Code 2
Solar/group "4" (cont.)
Coding in the delivered condition
27:15
28:3
Possible change
26:3
Priority for DHW cylinder 2
with cyclical heating
26:4
Cyclical heating without
priority for one of the DHW
cylinders
27:5
The cyclical heating time is
to
adjustable from 5 to
27:60
60 min.
Cyclical heating time
15 min.
The DHW cylinder without priority is heated at
most for the duration of
the set cyclical heating
time if the DHW cylinder
with priority is heated up.
Cyclical pause time
28:1
3 min.
to
After the selected cyclical 28:60
heating time for the DHW
cylinder without priority
has expired, the rise in
collector temperature is
captured during the cyclical pause time.
Cyclical pause time adjustable from 1 to 60 min.
Heating circuit 1, heating circuit 2, heating circuit 3/group "5"
Select "5" for constant temperature control unit (see page 79).
Service
Select "Heating circuit ..." for weathercompensated control unit (see
page 79).
Coding
Possible change
A0:1
With Vitotrol 200A/200 RF
(automatic recognition)
A0:2
With Vitotrol 300A/300 RF
or Vitocomfort 200 (automatic recognition)
5585 174 GB
Coding in the delivered condition
A0:0
Without remote control
97