EEDEN09-720 technical data AlthermaTM AlthermaTM Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrige-rants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste. ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment. Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. “The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..” Naamloze Vennootschap Zandvoordestraat 300 B-8400 Ostend, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende EEDEN0 9 - 7 2 0 EEDEN09-720 - 03/2009 Printed in Belgium by Goekint Graphics Copyright © Daikin Daikin units comply with the European regulations that guarantee the safety of the product. EEDEN09-720 technical data AlthermaTM • AlthermaTM rA e0 h1 t4 l- RA Heating only Heat pump 4 • AlthermaTM • AlthermaTM AlthermaTM Small Capacity Indoor - Outdoor Heating only Heating and Cooling PAGE 1 2 Oudoor unit - 1~ 1 ERHQ006-008AD 9 Indoor unit - 1~ 1 EKHBH(X)008AA 21 3 AlthermaTM Large Capacity Indoor - Outdoor Heating only Heating and Cooling Oudoor unit - 1~ 2 ERHQ011-016AA 35 Oudoor unit - 3~ 2 ERHQ011-016AAW1 53 Indoor unit - 1~ 2 EKHBH(X)016AB 69 5 Without bottom plate heater - 1~ 3 EDHQ011-016AA6V3 83 6 Without bottom plate heater - 3~ 3 EDHQ011-016AA6W1 103 Bottom plate heater - 1~ 3 EDLQ011-016AA6V3 121 Bottom plate heater - 3~ 3 EDLQ011-016AA6W1 139 Without bottom plate heater - 1~ 3 EBHQ011-016AA6V3 157 Without bottom plate heater - 3~ 3 EBHQ011-016AA6W1 177 Bottom plate heater - 1~ 3 EBLQ011-016AA6V3 197 Bottom plate heater - 3~ 3 EBLQ011-016AA6W1 217 4 AlthermaTM Monobloc Heating only Heating and Cooling 7 8 9 10 11 AlthermaTM Optional comfort Stainless steel domestic hot water tank 4 EKHWS-B 237 Enameled domestic hot water tank 4 EKHWE 245 Solar kit 4 EKSOLHWAV1 251 Wired room thermostat 4 EKRTW 259 Wireless room thermostat 4 EKRTR 265 12 13 14 15 16 • AlthermaTM 5 EEDEN09-720 technical data AlthermaTM Part 1/4: ERHQ006-008AD EKHBH/X008AA • Outdoor units • ERHQ006-008AD TABLE OF CONTENTS ERHQ006-008AD 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3 Cooling/Heating capacity tables 4 11 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 15 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 16 5 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 6 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Wiring diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • AlthermaTM • Outdoor units 19 9 • Outdoor units • ERHQ006-008AD 1 D iA n8 0u 0 a - r m 6 o r 0 o e 0 dh Q t H uRl EA•O 1 Features Small capacity outdoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 1 10 • AlthermaTM • Outdoor units • Outdoor units • ERHQ006-008AD 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT For combination indoor units + outdoor units Indoor Units Condition 1 Heating capacity Nominal Capacity ERHQ007AD ERHQ008AD EKHBH008AA kW 4.36 4.36 Nominal kW 5.75 6.84 8.43 Maximum kW 7.45 8.79 9.58 Heating PI Nominal 1.26 1.58 2.08 COP Nominal 4.56 4.34 4.05 Heating capacity Minimum kW 3.87 3.87 3.87 Nominal kW 4.36 kW 5.03 6.10 7.64 Maximum kW 6.68 7.98 8.76 Heating PI Nominal 1.58 1.95 2.54 COP Nominal 3.18 3.13 3.00 Indoor Units Condition 1 Heating capacity kW EKHBX008AA Minimum kW 4.36 4.36 Nominal kW 5.75 6.84 8.43 Maximum kW 7.45 8.79 9.58 Minimum kW 4.82 4.82 4.82 Nominal kW 7.20 8.16 8.37 Maximum kW 7.20 8.50 8.91 Heating PI Nominal kW 1.26 1.58 2.08 Cooling PI Nominal kW 2.27 2.78 2.97 COP Nominal 4.56 4.34 4.05 Cooling capacity EER Nominal Heating capacity Minimum kW Nominal 4.36 3.17 2.94 2.82 3.87 3.87 3.87 kW 5.03 6.10 7.64 Maximum kW 6.68 7.98 8.76 Minimum kW 3.67 3.67 3.67 Nominal kW 5.12 5.86 6.08 Maximum kW 5.12 6.13 7.10 Heating PI Nominal kW 1.58 1.95 2.54 Cooling PI Nominal kW 2.16 2.59 2.75 COP Nominal 3.18 3.13 3.00 EER Nominal 2.37 2.26 2.21 Cooling capacity 1 2 Minimum For combination indoor units + outdoor units Nominal Capacity ERHQ006AD Notes Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C) - heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) 2-2 TECHNICAL SPECIFICATIONS Casing ERHQ006AD Colour Unit Packing Weight Packing ERHQ008AD Ivory white Material Dimensions ERHQ007AD Polyester painted galvanised steel Height mm 735 735 735 Width mm 825 825 825 Depth mm 300 300 300 Height mm 797 797 797 Width mm 960 960 960 Depth mm 390 390 390 Unit kg 56 56 56 Packed Unit kg 61 61 61 Material EPS Carton Weight kg 5 • AlthermaTM • Outdoor units 5 5 11 • Outdoor units • ERHQ006-008AD 2 2-2 1 Specifications TECHNICAL SPECIFICATIONS Heat Exchanger Dimensions Length mm Nr of Rows 2 Fin Pitch mm Nr of Stages ERHQ006AD ERHQ007AD ERHQ008AD 845 845 845 2 2 2 1.8 1.8 1.8 32 32 32 Tube type Fin Hi-Xa(8) Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 1 Discharge direction Motor Quantity Output Compressor W Quantity Motor Heating Cooling Sanitary water Sound Level (nominal) Heating Cooling Refrigerant 1 1 1 53 53 1 1 1 Model 2YC63BXD#C Hermetically sealed swing compressor Motor Output W 1,920 Min °CWB -20 -20 -20 Max °CWB 25 25 25 Min °CDB 10 10 10 Max °CDB 43 43 43 -20 Min °CDB -20 -20 Max °CDB 43 43 43 Sound Power dBA 61 61 62 Sound Pressure dBA 48 48 49 Sound Power dBA 63 63 63 Sound Pressure dBA 48 48 50 kg 1.7 Type R-410A Charge Control 1 Type Liquid (OD) l mm Type 0.75 0.75 Flare connection mm Quantity 15,9 1 1 1 Socket Diameter (OD) mm Minimum m 3 3 3 Maximum m 30 30 30 Additional Refrigerant Charge kg/m Max. internunit level difference m 18 18 18 0.02>10m 20 20 Defrost Method Reverse cycle Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 12 1 6,35 Type Piping Length 1 Flare connection Diameter (OD) Drain 0.75 Type Diameter (OD) Gas 1.7 FVC50K Charged Volume Piping connections 1.7 Expansion valve(electronic type) Nr of Circuits Refrigerant Oil 1 53 Type Operation Range 1 Horizontal Inverter controlled • AlthermaTM • Outdoor units 20 • Outdoor units • ERHQ006-008AD 2 2-2 Specifications TECHNICAL SPECIFICATIONS Standard Accessories ERHQ006AD Item ERHQ007AD ERHQ008AD Installation manual Quantity 1 Item 1 1 2 Drain plug Quantity 1 Notes 1 1 1 See operation range drawing The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. 2-3 ELECTRICAL SPECIFICATIONS Power Supply ERHQ006AD Name 1~ Frequency Hz 50 50 50 Voltage V 230 230 230 Voltage range Minimum V -10% Maximum V +10% Starting current Heating A 11 11 Cooling A 11 11 11 Heating A 18 18 18 Cooling A 16.25 16.25 16.25 A Maximum running Current Recomended fuses Wiring connections ERHQ008AD V3 Phase Current ERHQ007AD 11 20 20 20 Quantity 3 3 3 For connection Quantity with indoor Remark 4 4 4 For Power Supply • AlthermaTM • Outdoor units Included earth wiring 13 • Outdoor units • ERHQ006-008AD 3 Capacity tables 3-1 Cooling/Heating capacity tables COOLING 1 Model 3 006 007 008 Tamb (°C) LWE (°C) 7 11 13 16 20 7 11 13 16 20 7 11 13 16 20 20 CC 6.01 6.81 7.23 7.88 8.80 7.15 8.09 8.57 9.33 10.4 8.24 9.26 9.79 10.6 11.7 25 PI 1.56 1.57 1.57 1.56 1.55 2.05 2.09 2.11 2.13 2.16 2.43 2.49 2.52 2.57 2.63 CC 5.73 6.50 6.90 7.54 8.42 6.84 7.73 8.20 8.92 9.9 7.90 8.87 9.38 10.17 11.3 30 PI 1.75 1.77 1.78 1.78 1.79 2.28 2.34 2.36 2.40 2.44 2.68 2.76 2.80 2.86 2.94 CC 5.43 6.17 6.56 7.17 8.03 6.50 7.34 7.79 8.49 9.48 7.52 8.45 8.93 9.69 10.75 35 PI 1.95 1.98 2.00 2.01 2.03 2.52 2.59 2.63 2.68 2.73 2.94 3.05 3.10 3.17 3.26 CC 5.12 5.83 6.20 6.79 7.63 6.13 6.94 7.36 8.03 8.99 7.10 7.79 8.14 8.68 9.39 40 PI 2.16 2.21 2.23 2.26 2.29 2.77 2.87 2.91 2.97 3.04 3.23 3.31 3.36 3.41 3.48 CC 4.80 5.30 5.56 5.95 6.48 5.35 5.84 6.09 6.46 6.96 5.68 6.12 6.34 6.67 7.09 43 PI 2.39 2.32 2.28 2.22 2.13 2.68 2.62 2.59 2.53 2.44 2.86 2.80 2.77 2.71 2.61 CC 4.59 4.98 5.18 5.46 5.82 4.89 5.21 5.36 5.57 5.82 4.87 5.18 5.33 5.55 5.80 PI 2.53 2.38 2.30 2.18 1.99 2.59 2.43 2.34 2.20 1.99 2.59 2.43 2.35 2.20 1.99 HEATING (Peak values) Model 006 007 008 LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 30 HC 3.93 4.65 5.14 6.06 6.89 8.03 4.87 5.67 6.21 7.23 8.14 9.40 5.42 6.27 6.84 7.92 8.9 10.2 35 PI 1.48 1.52 1.54 1.57 1.57 1.57 1.82 1.88 1.91 1.95 1.97 1.98 2.06 2.13 2.17 2.22 2.26 2.28 HC 3.67 4.32 4.77 5.62 6.38 7.45 4.62 5.34 5.83 6.77 7.61 8.79 5.16 5.93 6.46 7.45 8.35 9.58 40 PI 1.59 1.65 1.68 1.72 1.74 1.75 1.94 2.02 2.07 2.13 2.16 2.19 2.19 2.29 2.34 2.41 2.46 2.51 HC 3.47 4.07 4.49 5.28 6.00 7.00 4.43 5.09 5.55 6.42 7.21 8.32 4.97 5.68 6.17 7.10 7.93 9.10 45 PI 1.71 1.79 1.83 1.88 1.91 1.94 2.08 2.18 2.24 2.32 2.37 2.42 2.34 2.46 2.53 2.62 2.69 2.76 HC 3.33 3.89 4.28 5.03 5.72 6.68 4.30 4.92 5.35 6.17 6.92 7.98 4.86 5.51 5.97 6.85 7.65 8.76 50 PI 1.84 1.94 1.99 2.06 2.11 2.15 2.23 2.36 2.42 2.52 2.59 2.66 2.51 2.65 2.73 2.85 2.93 3.02 HC 3.25 3.78 4.15 4.87 5.53 6.47 4.24 4.82 5.23 6.02 6.74 7.78 4.80 5.42 5.86 6.70 7.47 8.56 PI 1.99 2.10 2.16 2.25 2.31 2.37 2.40 2.55 2.63 2.75 2.83 2.92 2.70 2.86 2.95 3.10 3.20 3.31 HEATING (integrated values*) Model 006 007 008 LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 30 HC 3.50 4.14 4.52 5.27 5.92 8.03 4.34 5.04 5.46 6.29 7.00 9.40 4.82 5.58 6.02 6.89 7.6 10.2 35 PI 1.40 1.45 1.45 1.46 1.45 1.57 1.73 1.79 1.80 1.81 1.81 1.98 1.96 2.03 2.04 2.07 2.08 2.28 HC 3.27 3.85 4.20 4.89 5.49 7.45 4.11 4.75 5.13 5.89 6.55 8.79 4.59 5.28 5.69 6.48 7.18 9.58 40 PI 1.51 1.56 1.58 1.60 1.60 1.75 1.85 1.92 1.94 1.98 1.99 2.19 2.08 2.17 2.20 2.25 2.27 2.51 HC 3.09 3.62 3.95 4.59 5.16 7.00 3.94 4.53 4.88 5.59 6.20 8.32 4.43 5.06 5.43 6.17 6.82 9.10 45 PI 1.62 1.70 1.72 1.75 1.76 1.94 1.98 2.07 2.10 2.15 2.18 2.42 2.23 2.34 2.37 2.44 2.47 2.76 HC 2.97 3.46 3.77 4.38 4.92 6.68 3.83 4.38 4.71 5.37 5.96 7.98 4.32 4.91 5.26 5.96 6.58 8.76 HC PI LWE LWC Tamb 14 PI 1.75 1.84 1.87 1.92 1.94 2.15 2.12 2.24 2.28 2.35 2.38 2.66 2.39 2.52 2.57 2.65 2.70 3.02 HC 2.89 3.36 3.65 4.24 4.76 6.47 3.77 4.29 4.60 5.23 5.80 7.78 4.27 4.82 5.15 5.83 6.43 8.56 PI 1.89 2.00 2.03 2.10 2.13 2.37 2.28 2.42 2.47 2.56 2.61 2.92 2.56 2.72 2.78 2.88 2.94 3.31 * The integrated heating capacity and power input, is the average heating capacity and power input during 1 cycle. (from end of defrost till end of the next defrost). 3TW57782-1A NOTES SYMBOLS CC 50 : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Outdoor units 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 60 W (according EN14511). For the optional model with heatertape (V38) when ambient temperature becomes lower than 4°C: add power input of 60W • Outdoor units • ERHQ006-008AD 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing unit (mm) ERHQ006-008 AD Drain outlet (I.D. J 15.9 hose for connection) 4 Wall height on air outlet side = less than 1200 Minimum space for air passage 1 In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10) Name plate Brand name label Wiring inlet Terminal strip with earth terminal Outdoor air temperature thermistor Liquid stop valve (J6.4 CuT) Service port • AlthermaTM • Outdoor units Gas stop valve (J15.9 CuT) 3D060289 15 • Outdoor units • ERHQ006-008AD 1 4 Dimensional drawing & centre of gravity 4-2 Centre of gravity ERHQ006-008 AD 4 The position of foundation bolt 4D042258L 16 • AlthermaTM • Outdoor units • Outdoor units • ERHQ006-008AD 5 Piping diagram ERHQ006-008AD 1 Outdoor unit Heat exchanger 5 Outdoor air temperature thermistor Capillary tube 1 Capillary tube 2 Capillary tube 3 Heat exchanger thermistor Muffler with filter Refrigerant flow Cooling Heating Capillary tube 4 Filter Motor operated valve Propeller fan Filter Four way valve on : heating Muffler with filter Field piping Muffler Liquid stop valve Muffler Field piping Discharge pipe thermistor Compressor Accumulator Gas stop valve with service port 3D052750F • AlthermaTM • Outdoor units 17 • Outdoor units • ERHQ006-008AD 1 6 Wiring diagram 6-1 Wiring diagram ERHQ006-008AD 6 Power supply To indoor unit Sheet metal Indoor g Field wiring (outdoor) (discharge) (Condenser) Outdoor Z1C∼Z7C X1M, X2M Y1E V2, V3, V5, V9, V100 SA2 FU1, FU2, FU3: AC1, AC2 U, V, W, X11A, X12A E1, E2 HR1, HR2 18 : Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Surge arrester : Fuse : Connector MRM10, MRM20 MRC/W R1T∼R3T S2∼S102 LEDA L N SW1 SW4 M1C M1F L1R : Magnetic relay : Thermistor : Connector : Pilot lamp : Live : Neutral : Forced operation on/off switch SW (SW1) : Local setting SW (SW4) : Compressor motors : Fan motor : Reactor • AlthermaTM • Outdoor units Q1L PM1 PCB1,2 Y1R Sheet metal : Overload protector : Power module : Printed circuit board : Reversing solenoide valve coil : Terminal strip fixed plate 3D052296E • Outdoor units • ERHQ006-008AD 7 Sound data 7-1 Sound pressure spectrum ERHQ008AA HEATING 1 Sound pressure level (dB) Sound pressure level (dB) ERHQ007AA HEATING Sound pressure level (dB) ERHQ006AA HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) 7 Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) ERHQ008AA COOLING Sound pressure level (dB) Sound pressure level (dB) ERHQ007AA COOLING Sound pressure level (dB) ERHQ006AA COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW57557-1A • AlthermaTM • Outdoor units 19 • Indoor units • EKHBH-X008AA TABLE OF CONTENTS EKHBH-X008AA 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 24 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 5 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 7 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 8 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Static pressure drop unit • AlthermaTM • Indoor units 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 21 • Indoor units • EKHBH-X008AA 1 t A i A n8 0u a 0 m X r r - o e H o h B d tH nKl E•IA 1 Features Small capacity indoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 1 22 • AlthermaTM • Indoor units • Indoor units • EKHBH-X008AA 2 2-1 Specifications TECHNICAL SPECIFICATIONS EKHBH008AA Outdoor units ERHQ008ADV3 Nominal input (Indoor only) Casing W 230 Colour Packing Unit Weight Packing 230 RAL9010 Material Dimensions EKHBX0008AA 1 2 Epoxy polyester painted galvanised steel Height mm Width mm 660 1,225 660 Depth mm 610 610 Height mm 922 922 Width mm 502 502 Depth 361 mm 361 Unit kg 52 52 Packed Unit kg 67 67 Material EPS Wood Carton PP (Straps) Weight kg 10 Type 10 Main components Pump Water cooled Nr. of speed 3 3 Pump Nominal ESP unit Heating 38 38 Cooling kPa Main components Pump Power input W 130 130 Water side Heat exchanger Type kPa 48 Brazed plate Qty 1 1 0.67 0.67 12 Water volume l Water flow rate Min. l/min 12 l/min 24.1 Water side Heat exchanger Water flow rate Heating Nom. Cooling Main components Water side Heat exchanger Insulation material Expansion vessel Volume l 10 10 Max. water