin 0% TR [°C] Y TR [°C] Y XpR SDR ON 100% YR OFF Y TR W H C YV YR C min 100% Changeover air XpH max Y Modulating radiator / floor heating YR W dz Output signal Room temperature Effective setpoint Comfort Heating sequence Cooling sequence Volume flow rate Radiator / floor heating 0% TR [°C] XpH XpC Vmin Vmax W dz TR [°C] Proportional band heating Proportional band cooling Minimum volume output Maximum volume output 35 / 78 Siemens Building Technologies RDG400KN Basic documentation Functions CE1P3192en 20 Jul 2010