Download Siemens SIMATIC NET Operating instructions
Transcript
Passive Components for Electrical Networks 4.5 Preassembled Industrial Twisted Pair (ITP) and Twisted-Pair (TP) Cables Use of Preassembled Cables Preassembled SIMATIC NET cables are available to connect DTEs and network components. Industrial Twisted Pair (ITP) Cables Preassembled Industrial Twisted Pair cables are intended for direct links (without patch cables) of up to 100 m in length between two devices. Due to the double, extra thick shielding, Industrial Twisted Pair cables are particularly suitable for an industrial environment with high levels of EMI, for example for a connection between wiring closets. Twisted-Pair (TP) Cables (Cord) The flexibility of the cord cables allows simple installation, for example in a wiring closet or to connect devices in a control room with low EMI levels. A maximum of 10 m of twisted-pair cord can be used between two devices. With structured cabling using two twisted-pair patch cables, this length is maximum for both patch cables together. Adapter cables are used to connect devices with a sub-D port to devices with RJ-45 port. To convert the RJ-45 interface of a DTE to a 15-pin sub-D interface of the ITP cabling system, you can use the TP converter cord 15/RJ-45. Note Other special cables and special lengths are available on request. You will find a contact address in Appendix B. SIMATIC NET Twisted-Pair and Fiber-Optic Networks C79000-G8976-C125-02 4-19