pressure bar 3 3 Pre pressure bar 1 1 Diameter mm perforatio ns 1 1 Water filter 17.4 Polyurethane foam Material Water circuit Piping connections diameter 24.1 l/min Brass inch Piping inch Safety valve bar G1 (MALE) 1-1/4’’ 3 Manometer 3 Yes Drain valve / Fill valve Yes Shut off valve Yes Air purge valve Yes Total water volume (6) l Refrigerant Circuit Gas side diameter mm Liquid side diameter mm Sound level Sound Pressure dBA 28 28 Sound Power dBA 42 42 • AlthermaTM • Indoor units 5.5 5.5 15,9 6,35 23 • Indoor units • EKHBH-X008AA 2 2-1 1 Specifications TECHNICAL SPECIFICATIONS Operation range 2 Ambient Waterside 2-2 °C Cooling °C Heating °C Cooling °C ELECTRICAL SPECIFICATIONS Electric heater Current Current Electric heater EKHBH008AA EKHBX0008AA 3V3 Phase 1~ Frequenc Hz y 50 50 Voltage V 230 230 Running Current A 13 13 List No requirements 0.25 + j0.15 Current Minimum Ssc value Voltage range Minimum -10% Maximum +10% Type Power Supply Current Equipment complying with EN/IEC 61000-3-12 Quantity of wires Type of wires 3G Select diameter and type according to national and local regulations 6V3 Phase 1~ Frequenc Hz y 50 50 Voltage V 230 230 Running Current A 26 26 Z-max Text 0.25 + j0.15 Zmax electric heater + booster heater (EKSWW* Models) Text 0.15 + j0.09 Current Minimum Ssc value Voltage range Minimum -10% Maximum +10% Wiring connections For power supply backup heater Electric heater Type Power Supply Current Electric heater 5~22 Text Electric heater Current 10~43 15~50 Zmax electric heater + booster heater (EKSWW* Models) For power supply backup heater Electric heater EKHBX0008AA -20~25 Z-max Wiring connections Current EKHBH008AA Type Power Supply 24 Heating Equipment complying with EN/IEC 61000-3-12 Quantity of wires Type of wires 3G Select diameter and type according to national and local regulations 6WN Phase 3~ Frequenc Hz y 50 50 Voltage V 400 400 Running Current A 8.7 8.7 Z-max List No requirements Zmax electric heater + booster heater (EKSWW* Models) List No requirements Current Minimum Ssc value Voltage range Minimum -10% Maximum +10% • AlthermaTM • Indoor units Equipment complying with EN/IEC 61000-3-12 • Indoor units • EKHBH-X008AA 2 2-2 Specifications ELECTRICAL SPECIFICATIONS Wiring connections For power supply backup heater Electric heater Type Power Supply EKHBH008AA Quantity of wires Type of wires Current Electric heater Wiring connections Electric heater Phase Electric heater Wiring connections Electric heater Voltage V 230 230 Running Current A 15.1 15.1 List Out of scope List Out of scope Current Minimum Ssc value Voltage range Minimum -10% Maximum +10% Quantity of wires Type of wires 4G Select diameter and type according to national and local regulations 9WN Phase 3~ Frequenc Hz y 50 50 Voltage V 400 400 Current Running Current A 13 13 Z-max List No requirements Zmax electric heater + booster heater (EKSWW* Models) List No requirements Current Minimum Ssc value Voltage range Minimum -10% Maximum +10% For power supply backup heater Equipment complying with EN/IEC 61000-3-12 Quantity of wires Type of wires 4G Select diameter and type according to national and local regulations Type 9T1 Phase 3~ Frequenc Hz y Current Electric heater Equipment complying with EN/IEC 61000-3-12 Type Power Supply Current 2 50 Z-max For power supply backup heater 1 3~ 50 Zmax electric heater + booster heater (EKSWW* Models) Power Supply Current Select diameter and type according to national and local regulations 6T1 Frequenc Hz y Current EKHBX0008AA 4G 50 50 Voltage V 230 230 Running Current A 22.6 22.6 Z-max List Out of scope Zmax electric heater + booster heater (EKSWW* Models) List Out of scope Current Minimum Ssc value Voltage range Minimum -10% Maximum +10% • AlthermaTM • Indoor units Equipment complying with EN/IEC 61000-3-12 25 • Indoor units • EKHBH-X008AA 2 2-2 1 Specifications ELECTRICAL SPECIFICATIONS Wiring connections 2 For power supply backup heater EKHBH008AA Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type For power supply connection to Optional Warm Water Tank + Q2L Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires (4) For more details of the voltage range and current refer to installation manual EKHBH/X008AA* Connection type For connection with R5T Quantity of wires wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type For connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual EKHB/X008AA* Type of wires Select diameter and type according to national and local regulations Type of wires Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm² Connection type For connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm² Connection type For connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Notes EKHBX0008AA 4G Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm² In accordance with EN/IEC 61000-3-11(*), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys(**) <= Zmax (*) European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A (**) System impedance 26 • AlthermaTM • Indoor units • Indoor units • EKHBH-X008AA 3 Options Factory mounted optional equipment for EKHB(H/X)008AA** Reference 1 Description Heating only model EKHBH008A... Reversible model EKHBX008A... Back up heater 3kW 1∼230 V Back up heater 6kW 1∼230 V Back up heater 6kW 3∼400 V Back up heater 6kW 3∼230 V Back up heater 9kW 3∼400 V Back up heater 9kW 3∼230 V 3V3 6V3 6WN 6T1 9WN 9T1 A3V3 A3V3 V ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ A6V3 ⎯ V ⎯ ⎯ ⎯ ⎯ A6V3 ⎯ V ⎯ ⎯ ⎯ ⎯ A6WN ⎯ ⎯ V ⎯ ⎯ ⎯ A6WN ⎯ ⎯ V ⎯ ⎯ ⎯ A6T1 ⎯ ⎯ ⎯ V ⎯ ⎯ A6T1 ⎯ ⎯ ⎯ V ⎯ ⎯ A9WN A9WN ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ A9T1 ⎯ ⎯ ⎯ ⎯ ⎯ V A9T1 ⎯ ⎯ ⎯ ⎯ ⎯ V 3 Outdoor combination table for EKHB(H/X) 008AA** EKHBH008AA* EKHBX008AA* Heating only indoor unit Reversible indoor unit ERHQ006ADV3(8) V V ERHQ007ADV3(8) V V ERHQ008ADV3(8) V V Bottom plate heater (1) (3) drain plug kit (3) drain stop kit (3) ERHQ006ADV3 V V V ERHQ007ADV3 V V V ERHQ008ADV3 V V V A3V3 A6V3 Kit availability for ERHQ006-008AD* EKBPHT08 EKDK02 EKDK03 Kit availability for EKHB(H/X)008AA* Reference Description EKHWS150(A/B)3V3 EKHWS200(A/)B3V3 EKHWS300(A/B)3V3 EKHWS200(A/B)3Z2 EKHWS300(A/B)3Z2 EKHWSU150(A/B)3V3 EKHWSU200(A/B)3V3 EKHWSU300(A/B)3V3 EKHWE150A3V3 EKHWET150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 EKHBDP EKRP1HB EKRTW EKRTR EKRTETS Heating only model EKHBH008A... Reversible model EKHBX008A... Domestic hot water tank 150l 1-230V Domestic hot water tank 200l 1-230V Domestic hot water tank 300l 1-230V Domestic hot water tank 200l 2-400V Domestic hot water tank 300l 2-400V Domestic hot water tank 150l 1-230V Domestic hot water tank 200l 1-230V Domestic hot water tank 300l 1-230V Enamel domestic hot water tank 150l 1∼230V Wallmounted enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V Option kit for condensate free cooling operation Digital I/O PCB (2) Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (4) A3V3 V V V V V V V V V V V V V V V V V V V V V A6V3 V V V V V V V A6WN V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) A6WN V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) A6T1 V V V V V V V A6T1 V V V V V V V A9WN A9WN V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) A9T1 V V V V V V V A9T1 V V V V V V V V V V V V(*) V(*) V V V(*) V(*) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V(*) V(*) V V V V V V V(*) V(*) V V V V V V V V V V V V V V V V V V V V V(*) V(*) V V V V V V V(*) V(*) V V V V V V V V V V V V V V V V V V V V 150(A/B) 200(A/B) 300(A/B) V V V - V - (*) If neutral line is available Kit available for EKHWS* Reference EKUHWA EKUHWB EKUHW2WB EKSOLHWAV1 EKWBSWW150 Description EKHWE(T)*3(V3/Z2) EKHWS*3(V3/Z2) EKHWSU*3V3 Option kit for UK EKHWSU150-300V3 Option kit 1 for UK EKHWSU150-300V3 (8) Option kit 2 for UK EKHWSU150-300V3 (8) Solarkit (5) Wall bracket for EKHWS(U)150(A/B)3V3 or EKSWW150V3 150A 200A 300A V V V - V - 150A V V(6) V(6) V V 200A V V(6) V(6) V - 300A V V(6) V(6) V - 150B V V V(7) V V 200B V V V(7) V - 300B V V V(7) V - Remarks: Other combinations than mentioned in this option TW are not guaranteed. (1) Heater tape that can be fixed on the bottom plate to prevent ice formation. (2) Address card that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included. (3) It is not allowed to combine bottom plate heater and drain plug/stop kit (4) EKRTETS can only be used in combination with EKRTR (5) Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. (6) If installation on tank A version both kits are required (7) Kit is only necessary when installing EKSOLHWAV1 on a UK tank B-series (EKHWSU(150/200/300)B3V3) (8) EKUHWB = EKUHWA - (2 way valve and 2 way valve accessories) EKUHW2WB = 2 way valve and 2 way valve accessories 3TW57789-2G • AlthermaTM • Indoor units 27 • Indoor units • EKHBH-X008AA 1 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHBH008AA FIXATION 4 Service door (Closed) 361 (Open) 553 G 1 (Male) Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection G 1 1/2 (female) j 4 Water OUT connection G 1 1/2 (female) j 5 Power supply intake (+ domestic hot water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J6.35 flare connection j 14 Shut off valves with drain/fill valve (accessory delivered with unit) j 15 Holes for fixation j 16 Switchbox terminals j 17 Switchbox terminals option domestic hot water tank j 18 Wallbracket Dimensions wallbracket Minimum space for service & ventilation Min. 150 Min. 200 3TW57784-1A EKHBX008AA FIXATION Service door (Closed) 361 (Open) 553 G 1 (Male) Dimensions wallbracket Minimum space for service & ventilation Min. 150 Min. 200 Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection G 1 1/2 (female) j 4 Water OUT connection G 1 1/2 (female) j 5 Power supply intake (+ domestic hot water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J6.35 flare connection j 14 Shut off valves with drain/fill valve (accessory delivered with unit) j 15 Holes for fixation j 16 Switchbox terminals j 17 Switchbox terminals option domestic hot water tank j 18 Wallbracket 3TW57784-2A 28 • AlthermaTM • Indoor units • Indoor units • EKHBH-X008AA 5 Piping diagram EKHBH(X)008AA R4T R3T R2T R1T Water side 1 Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat-exchanger thermistor Field installation 5 Filter Inlet Shut off valve Refrigerant side Safety valve Drain valve Pressure gauge Drain Expansion vessel Cooling (EKHBX) Heating (EKHBX + EKHBH) Option backup heater Drain valve Field installation Air purge Flowswitch Pump Outlet Shut off valve Overview Electric heater body Evaporator Condensor Outdoor unit Refr. out Refr. in Water inlet Refrigerant side Water side Refr. in Water outlet Refr. out O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe • AlthermaTM • Indoor units 3TW56715-1 29 • Indoor units • EKHBH-X008AA 1 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)008AA3V3 Power supply 230V 1N∼50Hz Only for EKSOLHWAV1 Option Outdoor unit Solar pump connection >> See note 2 << Domestic hot water tank Only See note 9 6 for EKHW Option Only for EKHW(S/E) Option See note 7 For EKHWSU*V3 Option User interface Alarm output Solar input Cooling/heating on/off output Only for EKHW Option Only for EKRTW Option 230V AC heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 Domestic hot supply from PCB Only for EKRTR Option water tank Only for EKHWS*V3 Option See note 7 For EKHWSU*V3 Option 3 wire type (SPST) Only for EKSOLHWAV1 Option Only for EKHW Option NO valve Only for EKHW(S/E) Option for EKRTETS Option F1B NC valve F2B : Terminal strips : Spark suppression 2 : Spark suppression 1 : Fuse 3.15A T 250V : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Earth leakage protector : Thermal protector booster heater : Thermal protector backup heater : Solar pumpstation relay : DIP switch : Transformer 24V for PCB : Domestic hot water thermistor : Inlet water thermistor : Refrigerant liquid side thermistor : Outlet water backup heater thermistor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Humidity sensor : Ambient sensor : Flowswitch : Booster heater (3kW) : Backup heater element 1 : 3way valve: floorheating/domestic hot water : 2 way valve for cooling mode : Pump : Optocoupler input circuit : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M : Contactor backup heater Step 1 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse backup heater A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB Electric heater fuse 20A Only Example field supply thermostat X1M-X9M V2S V1S FU1 FU2 FuS, FuR Q1DI Q2L Q1L S1S SS1 TR1 R5T R4T R3T R2T R2T (EKRTETS) R1T R1H (EKRTR) R1T (EKRTW/R) S1L E4H E1H M3S M2S M1P PHC1 K5M EKHW kit fuse 20A Notes: 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. (L,N) 9 For EKSOLHWAV1, refer to option manual Domestic hot water tank Only for EKHWE*V3 Option Wiring dependent on model Field wiring PCB Option Field wiring Wire colour 3TW57786-2B EKHBH(X)008AA6V3 Outdoor unit Power supply 230V 1N∼50Hz Only for EKSOLHWAV1 Option Domestic hot water Solar pump connection >> See note 2 << See note 9 tank Only for EKHWE*Option Only for EKHW(S/E)*Option See note 7 For EKHWSU*V3 Option User interface Only for EKRP1HB & EKSOLHWAV1 Option See note 8 heating cooling Solar input Alarm output Cooling/heating on/off output Only for EKHW Option Only for EKRTW* Option 230V AC supply from PCB Only for EKRTR* Option Domestic hot water tank 3 wire type (SPST) Only forEKHWS*V3 Option See note 7 For EKHWSU*V3 Option NO valve Only for EKHW Option Only for EKSOLHWAV1 Option Only for EKHW(S/E)* Option Electric heater fuse 32A F1B Only for EKRTETS* Option Example field supply thermostat NC valve F2B X1M-X9M : Terminal strips V2S : Spark suppression 2 V1S : Spark suppression 1 FU1 : Fuse 3.15A T 250V FU2 : Fuse 5A T 250V FuS, FuR : Fuse 5A 250V for solar/remote alarm PCB Q1DI : Earth leakage protector Q2L : Thermal protector booster heater Q1L : Thermal protector backup heater S1S : Solar pumpstation relay SS1 : DIP switch TR1 : Transformer 24V for PCB R5T : Domestic hot water thermistor R4T : Inlet water thermistor R3T : Refrigerant liquid side thermistor R2T : Outlet water backup heater thermistor R2T (EKRTETS) : External sensor (floor or ambient) R1T : Outlet water heat-exchanger thermistor R1H (EKRTR) : Humidity sensor R1T (EKRTW/R) : Ambient sensor S1L : Flowswitch E4H : Booster heater (3kW) E1H-E2H : Backup heater element 1-2 M3S : 3way valve: floorheating/domestic hot water M2S : 2 way valve for cooling mode M1P : Pump PHC1 : Optocoupler