Mailbox Messaging User Manual 6.1 PTQ-PDPMV1 ♦ Quantum Platform PROFIBUS DP Master Network Interface Module for Quantum Mailbox Message Queuing The PTQ-PDPMV1 module operates asynchronously on the Mailbox Messages and as such provides for the queuing of the messages as they are received. The queue sizes used in the module are as follows: Queue Type Queue Size Max Description Output message from processor 126 Input messages for processor 126 Alarm messages from slaves for processor 100 Number of messages that the PTQ module will queue by type of message. Note that status of the queues can be monitored via the Queue Message Count values. 6.1.1 Queue Timeouts The PTQ-PDPMV1 module will only allow a message to stay in a queue for up to 10 seconds. If the PROFIBUS Master (for output messages) or the processor (for input and alarm messages) has not successfully received a message within 10 seconds, the module will clear the message out of the queue. Page 152 of 306 ProSoft Technology, Inc. August 12, 2014