7. M-NET Cable Installation
7.1
Precautions When Installing Wiring
1. When routing the transmission cable outside of all units, position it 5 cm or more away
cable for the power supply so that it will not pick up electrical noise. (Never use multicore cable or place the transmission cable in the same conduit as the power supply
cable.)
2. Never connect the power cable to the transmission cable terminal block; it will burn
out the circuit board.
3. Always use two-core cable for the transmission cable. Do not route this transmission
cable with the transmission cable from another system on the same multi-core cable;
it will result in signal error and cause the system not to operate properly.