input circuit K5M : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M/K2M : Contactor backup heater step 1/2 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse backup heater A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB EKHW kit fuse 20A Domestic hot water tank Notes: See note 7 For EKHWE Option Wiring dependent on model Field wiring Option Field wiring PCB Wire colour 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. (N,L) 9 For EKSOLHWAV1, refer to option manual 3TW57786-3B 30 • AlthermaTM • Indoor units • Indoor units • EKHBH-X008AA 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)008AA6WN/9WN Power supply 3(/N)∼400(/230V) 50Hz Domestic hot water tank Only for EKSOLHWAV1 Option Outdoor unit 1 Domestic hot water tank Solar pump connection >> See note 2 << Only See note 9 for EKHWE Option 6 Only for EKHWS*Z2 Option Only for EKHW(S/E)* Option See note 7 Only for EKHW Option Only for EKRTW Option 230V AC heating cooling Only for EKRP1HB & ESOLHWAV1 Option See note 8 supply from PCB Only for EKRTR* Option Domestic hot water tank Domestic hot water tank User interface Solar input Cooling/heating on/off output Alarm output For EKHWSU*V3 Option 3 wire type (SPST) Only for EKHW Option NO valve Only for EKHW(S/E)* Option Only forEKHS*V3 Only forEKHWS*Z2 Option Option See note 7 For EKHWSU*V3 Option Only for EKRTETS* Option Model F1B Example field supply thermostat Only for EKSOLHWAV1 Option Electric heater fuse 6WN 16A X1M-X9M V2S V1S FU1 FU2 FuS, FuR Q1DI Q2L Q1L S1S SS1 TR1 R5T R4T R3T R2T R2T (EKRTETS) R1T R1H (EKRTR) R1T (EKRTW/R) S1L E4H E1H-E3H M3S : Terminal strips : Spark suppression 2 : Spark suppression 1 : Fuse 3.15A T 250V : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Earth leakage protector : Thermal protector booster heater : Thermal protector backup heater : Solar pumpstation relay : DIP switch : Transformer 24V for PCB : Domestic hot water thermistor : Inlet water thermistor : Refrigerant liquid side thermistor : Outlet water backup heater thermistor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Humidity sensor : Ambient sensor : Flowswitch : Booster heater (3kW) : Backup heater element 1-3 : 3way valve: floorheating/domestic hot water M2S : 2 way valve for cooling mode M1P : Pump PHC1 : Optocoupler input circuit K5M : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M/K2M : Contactor backup heater step 1/2 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse backup heater A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB 9WN 20A NC valve F2B EKHW kit fuse 20A Notes: Domestic hot water tank Domestic hot water tank Only forEKHWE*V3 Option Only forEKHWE*Z2 Option Wiring dependent on model Field wiring Option PCB Field wiring Wire colour 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. (N,L) 9 For EKSOLHWAV1, refer to option manual 3TW57786-4B EKHBH(X)008AA6T1/9T1 Power supply 3∼230V 50Hz >> See note 2 << Only for EKSOLHWAV1 Option Outdoor unit Domestic hot water Solar pump connection See note 9 tank Only for EKHWE Option Only for EKHW(S/E) Option Only for EKHW Option Only for EKRTW Option Only for EKRP1HB & EKSOLHWAV1 Option See note 8 230V AC heating cooling Alarm output User interface Solar input Cooling/heating on/off output See note 7 For EKHWSU*V3 Option supply from PCB Only for EKRTR Option Domestic hot water tank 3 wire type (SPST) Only for EKHW Only for EKSOLHWAV1 Option Option NO valve Only for EKHW(S/E) Option Only for EKHWS*V3 Option See note 7 For EKHWSU*V3 Option Only for EKRTETS Option Example field supply thermostat Model F1B Electric heater fuse 6T1 20A X1M-X9M V2S V1S FU1 FU2 FuS, FuR Q1DI Q2L/Q3L Q1L S1S SS1 R5T R4T R3T R2T R2T (EKRTETS) R1T R1H (EKRTR) R1T (EKRTW/R) S1L E4H E1H-E3H M3S M2S M1P PHC1 K5M : Terminal strips : Spark suppression 2 : Spark suppression 1 : Fuse 3.15A T 250V : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Earth leakage protector : Thermal protector booster heater : Thermal protector backup heater : Solar pumpstation relay : DIP switch : Domestic hot water thermistor : Inlet water thermistor : Refrigerant liquid side thermistor : Outlet water backup heater thermistor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Humidity sensor : Ambient sensor : Flowswitch : Booster heater (3kW) : Backup heater element 1-3 : 3way valve: floorheating/domestic hot water : 2 way valve for cooling mode : Pump : Optocoupler input circuit : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M/K2M : Contactor backup heater step 1/2 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse backup heater A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB 9T1 32A NC valve F2B EKHW kit fuse 20A Notes: Domestic hot water tank Only for EKHWE*V3 Option Wiring dependent on model Field wiring Option Field wiring PCB Wire colour 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. (L,N) 9 For EKSOLHWAV1, refer to option manual 3TW57786-6B • AlthermaTM • Indoor units 31 • Indoor units • EKHBH-X008AA 1 6 6 Wiring diagram 6-2 External connection diagram EKHBH(X)008AA Standard parts Power supply Outdoor unit 3 core Unit power supply: 230V + earth For more details please check unit wiring diagram X1M:L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Optional power supply X2M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth 4 core 3 or4 core 3 core Optional parts Field supply X1M:9-10-11-Earth Sanitary tank 2 way valve 2 core Q3L - Q1T Clixon Thermostat 2 way valve Only for EKSWWU*V3 Power supply booster heater 5 core 230V or400V Q2L - Clixon booster heater NO valve: NC valve: 2 core Thermistor cable Note: min. distance to power cable = 3cm Room thermostat A3P (optional) 2 core 2 core R5T - Thermistor water temperature Signal 4 core X1M:7-8-Earth 2 way valve M2S (EKHBX Units) for cooling mode 3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating Indoor unit User interface 3TW56719-6A 32 • AlthermaTM • Indoor units • Indoor units • EKHBH-X008AA 7 Operation range Outdoor temp. (°CDB) EKHBH(X)008AA ERHQ006-008AD 1 Cooling mode 7 Leaving evaporator water temperature (°C) Outdoor temp. (°CDB) Heating mode : Units with optional back up heater Leaving condenser water temperature (°C) 50 Domestic hot water Outdoor temp. (°CDB) : Booster heater operation only : Units with optional back up heater or booster heater operation only Water temperature sanitary tank (°C) 4TW57553-1A • AlthermaTM • Indoor units 33 • Indoor units • EKHBH-X008AA 1 8 Hydraulic performance 8-1 Static pressure drop unit EKHBH(X)008AA ESP [kPa] 8 Flow (l/min) III: High speed II: medium speed I: Low speed ESP: External static pressure Flow: waterflow through the unit Warning: 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. 4TW57789-1 34 • AlthermaTM • Indoor units EEDEN09-720 technical data AlthermaTM Part 2/4: ERHQ011-016AA ERHQ011-016AAW1 EKHBH(X)016AB • Outdoor units • ERHQ011-016AAV3 TABLE OF CONTENTS ERHQ011-016AAV3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 3 Heating capacity tables Cooling capacity tables 4 39 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 44 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 45 5 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 6 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Wiring diagram 7 8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Service space 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • AlthermaTM • Outdoor units 49 51 37 • Outdoor units • ERHQ011-016AAV3 1 A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H uRl EA•O Features Single phase large capacity outdoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 2 1 38 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAV3 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT ERHQ011AA ERHQ014AA ERHQ016AA For combination indoor units + outdoor units Indoor Units Condition 1 Heating capacity Nominal kW 11.2 14.0 16.0 Heating PI Nominal kW 2.46 3.17 3.83 COP Nominal 4.55 4.42 4.18 Heating capacity Nominal kW 10.3 13.1 15.2 Heating PI Nominal kW 3.06 3.88 4.66 COP Nominal 3.37 3.38 3.26 Nominal Capacity EKHBH016AB 2 For combination indoor units + outdoor units Indoor Units Condition 1 Heating capacity Nominal kW 11.2 14.0 16.0 Cooling capacity Nominal kW 13.9 17.3 17.8 Heating PI Nominal kW 2.46 3.17 3.83 Cooling PI Nominal kW 3.79 5.78 6.77 COP Nominal 4.55 4.42 4.18 Nominal Capacity 2 EKHBX016AB EER Nominal 3.67 2.99 2.63 Heating capacity Nominal kW 10.3 13.1 15.2 Cooling capacity Nominal kW 10.0 12.5 13.1 Heating PI Nominal kW 3.06 3.88 4.66 Cooling PI Nominal kW 3.60 5.29 5.95 COP Nominal 3.37 3.38 3.26 EER Nominal 2.78 2.36 2.20 Notes Condition 1: cooling Ta 35°C - LWE 18°C - heating Ta DB/WB 7°C/6°C - LWC 35°C ( DT = 5°C ) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) 2-2 TECHNICAL SPECIFICATIONS Casing ERHQ011AA Colour Unit Packing Weight Packing ERHQ016AA Ivory white Material Dimensions ERHQ014AA Painted galvanised steel plate Height mm Width mm 900 1,170 900 900 Depth mm 320 320 320 Height mm Width mm 980 1,349 980 980 Depth mm 420 420 420 Unit kg 103 103 103 Packed Unit kg 114 114 114 Material EPS Carton Wood PP (Straps) Weight kg 11 • AlthermaTM • Outdoor units 11 11 39 • Outdoor units • ERHQ011-016AAV3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Heat Exchanger Dimensions Length mm Nr of Rows Fin Pitch 2 mm Nr of Passes Face Area 2 m² Nr of Stages ERHQ011AA ERHQ014AA ERHQ016AA 857 857 857 2 2 2 1.4 1.4 1.4 6 6 6 0.98 0.98 0.98 52 52 52 Tube type Fin Hi-XSS(8) Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 2 Air Flow Rate (nominal at 230V) Heating High m³/min 90 90 90 Cooling High m³/min 96 100 97 Fan Discharge direction Motor 2 Horizontal Quantity 2 Model Motor Fan Speed (nominal) Steps Motor 8 8 8 760 760 760 Cooling rpm 800 850 830 Output W 70 70 70 Direct drive Quantity Motor 1 Model W 2,200 Starting Method Operation Range Heating Cooling Sanitary water Sound Level (nominal) Refrigerant Inverter driven Output W 33 33 33 Min °CWB -20 -20 -20 Max °CWB 35 35 35 Min °CDB 10 10 10 Max °CDB 46 46 46 -20 Min °CDB -20 -20 Max °CDB 43 43 43 Sound Power dBA 64 64 66 Sound Pressure dBA 49 51 53 Sound Power dBA 64 66 69 Sound Pressure dBA 50 52 54 Heating Sound Pressure dBA 42 42 43 Cooling Sound Pressure dBA 45 45 46 kg 3.7 Heating Cooling Sound Level (Night quiet) Type Charge R-410A Control 40 1 Type Charged Volume 3.7 3.7 Expansion valve(electronic type) Nr of Circuits Refrigerant Oil 1 Hermetically sealed scroll compressor Motor Output Crankcase Heater 1 JT100G-VD Type Motor 2 rpm Heating Drive Compressor 2 Brushless DC motor 1 1 Daphne FVC68D l 1.0 • AlthermaTM • Outdoor units 1.0 1.0 • Outdoor units • ERHQ011-016AAV3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Piping connections Liquid (OD) Quantity ERHQ011AA ERHQ014AA ERHQ016AA 1 1 1 Type Flare connection Diameter (OD) Gas mm Quantity 9,52 1 Type mm Quantity 2 3 3 3 Hole Diameter (OD) mm Minimum 26 26 26 m 5 5 5 Maximum m 75 75 75 Equivalent m 95 95 95 Chargeless m 30 30 30 Additional Refrigerant Charge Installation height difference 2 15,9 Type Piping Length 1 Flare connection Diameter (OD) Drain 1 kg/m Maximum m See installation manual outdoor unit 4PW37976-1B 30 Heat Insulation 30 30 Both liquid and gas pipes Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method Inverter controlled Safety Devices Fan motor thermal protector Fuse High pressure switch Standard Accessories Item Tie-wraps Quantity 2 Item 2 2 Installation manual Quantity 1 Notes 1 1 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Down to 3m with recharging of the outdoor unit. Refer to the installation manual of the outdoor unit. 2-3 ELECTRICAL SPECIFICATIONS Power Supply ERHQ011AA Name 1~ Frequency Hz 50 50 50 Voltage V 230 230 230 Voltage range Minimum V -10% Maximum V +10% Minimum Ssc value Maximum running Current kVa Cooling Recomended fuses Wiring connections For Power Supply Equipment complying with EN/IEC 61000-S-12 (1) A 22.8 A 32 27.4 31.9 32 32 Remark See installation manual outdoor unit 4PW37976-1B For connection Remark with indoor See installation manual outdoor unit 4PW37976-1B Power Supply Intake Notes ERHQ016AA V3 Phase Current ERHQ014AA Outdoor unit only (1) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase. • AlthermaTM • Outdoor units 41 • Outdoor units • ERHQ011-016AAV3 3 Capacity tables 3-1 Heating capacity tables Maximum Heating Capacity (Peak values) Model 2 3 ERHQ11 ERHQ14 ERHQ16 LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 30 HC 5.66 6.48 8.04 9.18 10.2 11.6 13.1 14.1 15.9 7.24 8.19 10.1 11.5 12.7 14.4 16.3 17.6 19.9 8.35 9.38 11.5 13.0 14.4 16.3 18.5 20.0 22.5 35 PI 2.17 2.21 2.24 2.24 2.23 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.87 2.87 2.88 2.86 2.85 2.82 3.25 3.33 3.42 3.46 3.48 3.50 3.51 3.51 3.50 HC 5.48 6.25 7.74 8.84 9.81 11.2 12.7 13.6 15.4 7.14 8.01 9.78 11.1 12.3 14.0 15.9 17.1 19.3 8.31 9.33 11.3 12.7 14.1 16.0 18.1 19.5 22.0 40 PI 2.37 2.42 2.46 2.47 2.47 2.46 2.43 2.41 2.36 2.97 3.04 3.11 3.14 3.16 3.17 3.16 3.15 3.13 3.54 3.63 3.73 3.78 3.81 3.83 3.85 3.86 3.85 HC 5.44 6.17 7.63 8.71 9.68 10.8 12.2 13.2 14.9 7.05 7.85 9.51 11.1 12.2 13.5 15.4 16.5 18.7 8.27 9.28 11.1 12.5 13.8 15.6 17.6 19.0 21.4 PI 2.37 2.42 2.46 2.33 2.39 2.46 2.43 2.41 2.36 2.97 3.04 3.11 2.96 3.05 3.17 3.16 3.15 3.13 3.54 3.63 3.64 3.56 3.45 3.83 3.85 3.86 3.85 HC 4.84 5.49 6.54 7.06 7.75 10.8 12.2 13.2 14.9 6.28 6.99 7.62 8.95 9.65 13.5 15.4 16.5 18.7 7.36 8.26 8.63 10.1 10.6 15.6 17.6 19.0 21.4 45 PI 2.61 2.67 2.72 2.74 2.74 2.74 2.72 2.70 2.65 3.26 3.34 3.43 3.47 3.48 3.50 3.50 3.50 3.48 3.89 3.98 4.10 4.15 4.19 4.22 4.24 4.25 4.25 50 55 HC PI HC PI HC PI 7.50 8.57 9.52 10.3 11.8 12.7 14.4 3.02 3.05 3.06 3.06 3.04 3.03 2.99 8.18 9.10 9.94 11.3 12.2 13.8 3.36 3.38 3.42 3.41 3.40 3.37 8.72 9.53 10.9 11.7 13.3 3.77 3.82 3.81 3.81 3.78 9.25 10.7 11.8 13.1 14.9 16.0 18.1 3.79 3.74 3.76 3.88 3.89 3.89 3.87 10.4 11.4 12.7 14.4 15.5 17.5 4.14 4.17 4.30 4.32 4.32 4.31 11.1 12.3 13.9 15.0 17.0 4.62 4.77 4.79 4.80 4.80 10.9 12.2 13.5 15.2 17.2 18.5 20.8 4.52 4.58 4.62 4.66 4.69 4.69 4.70 12.0 13.1 14.8 16.7 18.0 20.3 5.06 5.11 5.15 5.18 5.20 5.21 11.9 13.4 15.1 16.6 18.7 5.35 5.40 5.44 5.75 5.77 HC PI HC PI HC PI 6.43 6.94 7.63 10.3 11.8 12.7 14.4 3.02 2.87 2.96 3.06 3.04 3.03 2.99 6.63 7.29 9.94 11.3 12.2 13.8 3.17 3.26 3.42 3.41 3.40 3.37 6.99 9.53 10.9 11.7 13.3 3.64 3.82 3.81 3.81 3.78 7.42 8.65 9.32 13.1 14.9 16.0 18.1 3.79 3.52 3.64 3.88 3.89 3.89 3.87 8.38 9.02 12.7 14.4 15.5 17.5 3.90 4.03 4.30 4.32 