4. System Features and Examples
4.1
Features
Classification
Control
Function
Item
Notes/Cautions
• Multiple unit operation
Maximum 15 units with PZ-60DR-E & PZ-41SLB-E; 16
units with PZ-52SF-E or other M-NET controllers.
• Remote controller operation
Last condition priority before turning off the unit.
• External device operation and external
pulse control
Signal : 12VDC, 24VDC, uncharged a-contact.
• External monitor signal output and supply air fan monitor output
Uncharged a-contact (external monitor/supply air fan
monitor change).
• External control operation mode setting
ON/OFF, ON, OFF and external control priority ON/OFF
mode.
• Timer control
Weekly timer & simple timer available for PZ-60DR-E.
• Delayed start
Delayed time can be varied only when the PZ-41SLB-E is
connected.
• Automatic recovery following power supply interruption (*1)
Automatic power recovery is fixed when PZ-60DR-E or
PZ-41SLB-E is connected.
• Power supply start/stop function
Function cannot be performed when PZ-41SLB-E is connected.
• High/low/Extra-Low change input
Uncharged a-contact (Remote display adaptor (PAC-SA88HA-E) is required.)
• Remote/local control change
Uncharged a-contact (Remote ON/OFF adaptor (PAC-SE55RAE) is
required.)(Function cannot be performed when using PZ-41SLB-E.)
• M-NET air conditioning operation.
Only when M-NET transmission cable is connected.
• System controller by Mitsubishi building
air control management system
Only when M-NET transmission cable is connected.
• Interlocked with Mr. Slim
Function cannot be performed with PZ-41SLB-E.
• Lossnay (heat recovery) ventilation/automatic By-pass ventilation switch
Also external By-pass switcing is available(Remote display adaptor (PAC-SA88HA-E) is required).
• For cold area operation
Installation
Maintenance
• Two non polar wires for remote controller
For PZ-60DR-E, PZ-41SLB-E connection: ø 0.65 to 1.2
PVC cable or 0.3 mm2 to 1.25 mm2 strand wire.
For M-NET connection: 1.25 mm2 to 2.00 m2 shielded
wire or equivalent.
• Address setting unnecessary
Excluding central controller system (except automatic
address).
• Test operation switch
For Lossnay single unit test operation.
• Filter maintenance display
(remote controller display)
Filter, core maintenance display for PZ-60DR-E.
• Inspection display
(remote controller, control board LED)
Error code indication for PZ-60DR-E.
• M-NET power supply display
(control board LED)
*1 The operation condition is saved, and when the power is turned off and then back on, the operation condition returns to the
previous requested condition. (When using PZ-60DR-E, PZ-41SLB-E, the start/stop condition from an external device is not
saved.)