3.Overpressure APPENDIX D – System Piping (continued) temperature requirements. Install a boiler bypass, system bypass, or primary-secondary loop when needed to maintain water temperatures and flows within the specified limits. (1)Install a properly sized expansion tank. (2)Do not exceed the boiler’s specific requirements for maximum allowable working pressure. (3)Do not plug or block the relief valve. (3)Do not allow chilled water to enter the boiler during the heating cycle, or heated water to enter chilled water coils during the cooling cycle. 4.Freezing (1) Run all portions of the system piping inside a heated space unless the system is properly protected with an inhibited antifreeze solution. 5.Overheating (1)Comply with the boiler’s specific requirement for minimum water flow through the boiler. See the Specifications Section of this manual. (2) Install a low-water cutoff device whenever the boiler is installed above the level of the lowest heat emitter or radiator. Also add a low-water cutoff when required by local code requirements. It is recommended that the LWCO control is installed above the boiler to provide the highest level of protection. However, where the LWCO control is approved by the LWCO control manufacturer for installation in a high boiler tapping of a water boiler, the use of the listed LWCO control is permitted when it is installed according to the LWCO manufacturer's instructions. 8. Dry Fire Install a low-water cutoff when the boiler is installed above the level of the lowest radiator and when required by local code. 9. Combination Heating and Cooling Systems If this boiler is used in connection with refrigeration systems, the boiler must be installed so that the chilled medium is piped in parallel with the heating boiler using appropriate valves to prevent the chilled medium from entering the boiler, see Figure D-W1. Also consult Residential Hydronic Heating Installation and Design I=B=R Guide. If this Boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air, the boiler piping must be equipped with flow control valves to prevent gravity circulation of boiler water during the operation of the cooling system. 6. Thermal shock (1)Do not over-pump. Adhere to the design flow requirements for each zone. (2)Install a boiler bypass, system bypass, or primary-secondary loop when needed to avoid returning large volumes of cold water directly to a hot boiler. 7.Condensation (1)Do not over-pump. Adhere to the design flow requirements for each zone. (2)Adhere to the boiler’s specific i 42 Figure D-W1: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems minimum return water and supply water The following system diagrams are intended to provide a minimum level of guidance for a successful and trouble-free installation of the boiler in common applications. They do not substitute for proper design, evaluation, and installation by a trained and qualified installer using the proper tools, techniques, and design expertise. Not all options are available with every boiler.