4.32 4.31 8.73 12.3 13.9 15.0 17.0 4.47 4.77 4.79 4.80 4.80 8.49 9.91 10.4 15.2 17.2 18.5 20.8 4.41 4.31 4.18 4.66 4.69 4.69 4.70 9.71 10.2 14.8 16.7 18.0 20.3 4.77 4.62 5.15 5.18 5.20 5.21 9.19 13.4 15.1 16.6 18.7 4.84 5.40 5.44 5.75 5.77 Maximum Heating Capacity (integrated values*) Model ERHQ11 ERHQ14 ERHQ16 LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 30 HC 5.04 5.77 6.89 7.43 8.16 11.6 13.1 14.1 15.9 6.45 7.29 8.06 9.27 10.0 14.4 16.3 17.6 19.9 7.44 8.35 8.91 10.5 11.1 16.3 18.5 20.0 22.5 35 PI 2.17 2.21 2.24 2.11 2.16 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.70 2.78 2.88 2.86 2.85 2.82 3.25 3.33 3.34 3.26 3.15 3.50 3.51 3.51 3.50 HC 4.88 5.56 6.63 7.16 7.86 11.2 12.7 13.6 15.4 6.35 7.13 7.84 9.00 9.71 14.0 15.9 17.1 19.3 7.39 8.30 8.77 10.3 10.9 16.0 18.1 19.5 22.0 40 45 PI 2.61 2.67 2.72 2.58 2.65 2.74 2.72 2.70 2.65 3.26 3.34 3.43 3.26 3.37 3.50 3.50 3.50 3.48 3.86 3.98 4.00 3.91 3.79 4.22 4.24 4.25 4.25 Symbols HC PI LWC Tamb 42 55 3TW57752-1B Conditions : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% Note 1 50 For the optional model with heatertape (V38) when ambient temperature becomes lower than 4°C: add power input of 95W • AlthermaTM • Outdoor units 1 2 Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). • Outdoor units • ERHQ011-016AAV3 3 Capacity tables 3-2 Cooling capacity tables Maximum Cooling Capacity ERHQ11 ERHQ14 ERHQ16 Tamb (°C) LWE (°C) 7 10 13 15 18 22 7 10 13 15 18 22 7 10 13 15 18 22 20 CC 11.7 12.9 14.1 14.9 16.2 18.0 14.5 16.0 17.6 18.6 20.2 22.5 15.3 16.9 18.5 19.6 21.0 23.3 25 PI 2.56 2.58 2.59 2.60 2.61 2.62 3.85 3.94 4.02 4.08 4.17 4.29 4.37 4.48 4.60 4.68 4.97 5.21 CC 11.2 12.3 13.4 14.2 15.5 17.2 13.9 15.3 16.8 17.8 19.3 21.5 14.7 16.2 17.7 18.7 20.0 22.2 30 PI 2.86 2.89 2.92 2.93 2.96 2.99 4.27 4.37 4.47 4.54 4.65 4.80 4.84 4.97 5.10 5.19 5.52 5.79 CC 10.6 11.6 12.8 13.5 14.7 16.4 13.2 14.6 15.9 16.9 18.4 20.4 13.9 15.3 16.7 17.7 18.9 21.0 35 PI 3.21 3.25 3.29 3.31 3.35 3.40 4.75 4.86 4.98 5.06 5.18 5.36 5.37 5.51 5.66 5.76 6.12 6.42 CC 10.0 11.0 12.1 12.8 13.9 15.5 12.5 13.7 15.0 15.9 17.3 19.3 13.1 14.4 15.7 16.6 17.8 19.7 Symbols CC PI LWE Tamb CC 9.39 10.3 11.3 12.0 13.1 14.7 11.7 12.9 14.1 14.9 16.2 17.0 12.2 13.3 14.6 15.4 16.4 17.0 45 PI 4.03 4.09 4.15 4.20 4.26 4.35 5.90 6.04 6.18 6.28 6.44 5.33 6.59 6.75 6.93 7.04 6.69 5.33 CC 8.75 9.65 10.6 11.3 12.3 13.3 11.1 11.2 11.9 12.2 12.9 13.3 11.1 11.2 11.9 12.2 12.9 13.3 PI 4.50 4.58 4.65 4.70 4.78 3.93 5.92 5.46 5.04 4.79 4.42 3.93 5.92 5.46 5.04 4.79 4.42 3.93 2 3 3TW57752-1B Conditions : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Ambient temperature (°C) RH=85% Note 1 40 PI 3.60 3.65 3.70 3.73 3.79 3.86 5.29 5.42 5.55 5.64 5.78 5.98 5.95 6.11 6.27 6.38 6.77 7.10 1 2 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For the optional model with heatertape (V38) when ambient temperature becomes lower than 4°C: add power input of 95W • AlthermaTM • Outdoor units 43 • Outdoor units • ERHQ011-016AAV3 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing ERHQ011-016 Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8 2 4 Gas pipe connection ∅15.9 flare Liquid pipe connection ∅9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole ∅34) control wiring intake (knock out hole ∅27) Drain outlet 3TW57764-1 44 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAV3 4 Dimensional drawing & centre of gravity 4-2 Centre of gravity ERHQ011-016 2 4 4TW57919-5 • AlthermaTM • Outdoor units 45 • Outdoor units • ERHQ011-016AAV3 5 Piping diagram ERHQ011-016AAV3 2 Electronic expansion valve 5 Filter Filter Heat exchanger 4-Way-Valve High Pressure Low Pressure Switch Sensor EKHB 016 Field Piping ø9.5 C 1220T-0 Service Port 5/16’ Compressor Field Piping ø15.9 C 1220T-0 Accumulator Outdoor Unit Indoor Unit Heating Cooling Stop Valve (With Service Port 5/16’ Flare) Check Valve Flare Conn. Screw Conn. Flange Conn. Pinched Pipe Spinned Pipe 3TW57765-1 46 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAV3 6 Wiring diagram 6-1 Wiring diagram ERHQ011-016AAV3 Option EKBPHT16Y Only for *RHQ01*AAV3(7) Only for *RHQ01*AAV38 Indoor Outdoor (Note 4) HAP Position of compressor El. comp. Assy (Position of elements) terminal Wire entrance Notes: 1 This wiring diagram only applies to the outdoor unit 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Relay connector p : Noiseless earth G : Terminal 4 Refer to the option manual, for connecting wiring to x6A. 5 Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch. 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches by service. When the unit is shipped by factory all switches are set to be off. 9 Option (Back) A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U H1P∼7P (A2P) HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1C∼Z3C Z1F∼Z4F Optional Connector X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Electrical heatertape (fuse: 5A/250V) Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip for power source Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter 2 6 Connector (Front) Wiring dependent on model 2TW57986-1A • AlthermaTM • Outdoor units 47 • Outdoor units • ERHQ011-016AAV3 7 Sound data 7-1 Sound pressure spectrum ERHQ011-016 ERHQ011AAV3 HEATING ERHQ014AAV3 HEATING ERHQ016AAV3 HEATING 2 Octave band center frequency (Hz) Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) 7 Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-2A NOTES 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (Discharge side) ERHQ011-016 ERHQ014AAV3 COOLING Octave band center frequency (Hz) ERHQ016AAV3 COOLING Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) ERHQ011AAV3 COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-1A NOTES 1 2 3 4 48 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. • AlthermaTM • Outdoor units Measuring location (Discharge side) • Outdoor units • ERHQ011-016AAV3 7 Sound data 7-2 Sound pressure night quiet mode ERHQ011-016 ERHQ011AAV3 HEATING ERHQ014AAV3 HEATING ERHQ016AAV3 HEATING 2 Octave band center frequency (Hz) Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) 7 Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-4 NOTES 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (Discharge side) ERHQ011-016 ERHQ014AAV3 COOLING Octave band center frequency (Hz) ERHQ016AAV3 COOLING Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) ERHQ011AAV3 COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-3 NOTES 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. • AlthermaTM • Outdoor units Measuring location (Discharge side) 49 • Outdoor units • ERHQ011-016AAV3 8 Installation 8-1 Service space ERHQ011-016 A. Non stacked installation Legend 2 Unit: mm Suction side obstacle 8 Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 50 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAV3 9 Operation range ERHQ011-016AAV3 Outdoor temp. (°CDB) 2 Cooling mode 9 Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) Heating mode No heat pump operation, back up heater only * ERHQ_V18 units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the ERHQ_V3 models may experience problems with severe ice build up on the aircooled coil. In case such conditions are expected, the ERHQ-V38 must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. leaving condensor Water temperature (°C) Domestic hot water mode Outdoor temp. (°CDB) Booster heater operation only Water temperature domestic hot water tank (C°) 4TW57753-1B • AlthermaTM • Outdoor units 51 • Outdoor units • ERHQ011-016AAW1 TABLE OF CONTENTS ERHQ011-016AAW1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 3 Heating capacity tables Cooling capacity tables 4 55 57 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 60 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 61 5 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 6 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Wiring diagram 7 8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Service space 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • AlthermaTM • Outdoor units 65 67 53 • Outdoor units • ERHQ011-016AAW1 1 A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H uRl EA•O Features Three phase large capacity outdoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 2 1 54 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAW1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT For combination indoor units + outdoor units Condition 1 Nominal Capacity For combination indoor units + outdoor units Condition 1 Nominal Capacity ERHQ011AAW1 Indoor Units ERHQ014AAW1 ERHQ016AAW1 EKHBH016AB Heating capacity Nominal kW 11.32 14.50 16.05 Heating PI Nominal kW 2.54 3.33 3.73 2 COP Nominal 4.46 4.35 4.30 2 Heating capacity Nominal kW 10.98 13.57 15.11 Heating PI Nominal kW 3.15 4.12 4.60 COP Nominal 3.48 3.29 3.29 Indoor Units EKHBX016AB Heating capacity Nominal kW 11.32 14.50 16.05 Cooling capacity Nominal kW 15.05 16.06 16.76 Heating PI Nominal kW 2.54 3.33 3.73 Cooling PI Nominal kW 4.44 5.33 6.06 COP Nominal 4.46 4.35 4.30 EER Nominal Heating capacity Nominal 3.39 3.01 2.76 kW 10.98 13.57 15.11 Cooling capacity Nominal kW 11.72 12.55 13.12 Heating PI Nominal kW 3.15 4.12 4.60 Cooling PI Nominal kW 4.22 5.00 5.65 COP Nominal 3.48 3.29 3.29 EER Nominal 2.78 2.51 2.32 Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C) - heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) 2-2 TECHNICAL SPECIFICATIONS Casing ERHQ011AAW1 Colour Unit Packing ERHQ016AAW1 Ivory white Material Dimensions ERHQ014AAW1 Painted galvanised steel plate Height mm Width mm 900 1,345 900 900 Depth mm 320 320 320 Height mm Width mm 980 980 980 Depth mm 420 420 420 1,524 Weight Unit kg 108 (ERHQ*W1*)110 (ERHQ*W18*) Packed Unit kg 120 (ERHQ*W1*)122 (ERHQ*W18*) Packing Material EPS Carton Wood PP (Straps) Weight Heat Exchanger Dimensions Length kg 12 12 12 mm 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 Nr of Rows Fin Pitch Nr of Passes Face Area Nr of Stages 60 Tube type Fin Hi-XSS(8) Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 Discharge direction Motor 2 2 Horizontal Quantity Model • AlthermaTM • Outdoor units 2 2 2 Brushless DC motor 55 • Outdoor units • ERHQ011-016AAW1 2 2-2 Specifications TECHNICAL SPECIFICATIONS Motor Speed (nominal) ERHQ011AAW1 ERHQ014AAW1 8 8 8 rpm 760 760 760 Cooling rpm 780 780 780 Output W 70 70 70 Steps Heating 2 2 Fan Motor Drive Compressor Direct drive Quantity Motor 1 1 Model JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 1 2,200 Starting Method Inverter driven Motor Crankcase Heater Output W 33 33 33 Operation Range Heating Min °CWB -20 -20 -20 Max °CWB 35 35 35 Min °CDB 10 10 10 Max °CDB 46 46 46 Min °CDB -20 -20 -20 Max °CDB 43 43 43 Sound Power dBA 64 64 66 Sound Pressure 51 51 52 Cooling Sanitary water Sound Level (nominal) Heating Cooling Sound Level (Night quiet) Refrigerant dBA Sound Power dBA 64 66 69 Sound Pressure dBA 50 52 54 Heating Sound Pressure dBA 42 42 43 Cooling Sound Pressure dBA 45 45 46 Type R-410A Charge kg 2.95 Control Refrigerant Oil Type Piping connections Liquid (OD) 1 l Quantity Diameter (OD) 1 1.0 1.0 1 1 1 Flare connection mm Quantity 9,52 1 Type Diameter (OD) mm Quantity Diameter (OD) 1 1 Flare connection 15,9 3 Type 3 3 Hole mm Quantity 26 1 Type Piping Length 1 1.0 Type Drain 2.95 Daphne FVC68D Charged Volume Gas 2.95 Expansion valve(electronic type) Nr of Circuits 26 26 1 1 Hole Diameter (OD) mm 18 18 18 Minimum m 5 5 5 Maximum m 75 75 75 Equivalent m 95 95 95 Chargeless m 10 10 10 Additional Refrigerant Charge kg/m Installation height difference m Maximum Heat Insulation See installation manual outdoor unit 4PW42025-1 30 30 Both liquid and gas pipes Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 56 ERHQ016AAW1 Inverter controlled • AlthermaTM • Outdoor units 30 • Outdoor units • ERHQ011-016AAW1 2 2-2 Specifications TECHNICAL SPECIFICATIONS ERHQ011AAW1 Safety Devices ERHQ014AAW1 ERHQ016AAW1 High pressure switch Fan motor thermal protector Fuse Standard Accessories Item Tie-wraps Quantity 2 2 Item 2 Installation manual Quantity 1 Notes 1 2 2 1 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Down to 3m with recharging of the outdoor unit. Refer to the installation manual of the outdoor unit. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C ( Conditions: Ta 35°C - LWE 7°C ( DT = 5°C) 2-3 ELECTRICAL SPECIFICATIONS Power Supply ERHQ011AAW1 Name 3N~ Frequency Hz 50 50 50 Voltage V 400 400 400 Voltage range Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A Maximum running Current Heating A Cooling A Recomended fuses Wiring connections ERHQ016AAW1 W1 Phase Current ERHQ014AAW1 A 5.8 5.8 13.5 (ERHQ*W1*) / 14 (ERHQ*W18*) 13.5 (ERHQ*W1*) / 14 (ERHQ*W18*) 20 20 For Power Supply Remark See installation manual outdoor unit 4PW42025-1 For connection with indoor Remark See installation manual outdoor unit 4PW42025-1 Power Supply Intake 5.8 20 Outdoor unit only Notes Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) • AlthermaTM • Outdoor units 57 • Outdoor units • ERHQ011-016AAW1 3 Capacity tables 3-1 Heating capacity tables ERHQ011-016AAW1 Maximum Heating Capacity (Peak values) Model 2 LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW57912-1A SYMBOLS CC HC PI LWE LWC Tamb 58 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Outdoor units 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For ERHQ011-16AAW1 models only: if Tamb < 4°C: bottom plate heater power input to be added = 95 W • Outdoor units • ERHQ011-016AAW1 3 Capacity tables 3-2 Cooling capacity tables ERHQ011-016AAW1 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 2 3 3TW57912-1A NOTES SYMBOLS CC HC PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Outdoor units 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For ERHQ011-16AAW1 models only: if Tamb < 4°C: bottom plate heater power input to be added = 95 W 59 • Outdoor units • ERHQ011-016AAW1 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing ERHQ011-016AAW1 1. 2. 3. 4. 5. 6. 7. 