Download Mircom QMT-5302 Specifications

Transcript
FleX-NetTM Installation and Operation Manual
QMP-5101N Network Paging Wiring for Mass Notification
QMP-5101N Network Master Paging Control Module Wiring to the ANC-5000 Audio
Network Controller Module
MNS - ACU
FX- LOC(R)
TWISTED
SHIELDED
PAIR
CABLE
QMP-5101N Network
Master Paging Module
PTT
TWISTED
SHIELDED
PAIR CABLE
Wire the Paging Bus
to all other ANC-5000
Audio Network
Controller Modules
OUT to IN. See Figure
73 for more details.
NOT USED
G.A.
Input
RS-485 IN
IN
-
This connection to Aux
Power is not
required when
ANC-5000 is
installed in the
Audio Card
Cage
+
-
MIC
PTT
OUT
S
+
+
+
-
QMP-5101N Network
Master Paging Module
S
-
MIC
Daisy chain PTT and
MIC to next FX-LOC(R).
At the last FX-LOC(R)
QMP-5101N Paging
Mocule connect EOL
resistors (3K9 ohms
value) to + and - of
both the MIC and PTT
terminals.
S - + S - + L - + S - + S - + - + - +
PAGING BUS
PTT
ANC-5000 Audio
Network Controller
Module in the
MNS (ACU)
Remote
Power
Input
MIC
JW8 JW7
Jumpers JW7 and JW8
must be installed at all
times.
139