Transcript
3.10.12 Emergency control (LTE Mode only) In case of smoke or fire the damper can be overridden via KNX. The necessary information is provided by the function block “HVAC Emergency Mode” The table below describes the behavior of the controller output. # 0 1 2 3 4 5 Datapoint value Normal EmergPressure EmergDepressure EmergPurge EmergShutdown EmergFire Damper Normal operation Fully open Fully closed Fully open Fully closed Fully closed Emergency signals have highest priority and command the control output accordingly. Any ongoing function like fan-overrun etc. will be stopped immediately. The priority is as follows: 1. 2. 3. 4. Smoke Fire Fan overrun Normal operation (Emergency 1..4) (Emergency 5) (Emergency 0 and el heater fan overrun function is active) (Emergency 0 and operation by operating mode button) 53 / 78 Siemens Building Technologies RDG400KN Basic documentation Functions CE1P3192en 20 Jul 2010