8. Hole for anchor bolt 4-M12 2 Gas pipe connection J15.9 flare Liquid connection pipe "9.5 flare Service port (in the unit) Electronic connection and grounding terminal MS (in switch box) Refrigerant piping intake Power supply wiring intake (knock hole J34) Control wiring intake (knock hole J27) Drain outlet 4 4TW57914-1 60 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAW1 4 Dimensional drawing & centre of gravity 4-2 Centre of gravity ERHQ011-016 2 4 4TW57919-5 • AlthermaTM • Outdoor units 61 • Outdoor units • ERHQ011-016AAW1 5 Piping diagram ERHQ011-016AAW1 2 5 R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC Y1S Y3S S1PH M*F M*C : Thermistor (Air) : Thermistor (discharge) : Thermistor (Suction) : Thermistor (Liquid 1) : Thermistor (middle) : Thermistor (Liquid 2) : Pressure sensor : : Crankcase heater : 4-way valve : Injection valve : High pressure switch : Fan motor :Compressor filter (strainer) filter (strainer) Heat exchanger Distributor Capillary tube Service port 5/16″ Field piping J 9.5 C 1220T-0 Field piping J15.9 C 1220T-0 Accumulator Indoor unit Outdoor unit Stop valve (with service port 5/16’ flare) 62 • AlthermaTM • Outdoor units Heating Cooling 3TW57915-1A • Outdoor units • ERHQ011-016AAW1 6 Wiring diagram 6-1 Wiring diagram ERHQ011-016AAW1 EKBPHT16Y Only for *RHQ01*AAW1 Power supply 3N∼ 400V 50Hz Only for *RHQ01*AAW18 Indoor Outdoor Reactor terminal position Note: 4 Notes: 1 This wiring diagram only applies to the outdoor unit 2 L: Live, N: Neutral, g: Field wiring 3 D : Terminal strip F : Connector GM: Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 Refer to the option manual, for connecting wiring to x6A and X77A 5 Refer to the ’wiring diagram sticker’ (on the back of front plate) on how to use BS1-BS4 and DS1 switch. 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’Off’ 9 : Option : Wiring dependent on model Compressor terminal position A1P A2P A3P BS1∼BS4 C1∼C4 DS1 E1HC E1H F1U F2U F3U F4U F5U F6U F7U F8U, F9U HAP (A1P) HAP (A2P) H1P∼7P (A1P) K1M-K2M K1R (A1P) K1R (A2P) K2R (A1P) K3R (A1P) L1R∼L3R L4R M1C M1F M2F PS R1∼R4 R1T R2T R3T R4T R5T R6T R7T S1NPH S1PH V1R∼V2R V3R X1M Y1E Y1S Y3S Z1C∼Z9C Z1F∼Z4F Q1DI Optional connector X6A X77A X1Y Printed circuit board Printed circuit board (INV) Printed circuit board (Noise filter) Push button switch Capacitor DIP switch Crankcase heater Bottomplate heater Fuse (31.5A 500V) Fuse (31.5A 500V) Fuse (T 6.3A / 250V) Fuse (T 6.3A / 250V) Fuse (T 6.3A / 250V) Fuse (T 6.3A / 250V) Fuse (T 5.0A / 250V) Fuse (F 1.0A / 250V) Pilot lamp (Service monitor-green) Pilot lamp (Service monitor-green) Pilot lamp (Service monitor-orange) Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (Y2S) Magnetic relay (E1HC) Reactor Reactor (For outdoor fan motor) Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (Heat exchanger middle) Thermistor (liquid) Thermistor (Fin) Pressure sensor Pressure switch (high) Power module Diode module Terminal strip Electronic expansion valve Solenoid valve (4 way valve) Solenoid valve Noise filter Noise filter Earth leakage protector 2 6 Connector Connector Connector Reactor box A El. comp. Assy Front arrow A arrow B 2TW57916-1C • AlthermaTM • Outdoor units 63 • Outdoor units • ERHQ011-016AAW1 7 Sound data 7-1 Sound pressure spectrum ERHQ016AAW1* HEATING Sound pressure level (dB) 7 ERHQ014AAW1* HEATING Sound pressure level (dB) 2 Sound pressure level (dB) ERHQ011AAW1* HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW57919-2 ERHQ016AAW1* COOLING Sound pressure level (dB) Sound pressure level (dB) ERHQ014AAW1* COOLING Sound pressure level (dB) ERHQ011AAW1* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW57919-1 64 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAW1 7 Sound data 7-2 Sound pressure night quiet mode ERHQ016AAW1* HEATING Sound pressure level (dB) Sound pressure level (dB) ERHQ014AAW1* HEATING Sound pressure level (dB) ERHQ011AAW1* HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) 2 7 Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW57919-4 ERHQ016AAW1* COOLING Sound pressure level (dB) Sound pressure level (dB) ERHQ014AAW1* COOLING Sound pressure level (dB) ERHQ011AAW1* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW57919-3 • AlthermaTM • Outdoor units 65 • Outdoor units • ERHQ011-016AAW1 8 Installation 8-1 Service space ERHQ011-016 A. Non stacked installation Legend 2 Unit: mm Suction side obstacle 8 Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 66 • AlthermaTM • Outdoor units • Outdoor units • ERHQ011-016AAW1 9 Operation range ERHQ011-016AAW1 Outdoor temp. (°CDB) 2 Cooling mode 9 Leaving evaporator Water temperature (°C) 6 Outdoor temp. (°CDB) Units with optional back up heater Heating mode operation possible, but no guarantee of capacity (if outdoor temperature < -25°C unit will stop) ERHQ_W18 units include special equipment (insulation heater sheet, à) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the ERHQ_W1 models may experience problems with severe ice build up on the aircooled coil. In case such conditions are expected, the ERHQ-W18 must be installed instead. These models contain countermeasures (insulation, heater sheet, à) to prevent freeze up. leaving condensor Water temperature (°C) Domestic hot water mode Outdoor temp. (°CDB) Booster heater operation only Water temperature domestic hot water tank (C°) 4TW57913-1A • AlthermaTM • Outdoor units 67 • Indoor units • EKHBH-X016AB TABLE OF CONTENTS EKHBH-X016AB 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 72 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 75 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 5 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 6 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Drainage instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 8 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 9 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 7 Static pressure drop unit • AlthermaTM • Indoor units 79 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 69 • Indoor units • EKHBH-X016AB 1 t B i A n6 1u a 0 m X r r - o e H o h B d tH nKl E•IA Features Large capacity indoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 2 1 70 • AlthermaTM • Indoor units • Indoor units • EKHBH-X016AB 2 2-1 Specifications TECHNICAL SPECIFICATIONS EKHBH016AB Outdoor units ERHQ16AAV3 Nominal input (Indoor only) Casing Colour Dimensions Packing W 230 2 Epoxy polyester painted galvanised steel Unit Packing 230 RAL9010 Material Weight EKHBX016AB Height mm 1,225 Width mm 660 Depth mm 610 610 Height mm 922 922 660 Width mm 502 502 Depth mm 361 361 Unit kg 55 55 Packed Unit kg 65 65 Material 2 EPS Wood Carton PP (Straps) Weight kg Main components Pump Pump Nominal ESP unit Heating kPa Cooling kPa Main components Pump Power input W Water side Heat exchanger Type 10 Type Nr. of speed 2 2 35.0 35.0 46.8 210 1 1 1.01 1.01 l/min 16 16 45.9 45.9 Water volume l Water side Heat exchanger Water flow rate Nom. Heating l/min Cooling l/min Main components Water side Heat exchanger Water flow rate Max. l/min 37.6 58 Insulation material Expansion vessel Water filter Polyurethane foam l 10 10 Max. water pressure bar 3 3 Pre pressure bar 1 1 Diameter perforations mm 1 1 Piping connections diameter Brass inch Piping inch Safety valve bar G 1-1/4 (MALE) 1-1/4’’ 3 3 Manometer Yes Drain valve / Fill valve Yes Shut off valve Yes Air purge valve Refrigerant Circuit 58 Volume Material Water circuit 210 Brazed plate Qty Water flow rate Min. 10 Water cooled Yes Total water volume (6) l 5,5 Gas side diameter mm 15,9 Liquid side diameter mm Sound level Sound Pressure dBA Operation range Ambient Heating Cooling °C Waterside Heating °C Cooling °C °C • AlthermaTM • Indoor units 9,52 28 28 -20~35 10-46 15-55 5-22 71 • Indoor units • EKHBH-X016AB 2 2-2 Specifications ELECTRICAL SPECIFICATIONS Electric heater Type EKHBX016AB 3V3 Power Supply Phase 1~ Frequency Hz 50 50 Voltage V 230 230 Current back-up heater Running Current A 13 13 Current back-up heater + booster heater (EKHWS* models) Z-max Text Running Current *V3 Minimum Ssc value *V3 Electric heater Voltage range Minimum -10% Maximum +10% 2 2 Wiring connections Electric heater For power supply backup heater 0.29 A 0.29 26 (13+13) Equipment complying with EN/IEC 61000-3-12 ** Quantity of wires Type of wires 3G Select diameter and type according to national and local regulations Type 6V3 Power Supply Phase 1~ Frequency Hz 50 50 Voltage V 230 230 Current back-up heater Running Current A 26 26 Current back-up heater Z-max Text 0.29 0.29 Electric heater Current back-up heater Minimum Ssc value Current back-up heater + booster heater (EKHWS* models) Z-max Text Running Current *V3 Minimum Ssc value *V3 Electric heater Voltage range Minimum -10% Maximum +10% Wiring connections Electric heater For power supply backup heater Running Current Electric heater Voltage range 0.17 39 (26+13) Equipment complying with EN/IEC 61000-3-12 ** 3G Select diameter and type according to national and local regulations Type Current back-up heater + booster heater (EKHWS* models) Electric heater 0.17 A Type of wires 6WN Phase Current back-up heater Wiring connections Equipment complying with EN/IEC 61000-3-12 ** Quantity of wires Power Supply Minimum Ssc value For power supply backup heater 3~ Frequency Hz 50 50 Voltage V 400 400 Running Current A 8.7 8.7 *V3 A 21,7 (8.7+13) *Z2 A 16.2 (8.7+7.5) *V3 Equipment complying with EN/IEC 61000-3-12 ** *Z2 Equipment complying with EN/IEC 61000-3-12 ** Minimum -10% Maximum +10% Quantity of wires Type of wires 4G Select diameter and type according to national and local regulations Type 6T1 Power Supply Phase 3~ Frequency Hz 50 50 Voltage V 230 230 Current back-up heater Running Current A 15.1 15.1 Current back-up heater + booster heater (EKHWS* models) Running Current *V3 A Minimum Ssc value *V3 Electric heater Voltage range Minimum -10% Maximum +10% Wiring connections 72 EKHBH016AB For power supply backup heater Quantity of wires Type of wires • AlthermaTM • Indoor units 26.1 (15.1+13) Equipment complying with EN/IEC 61000-3-12 ** 4G Select diameter and type according to national and local regulations • Indoor units • EKHBH-X016AB 2 2-2 Specifications ELECTRICAL SPECIFICATIONS Electric heater EKHBH016AB Type EKHBX016AB 9WN Power Supply Phase 3~ Frequency Hz 50 50 Voltage V 400 400 Current back-up heater Running Current A 13 13 Current back-up heater + booster heater (EKHWS* models) Running Current *V3 A *Z2 A Electric heater Voltage range Wiring connections Electric heater Minimum Ssc value For power supply backup heater 20.5 (13+7.5) *V3 Equipment complying with EN/IEC 61000-3-12 ** *Z2 Equipment complying with EN/IEC 61000-3-12 ** Minimum -10% Maximum +10% 4G Type of wires Select diameter and type according to national and local regulations Type 9T1 Phase Current back-up heater 3~ Frequency Hz 50 50 Voltage V 230 230 Running Current A 22.6 22.6 Minimum Ssc value Current back-up heater Running Current + booster heater Minimum Ssc value (EKHWS* models) Wiring connections Voltage range For power supply backup heater *V3 Equipment complying with EN/IEC 61000-3-12 ** A 35.6 (22.6+13) *V3 Equipment complying with EN/IEC 61000-3-12 ** Minimum -10% Maximum +10% Quantity of wires 4G Type of wires Select diameter and type according to national and local regulations Connection type For power supply connection to Optional Warm Water Tank + Q2L Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details of the voltage range and current refer to installation manual EKHBH/X016AB* Connection type For connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type For connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual EKHBH/X016AB* Type of wires Select diameter and type according to national and local regulations Type of wires Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm² Connection type For connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm² Connection type For connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Notes 2 26 (13+13) Quantity of wires Power Supply Electric heater 2 Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm² Above mentioned power supply of the hydro box is for the backup heater only. The Switch box & pump of the hydrobox are supplied via the outdoor unit. The optional domestic warm water tank has a separate power supply. Optional electric heater has 2 capacity steps except for the 3V3 model which has only 1 capacity step. In accordance with EN/IEC 61000-3-11(*), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys(***) <= Zmax (*) European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A (**) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and <= 75A per phase (***) System impedance • AlthermaTM • Indoor units 73 • Indoor units • EKHBH-X016AB 3 Options Factory mounted optional equipment for EKHB(H/X)016AB** Reference 2 3 Description Heating only model EKHBH016A... Reversible model EKHBX016A... Back up heater 3kW 1∼230 V Back up heater 6kW 1∼230 V Back up heater 6kW 3∼400 V Back up heater 6kW 3∼230 V Back up heater 9kW 3∼400 V Back up heater 9kW 3∼230 V 3V3 6V3 6WN 6T1 9WN 9T1 B3V3 B3V3 V ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ B6V3 B6V3 ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ B6WN ⎯ ⎯ V ⎯ ⎯ ⎯ B6T1 B6WN ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ B9WN B6T1 ⎯ ⎯ ⎯ V ⎯ ⎯ B9WN ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ B9T1 B9T1 ⎯ ⎯ ⎯ ⎯ ⎯ V ⎯ ⎯ ⎯ ⎯ ⎯ V Outdoor combination table for EKHB(H/X)016AB** EKHBH016AB* EKHBX016AB* Note: ERHQ(W18/V38) units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the ERHQ(W1/V3) models may experience problems with severe ice build up on the aircooled coil. In case such conditions are expected, the ERHQ(W18/V38) must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. ERHQ011AA(V3*/W1*) ERHQ014AA(V3*/W1*) ERHQ016AA(V3*/W1*) V V V V V V ERHQ011AA(V3/W1) ERHQ014AA(V38/W18) ERHQ014AA(V3/W1) ERHQ014AA(V38/W18) ERHQ016AA(V3/W1) ERHQ016AA(V38/W38) V V - V V - V V - Heating only indoor unit Reversible indoor unit Kit availability for ERHQ011-016AA** EKBPHT16Y EKDK04 Bottom plate heater (2) drain plug kit (2) Kit availability for EKHB(H/X)016AB* Reference Description EKHWS150(A/B)3V3 EKHWS200(A/)B3V3 EKHWS300(A/B)3V3 EKHWS200(A/B)3Z2 EKHWS300(A/B)3Z2 EKHWSU150(A/B)3V3 EKHWSU200(A/B)3V3 EKHWSU300(A/B)3V3 EKHWE150A3V3 EKHWET150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 EKHBDP EKRP1HB EKRTW EKRTR EKRTETS Heating only model EKHBH016A... Reversible model EKHBX016A... Stainless domestic hot water tank 150l 1-230V Stainless domestic hot water tank 200l 1-230V Stainless domestic hot water tank 300l 1-230V Stainless domestic hot water tank 200l 2-400V Stainless domestic hot water tank 300l 2-400V Stainless domestic hot water tank 150l 1-230V Stainless domestic hot water tank 200l 1-230V Stainless domestic hot water tank 300l 1-230V Enamel domestic hot water tank 150l 1-230V B3V3 B3V3 V V V V V V V V V V V V V V V V V V V V V V V V V V V V V Wallmounted enamel domestic hot water tank 150l 1-230V Enamel domestic hot water tank 200l 1-230V Enamel domestic hot water tank 300l 1-230V Enamel domestic hot water tank 200l 2-400V Enamel domestic hot water tank 300l 2-400V Option kit for condensate free cooling operation Digital I/O PCB (1) Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) B6V3 V V V V V V V V V V V V V V B6V3 V V V V V V V V V V V V V V V B6WN V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) V(*) V(*) V(*) V V V V V V B6WN V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) V(*) V(*) V(*) V V V V V V V B6T1 V V V V V V V V V V V V V V B6T1 V V V V V V V V V V V V V V V B9WN B9WN V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) V(*) V(*) V(*) V V V V V V V V (*) V (*) V (*) V V V (*) V (*) V (*) V(*) V(*) V(*) V(*) V V V V V V B9T1 V V V V V V V V V V V V V V B9T1 V V V V V V V V V V V V V V V (*) If neutral line is available Kit available for EKHWS* Reference EKUHWA EKUHWB EKUHW2WB EKSOLHWAV1 EKWBSWW150 Description EKHWE(T)*3(V3/Z2) EKHWS*3(V3/Z2) EKHWSU*3V3 Option kit for UK EKHWSU150-300V3 Option kit 1 for UK EKHWSU150-300V3 (7) Option kit 2 for UK EKHWSU150-300V3 (7) Solarkit (5) Wall bracket for EKHWS(U)150(A/B)3V3 or EKSWW150V3 150A 200A 300A V V V - V - 150(A/B) 200(A/B) 300(A/B) V V V - V - 150A V V(5) V(5) V V 200A V V(5) V(5) V - 300A V V(5) V(5) V - 150B V V V(6) V V 200B V V V(6) V - 300B V V V(6) V - Remarks: Other combinations than mentioned in this option TW are not guaranteed. (1) Address card that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included. (2) It is not allowed to combine bottom plate heater and drain plug/stop kit (3) EKRTETS can only be used in combination with EKRTR (4) Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. (5) If installation on tank A version both kits are required (6) Kit is only necessary when installing EKSOLHWAV1 on a UK tank B-series (EKHWSU(150/200/300)B3V3 (7) EKUHWB = EKUHWA -(Kit is only necessary when installing EKSOLHWAV1 on a UK tank B-series) EKUHW2WB = 2 way valve and 2 way valve accessories 3TW57819-2C 74 • AlthermaTM • Indoor units • Indoor units • EKHBH-X016AB 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHBH016AB FIXATION 2 4 Service door (Closed) 361 (Open) 553 1-1/4″ Male BSP View A Scale 1/5 Dimensions wallbracket Minimum space for service & ventilation Min. 150 Min. 200 Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection: 1 1/4’’ M BSP j 4 Water OUT connection: 1 1/4’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J9.52 flare connection j 14 Shut off valves with drain/fill valve (accessory delivered with unit) j 15 Holes for fixation j 16 Switchbox terminals j 17 Switchbox terminals option sanitary warm water tank j 18 Wallbracket 3TW57754-1A EKHBX016AB FIXATION Service door (Closed) 361 (Open) 553 1-1/4″ Male BSP View A Scale 1/5 Dimensions wallbracket Minimum space for service & ventilation Min. 150 Min. 200 Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection: 1 1/4’’ M BSP j 4 Water OUT connection: 1 1/4’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J9.52 flare connection j 14 Shut off valves with drain/fill valve (accessory delivered with unit) j 15 Holes for fixation j 16 Switchbox terminals j 17 Switchbox terminals option sanitary warm water tank j 18 Wallbracket • AlthermaTM • Indoor units Dimensions wallbracket Scale 1/5 3TW57754-2A 75 • Indoor units • EKHBH-X016AB 5 Piping diagram EKHBH(X)016AB Water Site Expansion Vessel Pressure Gauge 2 5 Drain Safety Valve Flowswitch Evaporator Condensor Air Purge Blow Off Field Installation R2T Refriferant Side R1T Pump Refr. Out Water Outlet Refr. In Electric Heater Body Shut Off Valve With Drain/Fill Valve Plate Heat Exchanger R3T Field Installation R4T Filter Refr. In Water Inlet Refr. Out Shut Off Valve With Drain/Fill Valve Check Valve Cooling (EKHBX) Heating (EKHBX + EKHBH) Flare Conn. Screw Conn. Flange Conn. Pinched Pipe Spinned Pipe R4T R3T R2T R1T Thermistor Inlet water Thermistor Refrigerant Liquid Side Thermistor Outlet Water Backup heater Thermistor Outlet Water Heat-exchanger Thermistor Description 3TW57755-1 76 • AlthermaTM • Indoor units • Indoor units • EKHBH-X016AB 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)016AB3V3 Only for EKSOLHWAV1 Option Outdoor unit Power supply 230V 1N∼50Hz Domestic hot water tank Solar pump connection >> See note 2 << Only for *EKHWE* Option See note 9 Only for *EKHW(S/E) Option See note 7 For EKHWSU*V3 Option 2 User interface 6 Only for EKRTW Option Solar input Alarm output Cooling/heating on/off output Only for EKHW Option heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 230V AC supply from PCB Domestic hot water Only for EKRTROption 3 wire type (SPST) tank Only forEKHW*V3 Option Only for EKHW Option NO valve Only for EKSOLHWAV1 Option Only for EKHW(S/E) Option See note 7 For EKHWSU*V3 Option Electric heater fuse 20A F1B Only for EKRTWOption Example field supply thermostat NC valve F2B EKHW kit fuse 20A X1M-X9M V1S, V2S FU1 FU2 FuS, FuR Q1DI Q2L Q1L S1S SS1 TR1 R5T R4T R3T R2T R2T (EKRTETS) R1T R1H (EKRTR) R1T (EKRTW/R) S1L E4H E1H M3S M2S M1P PHC1 K5M : Terminal strips : Spark suppression 1,2 : Fuse 3.15A T 250V : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Earth leakage protector : Thermal protector booster heater : Thermal protector backup heater : Solar pumpstation relay : DIP switch : Transformer 24V for PCB : Domestic hot water thermistor : Inlet water thermistor : Refrigerant liquid side thermistor : Outlet water backup heater thermistor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Humidity sensor : Ambient sensor : Flowswitch : Booster heater (3kW) : Backup heater element 1 : 3way valve: floorheating/domestic hot water : 2 way valve for cooling mode : Pump : Optocoupler input circuit : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K4M : Pump Relay K3M : Contactor booster heater K1M : Contactor backup heater step 1 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse Back up heater A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB Notes: 1 2 3 4 5 6 7 8 9 Domestic hot water tank Only forEKHW*V3 Option Wiring dependent on model Option Field wiring PCB Wire colour Field wiring This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow / BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For EKHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (L,N) For EKSOLHWAV1, refer to option manual 3TW57816-2B EKHBH(X)016AB6V3 Outdoor unit Power supply 230V 1N∼50Hz >> See note 2 << Only for EKSOLHWAV1 Option Solar pump connection Domestic hot water tank Only See note 9 for EKHW*V3 Option User interface Only for EKHW Option Only forEKRTW Option Solar input Cooling/heating on/off output Alarm output See note 7 For EKHWSU*V3 Option Only for EKRP1HB & EKSOLWAV1 Option 230V AC supply from PCB See note 8 Only forEKRTR Option Domestic hot water tank Only for EKHW*V3 Option 3 wire type (SPST) Only for EKHW* Option NO valve Only for EKSOLWAV* Option Only for EKHW Option See note 7 For EKHWSU*V3 Option Wiring dependent on model Field wiring F1B Only forEKRTETS Option Example field supply thermostat Option Field wiring Wire colour NC valve F2B Electric heater fuse 32A EKHW kit fuse 20A X1M-X9M : Terminal strips V2S : Spark suppression 2 V1S : Spark suppression 1 FU1 : Fuse 3.15A T 250V FU2 : Fuse 5A T 250V FuS, FuR : Fuse 5A 250V for solar/remote alarm PCB Q1DI : Earth leakage protector Q2L : Thermal protector 1/2 Booster heater Q1L : Thermal protector backup heater S1S : Solar pumpstation relay SS1 : DIP switch R5T : Domestic hot water thermistor R4T : Inlet water thermistor R3T : Refrigerant liquid side thermistor R2T (EKRTETS) : External sensor (floor or ambient) R2T : Outlet water backup heater thermistor R1H (EKRTW/R) : Ambient sensor R1T : Outlet water heat-exchanger thermistor R1H (EKRTR) : Humidity sensor S1L : Flowswitch E4H : Booster heater (3kW) E1H-E2H : Backup heater element 1-2 M3S : 3way valve: floorheating/domestic hot water M2S : 2 way valve for cooling mode M1P : Pump PHC1 : Optocoupler input circuit K5M : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M/K2M : Contactor backup heater step 1/2 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse Back up heater E4H : Booster heater E1H-E3H : Backup heater element 1-2 A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB Domestic hot water tank Only for EKHW*V3 Option Notes: 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. 9 For EKSOLHWAV1, refer to option manual • AlthermaTM • Indoor units 3TW57816-3B 77 • Indoor units • EKHBH-X016AB 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)016AB6T1/9T1 Power supply Only for EKSOLHWAV1 Option Outdoor unit Domestic hot water Solar pump connection tank >> See note 2 << See note 9 Only for EKHW*V3 Option See note 7 For EKHWSU*V3 Option 2 User interface Only for EKHW Option Only forEKRTW Option Solar input Cooling/heating on/off output Alarm output 6 Only for EKRP1HB & EKSOLWAV1 Option 230V AC supply from PCB See note 8 Only for EKRTR Option Domestic hot water tank 3 wire type (SPST) Only for EKHW*V3 Option Only for EKHW* Option NO valve Only for EKSOLWAV* Option Only for EKHW Option See note 7 For EKHWSU*V3 Option Option Field wiring Field wiring Example field supply thermostat NC valve Wire colour Electric heater fuse 6T1 20A Model F1B Only for EKRTETS Option Wiring dependent on model F2B 9T1 32A EKHW kit fuse 20A X1M-X9M : Terminal strips V2S : Spark suppression 2 V1S : Spark suppression 1 FU1 : Fuse 3.15A T 250V FU2 : Fuse 5A T 250V FuS, FuR : Fuse 5A 250V for solar/remote alarm PCB Q1DI : Earth leakage protector Q2L/Q3L : Thermal protector 1/2 Booster heater Q1L : Thermal protector backup heater S1S : Solar pumpstation relay SS1 : DIP switch R5T : Domestic hot water thermistor R4T : Inlet water thermistor R3T : Refrigerant liquid side thermistor R2T (EKRTETS) : External sensor (floor or ambient) R2T : Outlet water backup heater thermistor R1H (EKRTW/R) : Ambient sensor R1T : Outlet water heat-exchanger thermistor R1H (EKRTR) : Humidity sensor S1L : Flowswitch E4H : Booster heater (3kW) E1H-E3H : Backup heater element 1-3 M3S : 3way valve: floorheating/domestic hot water M2S : 2 way valve for cooling mode M1P : Pump PHC1 : Optocoupler input circuit K5M : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M/K2M : Contactor backup heater step 1/2 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse Back up heater E4H : Booster heater E1H-E3H : Backup heater element 1-3 A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB Domestic hot water tank Only for EKHW*V3 Option Notes: 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. 9 For EKSOLHWAV1, refer to option manual EKHBH(X)016AB6WN/9WN Power supply 230V 1N∼50Hz >> See note 2 << Outdoor unit Only for EKSOLHWAV1 Option 3TW57816-6B Domestic hot water Solar pump connection Domestic hot water tank tank Only See note 9 for EKHW*V3 Option Cooling/heating on/off output Only for EKHW*V3 Option User interface Only for EKHW Option Only forEKRTW Option Solar input Alarm output See note 7 For EKHWSU*V3 Option 230V AC Only for EKRP1HB & EKSOLWAV1 Option supply from PCB See note 8 Domestic hot water tank Only for EKHW*V3 Option Only forEKRTR Option Domestic hot water tank 3 wire type (SPST) Only for EKHW*Option NO valve Only for EKHW Option Only forEKHW*Z2 Option See note 7 For EKHWSU*V3 Option Wiring dependent on model Field wiring Domestic hot water tank Only for EKHW*V3 Option Model F1B Only for EKRTETS Option Example field supply thermostat Option Field wiring Wire colour NC valve F2B Only for EKSOLWAV* Option Electric heater fuse 6WN 16A EKHW kit fuse 20A 9WN 20A X1M-X9M : Terminal strips V2S : Spark suppression 2 V1S : Spark suppression 1 FU1 : Fuse 3.15A T 250V FU2 : Fuse 5A T 250V FuS, FuR : Fuse 5A 250V for solar/remote alarm PCB Q1DI : Earth leakage protector Q2L/Q3L : Thermal protector 1/2 Booster heater Q1L : Thermal protector backup heater S1S : Solar pumpstation relay SS1 : DIP switch R5T : Domestic hot water thermistor R4T : Inlet water thermistor R3T : Refrigerant liquid side thermistor R2T (EKRTETS) : External sensor (floor or ambient) R2T : Outlet water backup heater thermistor R1H (EKRTW/R) : Ambient sensor R1T : Outlet water heat-exchanger thermistor R1H (EKRTR) : Humidity sensor S1L : Flowswitch E4H : Booster heater (3kW) E1H-E3H : Backup heater element 1-3 M3S : 3way valve: floorheating/domestic hot water M2S : 2 way valve for cooling mode M1P : Pump PHC1 : Optocoupler input circuit K5M : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump K3M : Contactor booster heater K1M/K2M : Contactor backup heater step 1/2 F2B : Fuse booster heater F1B : Fuse backup heater F1T : Thermal fuse Back up heater E4H : Booster heater E1H-E3H : Backup heater element 1-3 A4P (EKRTR) : Receiver PCB A4P (EKRP1HB) : Solar/remote alarm PCB A3P : Thermostat (PC=power circuit) A2P : User interface PCB A1P : Main PCB Domestic hot water tank Only for EKHW*Z2 Option Notes: 1 2 3 4 5 6 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option. :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-sircuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 7 For EKHWSU*V3, refer to option manual 8 Option PCB works with an external 230V AC power supply unit. 9 For EKSOLHWAV1, refer to option manual 78 • AlthermaTM • Indoor units 3TW57816-4B • Indoor units • EKHBH-X016AB 6 Wiring diagram 6-2 External connection diagram Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply unit power supply: 400V or 230V + earth 5 or 3 core 2 X1M:L1-L2-L3-N-Earth Optional power supply Backup heater power supply (3/6/9kW): 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth 4 core <10m: 4Gx1.5 >10m: 4Gx2.5 2 core 3 core 3 or4 core Optional parts 6 Field supply Only for EKBPHT Indoor unit Only for EKRP1HB & EKSOLHWAV1 X1M:1-2-3-Earth 1 core Domestic hot water tank X1M:L1-L2-L3-N-Earth 1 core X3M:L-N-Earth Alarm indication Alarm output A4P: Y2 Cooling/Heating on/off output 2 way valve 2 core Q3L Clixon A4P: Y3 Solar input 1 core solar interlock Only for EKHWSU*V3 Power supply booster heater 5 core X4M:1-2-Earth NO valve: X2M: 6-7 2 core NC valve: X2M: 5-7 Q2L - Clixon booster heater R5T - Thermistor water temperature Cooling/Heating on/off indication 1 core 2 way valve M2S (EKHBX Units) for cooling mode Room thermostat Only for field supplied room thermostat Possibility 1 Note: min. distance to power cable * 5cm 2 core 4 core Signal 2 core Possibility 2 3 core for C/H application 2 core for H only application Only for EKRTW (wired room thermostat) Possibility 3 5 core for C/H application 4 core for H only application Only for EKTR (wireless room thermostat) Q3L Clixon Solar pump Only for EKSOLHWAV1 Only for EKRTETS 2 core (3m R2T External sensor included) floor or ambient 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating 3 core User interface Signal 3TW57786-7A • AlthermaTM • Indoor units 79 • Indoor units • EKHBH-X016AB 7 Installation 7-1 Drainage instructions EKHBDP 2 Leaving water temperature limit to prevent condesation 7 Relative humidity 40% Relative humidity 60% Relative humidity 80% Leaving water temperature [°C] Leaving water temperature [°C] Maximum leaving water temperature cooling mode = 22°C Example: With ambient temperature of 25°C and relative humidity of 40%. If leaving water temperature is below 12°C, condensation on water piping will happen. Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDP - drainpan kit must be considered. 4TW57759-3 80 • AlthermaTM • Indoor units • Indoor units • EKHBH-X016AB 8 Operation range EKHBH(X)016AB Outdoor temp. (°CDB) 2 Cooling mode 8 Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) Heating mode No heat pump operation, back up heater only * ERHQ_V18 units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the ERHQ_V3 models may experience problems with severe ice build up on the aircooled coil. In case such conditions are expected, the ERHQ-V38 must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. leaving condensor Water temperature (°C) Domestic hot water mode Outdoor temp. (°CDB) Booster heater operation only Water temperature domestic hot water tank (C°) 4TW57753-1B • AlthermaTM • Indoor units 81 • Indoor units • EKHBH-X016AB 9 Hydraulic performance 9-1 Static pressure drop unit EKHBH(X)016 2 ESP [kPa] 9 Flow [l/min] l high speed ll medium speed ESP: external static pressure Flow: waterflow through the unit Warning: 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. 4TW57759-1 82 • AlthermaTM • Indoor units EEDEN09-720 technical data AlthermaTM Part 3/4: EDHQ011-016AA6V3 EDHQ011-016AA6W1 EDLQ011-016AA6V3 EDLQ011-016AA6W1 EBHQ011-016AA6V3 EBHQ011-016AA6W1 EBLQ011-016AA6V3 EBLQ011-016AA6W1 • Monobloc • EDHQ011-016AA6V3 TABLE OF CONTENTS EDHQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 87 88 89 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Heating capacity tables 5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 94 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 97 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 96 98 99 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 85 • Monobloc • EDHQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnH Dlo E•MA Features Heating only monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 86 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 16.00 Heating capacity Nominal kW 11.20 14.00 Heating PI Nominal kW 2.47 3.20 3.79 COP Nominal 4.54 4.37 4.22 15.06 Heating capacity Nominal kW 10.87 13.10 Heating PI Nominal kW 3.22 3.91 4.62 COP Nominal 3.37 3.35 3.26 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EDHQ011AA6V3 Colour Unit Packing Weight Packing 2 EDHQ016AA6V3 Ivory white Material Dimensions EDHQ014AA6V3 3 Painted galvanised steel Height mm Width mm Depth mm Height mm 1,418 1,435 382 382 382 1,557 Width mm Depth mm 430 1,500 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Material 430 Wood Carton Plastic foil Weight Operation Range Heating - Ambient Min Max Sound Level (nominal) Sound Level (Night quiet) Refrigerant kg 20 20 20 °CDB -15 -15 -15 °CDB 35 35 35 Heating - Waterside Min °C 15 15 15 Max °C 55 55 55 Domestic hot water -Ambient Min °CDB -15 -15 -15 Max °CDB 43 43 43 Domestic hot water - Waterside Min °C 25 25 25 Max °C 80 80 80 Heating Sound Power dBA 64 64 66 Sound Pressure dBA 51 51 52 Sound Pressure dBA 42 42 43 Heating Type Charge R-410A kg 2.95 Control Nr of Circuits Refrigerant Oil 1 Type Charged Volume 2.95 2.95 Electronic expansion valve 1 1 Daphne FVC68D l 1.0 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee • AlthermaTM • Monobloc 87 • Monobloc • EDHQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 3 60 Tube type Hi-XSS Fin 2 Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity Air Flow Rate (nominal at 230V) Heating High Fan Discharge direction Motor m³/min 2 2 2 90 90 90 Horizontal Quantity 2 Model Motor Fan Speed (nominal) Steps Motor 8 8 8 rpm 760 760 760 Output W 70 70 70 Direct drive Quantity 1 Motor JT100G-VD Type Hermetically sealed scroll compressor Crankcase Heater Type Output W Inverter driven 33 Nominal ESP unit Heating Power input Water filter 2 2 2 52.5 43.5 35.0 W 210 210 210 Type Brazed plate Quantity 1 1 1 1.01 1.01 1.01 Water volume l Water flow rate Min. l/min 16 16 16 Water flow rate Nom. Heating l/min 32.1 40.1 45.9 Water flow rate Max. l/min 58 58 58 Foamed synthetic elastomer Volume l 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit 10 Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer 3 3 Yes Drain valve / Fill valve yes Shut off valve yes Air purge valve yes Total water volume (6) 88 33 kPa Insulation material Expansion vessel 33 Water cooled Nr. of speed Water side Heat exchanger 1 2,200 Starting Method Pump 1 Model Motor Output W Motor 2 Heating Drive Compressor 2 Brushless DC l • AlthermaTM • Monobloc 5.5 5.5 5.5 • Monobloc • EDHQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power EDHQ011AA6V3 Name Current Power supply Current back-up hydraulic component heater Current back-up heater Power Supply 1 1 1 50 50 230 230 Frequency Hz 50 Voltage V 230 Minimum V Maximum V -10% +10% Minimum Ssc kVa value Recomended A fuses Wiring connections EDHQ016AA6V3 V3 Phase Voltage range EDHQ014AA6V3 3 Equipment complying with EN/IEC 61000-3-12(*) 32 For power supply compressor component 32 32 See installation manual Type 6V3 Phase 1~ Frequency Hz 50 50 50 Voltage V 230 230 230 Running Current Back-up heater A 26 26 26 Running Current Back-up heater + booster heater +EK*V3 A Current back-up heater Z-max Back-up heater A 0.29 0.29 0.29 Back-up heater + booster heater A 0.17 0.17 0.17 +EK*V3 kVa Minimum Ssc value 2 • AlthermaTM • Monobloc 39(26+13) Equipment complying with EN/IEC 61000-3-12(**) 89 • Monobloc • EDHQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDHQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 2G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDHQ016AA6V3 -10% Quantity of wires 3 EDHQ014AA6V3 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 90 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 3 Options EDHQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 91 • Monobloc • EDHQ011-016AA6V3 3 Options EDHQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 92 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EDHQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 93 • Monobloc • EDHQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDHQ011-016AA6V3 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 94 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EDHQ011-016AA6V3 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Stop valve (with service port 5/16’ flare) Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58015-1A • AlthermaTM • Monobloc 95 • Monobloc • EDHQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EDHQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Fuse (F 1,0A/250V) Light Emit. Diode (Serv. Monitor-Orange) Prepare, Test --------- Flickering Malfunction Detection -- Light up Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip (Power supply) Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1C∼Z3C Z1F∼Z4F Optional connector X1Y 3 7 Connector Position of compressor terminal Wire entrance Option Wiring dependent on model Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. El. comp. Assy (Position of elements) 2TW58016-1 EDHQ011-016AA6V3 Outdoor unit Only for EC/BLQOption Only for EKSOLHWAV1Option Domestic hot water tank Solar pump connection Power supply 230V 1N∼50Hz Only for *KHWE*Option See note 9 >> See note 2 << Only for *KHW(S/E)*Option See note 7 For *KHWSU*V3 Option User interface F1B heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 Domestic hot water tank Only for *KHW Option Only for *KRTW* Option Solar input Alarm output Standard 6kw (_) See note 10 Cooling/heating on/off output From compressor module switchbox (B.7 PageA) supply from PCB Only for *KRTR* Option 3 wire type (SPST) NO valve Only forEKHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHW(S/E)* Option Only for EKHW Option Wiring dependent on model Only for EKRTETS* Option Field wiring Example field supply thermostat Reduced 3kw See note 10 Electric heater fuse 32A 230V AC Only for EKSOLHWAV1 Option Option Field wiring F2B PCB *KHW kit fuse 20A A11P A12P A3P (*KRTW) A4P (EKRTR) A4P (*KRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M K7M M1P M2S M3S PHC1 Q1DI Q1L Q2L R1H (*KRTR) R1T (*KRTW/R) R2T (EKRTETS) R11T R12T R13T R14T R5T (*KHW*) S1L S1S S2S SS1 S1T S2T TR1 V1S, V2S X1M-X10M X2Y : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection : Relay for solar pump : Pump : 2 way valve for cooling mode : 3 way valve: floorheating/domestic hot water : Optocoupler input circuit : Earth leakage protector : Thermal protector backup heater : Thermal protector 1/2Booster heater : Humidity sensor : Ambient sensor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Outlet water backup heater thermistor : Refrigerant liquid side thermistor : Inlet water thermistor : Domestic hot water thermistor : Flowswitch : Solar pumpstation relay : benefit kWh rate power supply contact : DIP switch : thermostat switchbox heater : thermostat expansion vessel heater : Transformer 24V for PCB : Spark suppression 1, 2 : Terminal strips : Connector Wire colour NC valve Notes: Domestic hot water tank Only for *KHWE*V3 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58016-1 96 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EDHQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth 230V 3 core 3 or4 core Optional parts Only for EKRP1HB & EKSOLHWAV1 230V X1M:1-2-3-Earth A4P: Y1 Alarm output A4P: Y2 Cooling/Heating on/off output 2 way valve Power supply booster heater A4P: Y3 Solar input 2 core 2x0.75 X7M X5M F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 NO valve: X2M: 6-7 NC valve: X2M: 5-7 X4M:1-2-Earth Alarm indication 230V X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core X3M: L1-L2-Earth or L-N-Earth Q*L Clixon 7 1 core A4P: YC X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 3 2 core Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT X2M: 16-160 User interface communication 3TW58016-2A • AlthermaTM • Monobloc 97 • Monobloc • EDHQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EDHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 98 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EDHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 • AlthermaTM • Monobloc 99 • Monobloc • EDHQ011-016AA6V3 9 Installation 9-1 Service space EDHQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 100 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6V3 10 Operation range EDHQ011-016AA6V3 3 Outdoor temp. (°CDB) Cooling mode only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58013-1A • AlthermaTM • Monobloc 101 • Monobloc • EDHQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EDHQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. 102 • AlthermaTM • Monobloc 4TW58019-2 • Monobloc • EDHQ011-016AA6W1 TABLE OF CONTENTS EDHQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 105 106 107 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Heating capacity tables 5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 112 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 115 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 114 116 117 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 103 • Monobloc • EDHQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnH Dlo E•MA Features Heating only monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 104 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 16.00 Heating capacity Nominal kW 11.20 14.00 Heating PI Nominal kW 2.51 3.22 3.72 COP Nominal 4.46 4.35 4.30 15.06 Heating capacity Nominal kW 10.87 13.10 Heating PI Nominal kW 3.12 3.98 4.58 COP Nominal 3.48 3.29 3.29 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EDHQ011AA6W1 Colour Unit Packing Weight Packing 2 EDHQ016AA6W1 Ivory white Material Dimensions EDHQ014AA6W1 3 Painted galvanised steel Height mm 1,418 Width mm 1,435 Depth mm Height mm 382 382 382 1,557 Width mm Depth mm 430 1,500 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Material 430 Wood Carton Plastic foil Weight Operation Range Heating - Ambient Min Max kg 20 20 20 °CDB -15 -15 -15 °CDB 35 35 35 Heating - Waterside Min °C 15 15 15 Max °C 55 55 55 °CDB -15 -15 -15 Domestic hot water Min -Ambient Max °CDB 43 43 43 Domestic hot water Min - Waterside Max °C 25 25 25 °C 80 80 80 Sound Level (nominal) Heating Sound Pressure dBA 49 51 53 Sound Level (Night quiet) Heating Sound Pressure dBA 42 42 43 Refrigerant Type Charge R-410A kg 2.95 Control Nr of Circuits Refrigerant Oil 1 Type Charged Volume 2.95 2.95 Electronic expansion valve 1 1 Daphne FVC68D l 1.0 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee • AlthermaTM • Monobloc 105 • Monobloc • EDHQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 3 60 Tube type Hi-XSS Fin 2 Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 Discharge direction Motor Quantity 2 Model Motor Fan Speed (nominal) Steps Motor Crankcase Heater Pump Type 8 8 8 760 760 760 Output W 70 70 70 Direct drive 1 JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven W 33 Heating 2 2 2 52.5 43.5 35.0 W 210 210 210 Brazed plate Quantity l Water flow rate Min. Water flow rate Nom. Heating Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 l/min 32.1 40.1 45.9 l/min 58 58 58 Insulation material Foamed synthetic elastomer Volume l 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material 10 Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer 3 3 Yes Drain valve / Fill valve yes Shut off valve yes Air purge valve yes Total water volume (6) 106 33 kPa Type Water volume Water circuit 33 1 Water cooled Power input Water filter 1 Model Output Nominal ESP unit Expansion vessel 2 rpm Nr. of speed Water side Heat exchanger 2 Heating Quantity Motor Motor 2 Brushless DC Drive Compressor 2 Horizontal l • AlthermaTM • Monobloc 5.5 5.5 5.5 • Monobloc • EDHQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power Voltage range EDHQ011AA6W1 EDHQ014AA6W1 Name W1 Phase 3N~ EDHQ016AA6W1 Frequency Hz 50 50 50 Voltage V 400 400 400 Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A 5.8 5.8 5.8 Maximum running current Heating A 14 14 14 Power supply compressor component Current Recomended A fuses 20 20 20 Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply Phase Current Running Current Current back-up heater 3 2 See installation manual 6W1 3~ Frequency Hz 50 50 50 Voltage V 400 400 400 Running Current Back-up heater A 8.7 8.7 8.7 Back-up heater + booster heater +EK*V3 A 21.7(8.7+13) +EK*Z2 A 16.2(8.7+7.5) Minimum Ssc value +EK*V3 kVa Equipment complying with EN/IEC 61000-3-12(**) +EK*Z2 kVa Equipment complying with EN/IEC 61000-3-12(**) • AlthermaTM • Monobloc 107 • Monobloc • EDHQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDHQ011AA6W1 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDHQ016AA6W1 -10% Quantity of wires 3 EDHQ014AA6W1 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 108 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 3 Options EDHQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 109 • Monobloc • EDHQ011-016AA6W1 3 Options EDHQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 110 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EDHQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 111 • Monobloc • EDHQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDHQ011-016AA6W1 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 112 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EDLH011-016AA6W1 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58135-1A • AlthermaTM • Monobloc 113 • Monobloc • EDHQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EDHQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.5 Page 2 Only for E(D/B)LO* 3 7 Reactor terminal position Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. Position of compressor terminal Option A1P A2P A3P BS1∼BS4 C1∼C4 DS1 E1HC E1H F1U F2U F3U F4U F5U F6U F7U F8U, F9U H1P∼7P (A1P) HAP (A1P) HAP (A2P) K1M∼K2M K1R (A1P) K1R (A2P) K2R (A1P) K3R (A1P) L1R∼L3R L4R M1C M1F M2F PS Q1DI R1∼R4 R1T R2T R3T R4T R5T R6T R7T S1NPH S1PH V1R, V2R V3R X1M Y1E Y1S Y3S Z1C∼Z9C Z1F∼Z4F Optional connector X6A X77A X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Push button switch Capacitor DIP switch Crankcase heater Bottomplate heater Fuse (T 31,5A/250V) Fuse (T 31,5A/250V) Fuse (T 6.3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 5,0A/250V) Fuse (T 1,0A/250V) Pilotlamp (service monitor - orange) Pilotlamp (service monitor - green) Pilotlamp (service monitor - green) Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (Y2S) Magnetic relay (E1HC) Reactor Reactor (For outdoor fan motor) Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Earth leakage protector Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Thermistor (Fin) Pressure sensor Pressure switch (High) Power module Diode module Terminal strip Electronic expansion valve Solenoid valve (4 way valve) Solenoid valve Noise filter Noise filter Connector Connector Connector Wiring dependent on model Reactor box El. comp. Assy (Position of elements) Arrow A Arrow B 2TW58136-1 EDHQ011-016AA6W1 Only for E(D/B)LO* Option Only for EKSOLHWAV1 Option Power supply E11H-E12H-E13H / E4H Domestic hot water tank Domestic hot water tank Solar pump connection >> See note 2 << See note 9 Only for *KHWE*V3 Option Only for *KHW(S/E)* Option Only for *KHWS*Z2 Option See note 7 For *KHWSU*V3 Option User interface From compressor module switchbox (B.7 PageA) Cooling/heating on/off output See note 8 Standard 6kw (_) See note 10 230V AC heating cooling Domestic hot water tank Domestic hot water tank Only for *KHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHWS*Z2 Option Only for *KHW* Option Only for *KRTW Option Solar input Only for EKRP1HB & ESOLHWAV1 Option Alarm output Outdoor unit supply from PCB Only for *KRTR Option 3 wire type (SPST) Only for *KHW* Option NO valve Only for EKSOLHWAV1 Option Only for EKHW(S/E)* Option Only for EKRTETS Option Example field supply thermostat Reduced 3.5kw ( ) See note 10 Wiring dependent on model Option PCB Field wiring Field wiring Wire colour Electric heater fuse Model 6WN F1B 16A KHW kit fuse F2B 20A A11P A12P A3P (*KRTW) A4P (*KRTR) A4P (EKRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump M1P : Pump M2S : 2 way valve for cooling mode M3S : 3 way valve: floorheating/domestic hot water PHC1 : Optocoupler input circuit Q1DI : Earth leakage protector Q1L : Thermal protector backup heater Q2L/Q3L : Thermal protector 1/2Booster heater R1H (*KRTR)) : Humidity sensor R1T (*KRTW/R) : Ambient sensor R2T (EKRTETS) : External sensor (floor or ambient) R11T : Outlet water heat-exchanger thermistor R12T : Outlet water backup heater thermistor R13T : Refrigerant liquid side thermistor R14T : Inlet water thermistor R5T (*KHW*) : Domestic hot water thermistor S1L : Flowswitch S1S : Solar pumpstation relay S2S : benefit kWh rate power supply contact SS1 : DIP switch S1T : thermostat switchbox heater S2T : thermostat expansion vessel heater TR1 : Transformer 24V for PCB V1S, V2S : Spark suppression 1, 2 X1M-X10M : Terminal strips X2Y : Connector NC valve Notes: Domestic hot water tank Domestic hot water tank Only for *KHWE*V3 Option Only for *KHWE*Z2 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58136-1 114 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EDHQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth 230V 3 core 3 or4 core Optional parts Only for EKRP1HB & EKSOLHWAV1 230V X1M:1-2-3-Earth A4P: Y1 Alarm output A4P: Y2 Cooling/Heating on/off output 2 way valve Power supply booster heater A4P: Y3 Solar input 2 core 2x0.75 X7M X5M F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 NO valve: X2M: 6-7 NC valve: X2M: 5-7 X4M:1-2-Earth Alarm indication 230V X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core X3M: L1-L2-Earth or L-N-Earth Q*L Clixon 7 1 core A4P: YC X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 3 2 core Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT X2M: 16-160 User interface communication 3TW58016-2A • AlthermaTM • Monobloc 115 • Monobloc • EDHQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EDHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 116 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EDHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 • AlthermaTM • Monobloc 117 • Monobloc • EDHQ011-016AA6W1 9 Installation 9-1 Service space EDHQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 118 • AlthermaTM • Monobloc • Monobloc • EDHQ011-016AA6W1 10 Operation range Outdoor temp. (°CDB) Cooling mode EDHQ011-016AA6W1 3 only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58133-1A • AlthermaTM • Monobloc 119 • Monobloc • EDHQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EDHQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. 120 • AlthermaTM • Monobloc 4TW58019-2 • Monobloc • EDLQ011-016AA6V3 TABLE OF CONTENTS EDLQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 123 124 125 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Heating capacity tables 5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 130 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 133 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 132 134 135 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 121 • Monobloc • EDLQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnL Dlo E•MA Features Heating only monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 122 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 16.00 Heating capacity Nominal kW 11.20 14.00 Heating PI Nominal kW 2.47 3.20 3.79 COP Nominal 4.54 4.37 4.22 15.06 Heating capacity Nominal kW 10.87 13.10 Heating PI Nominal kW 3.22 3.91 4.62 COP Nominal 3.37 3.35 3.26 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EDLQ011AA6V3 Colour Unit Packing Weight Packing 2 EDLQ016AA6V3 Ivory white Material Dimensions EDLQ014AA6V3 3 Painted galvanised steel Height mm 1,418 Width mm 1,435 Depth mm Height mm 382 382 382 1,557 Width mm Depth mm 430 1,500 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Material 430 Wood Carton Plastic foil Weight Operation Range Heating - Ambient Min Max Sound Level (Night quiet) Refrigerant 20 20 20 °CDB -15 -15 -15 °CDB 35 35 35 Heating - Waterside Min °C 15 15 15 Max °C 55 55 55 °CDB -15 -15 -15 Domestic hot water Min -Ambient Max Sound Level (nominal) kg °CDB 43 43 43 Domestic hot water Min - Waterside Max °C 25 25 25 °C 80 80 80 Heating Sound Power dBA 64 64 66 Sound Pressure dBA 51 51 52 Sound Pressure dBA 42 42 43 Heating Type Charge R-410A kg 2.95 Control Nr of Circuits Refrigerant Oil 1 Type Charged Volume 2.95 2.95 Electronic expansion valve 1 1 Daphne FVC68D l 1.0 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee • AlthermaTM • Monobloc 123 • Monobloc • EDLQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 3 60 Tube type Hi-XSS Fin 2 Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity Air Flow Rate (nominal at 230V) Heating Fan Discharge direction High m³/min 2 2 2 90 90 90 Horizontal Motor Quantity 2 Model Motor Fan Speed (nominal) Steps Motor 8 8 8 rpm 760 760 760 Output W 70 70 70 Direct drive Quantity 1 Motor Motor Crankcase Heater Pump Type JT100G-VD Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven Output W 33 Heating Power input 2 2 2 52.5 43.5 35.0 W 210 210 210 Brazed plate Quantity l Water flow rate Min. Water flow rate Nom. Heating Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 l/min 32.1 40.1 45.9 l/min 58 58 58 Insulation material Foamed synthetic elastomer Volume l 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit 10 Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 3 Manometer Yes Drain valve / Fill valve yes Shut off valve yes Air purge valve 3 yes Total water volume (6) 124 33 kPa Type Water volume Water filter 33 1 Water cooled Nominal ESP unit Expansion vessel 1 Model Nr. of speed Water side Heat exchanger 2 Heating Drive Compressor 2 Brushless DC l • AlthermaTM • Monobloc 5.5 5.5 5.5 • Monobloc • EDLQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power EDLQ011AA6V3 Name EDLQ014AA6V3 EDLQ016AA6V3 V3 Phase 1 1 1 50 50 230 230 Frequency Hz 50 230 Voltage V Voltage range Minimum V Maximum V Current Minimum Ssc value kVa Recomende d fuses A Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply -10% +10% 3 Equipment complying with EN/IEC 61000-3-12(*) 32 32 32 See installation manual 6V3 Phase 1~ Frequency Hz 50 50 50 Voltage V 230 230 230 Running Current Back-up heater A 26 26 26 Running Current Back-up heater + booster heater +EK*V3 A Current back-up heater Z-max Back-up heater A 0.29 0.29 0.29 Back-up heater + booster heater A 0.17 0.17 0.17 Minimum Ssc value +EK*V3 2 kVa • AlthermaTM • Monobloc 39(26+13) Equipment complying with EN/IEC 61000-3-12(**) 125 • Monobloc • EDLQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDLQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 2G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDLQ016AA6V3 -10% Quantity of wires 3 EDLQ014AA6V3 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 126 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 3 Options EDLQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 127 • Monobloc • EDLQ011-016AA6V3 3 Options EDLQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 128 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EDLQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 129 • Monobloc • EDLQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDLQ011-016AA6V3 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 130 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EDLQ011-016AA6V3 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Stop valve (with service port 5/16’ flare) Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58015-1A • AlthermaTM • Monobloc 131 • Monobloc • EDLQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EDLQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Fuse (F 1,0A/250V) Light Emit. Diode (Serv. Monitor-Orange) Prepare, Test --------- Flickering Malfunction Detection -- Light up Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip (Power supply) Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1C∼Z3C Z1F∼Z4F Optional connector X1Y 3 7 Connector Position of compressor terminal Wire entrance Option Wiring dependent on model Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. El. comp. Assy (Position of elements) 2TW58016-1 EDLQ011-016AA6V3 Outdoor unit Only for EC/BLQOption Only for EKSOLHWAV1Option Domestic hot water tank Solar pump connection Power supply 230V 1N∼50Hz Only for *KHWE*Option See note 9 >> See note 2 << Only for *KHW(S/E)*Option See note 7 For *KHWSU*V3 Option User interface F1B heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 Domestic hot water tank Only for *KHW Option Only for *KRTW* Option Solar input Alarm output Standard 6kw (_) See note 10 Cooling/heating on/off output From compressor module switchbox (B.7 PageA) supply from PCB Only for *KRTR* Option 3 wire type (SPST) NO valve Only forEKHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHW(S/E)* Option Only for EKHW Option Wiring dependent on model Only for EKRTETS* Option Field wiring Example field supply thermostat Reduced 3kw See note 10 Electric heater fuse 32A 230V AC Only for EKSOLHWAV1 Option Option Field wiring F2B PCB *KHW kit fuse 20A A11P A12P A3P (*KRTW) A4P (EKRTR) A4P (*KRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M K7M M1P M2S M3S PHC1 Q1DI Q1L Q2L R1H (*KRTR) R1T (*KRTW/R) R2T (EKRTETS) R11T R12T R13T R14T R5T (*KHW*) S1L S1S S2S SS1 S1T S2T TR1 V1S, V2S X1M-X10M X2Y : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection : Relay for solar pump : Pump : 2 way valve for cooling mode : 3 way valve: floorheating/domestic hot water : Optocoupler input circuit : Earth leakage protector : Thermal protector backup heater : Thermal protector 1/2Booster heater : Humidity sensor : Ambient sensor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Outlet water backup heater thermistor : Refrigerant liquid side thermistor : Inlet water thermistor : Domestic hot water thermistor : Flowswitch : Solar pumpstation relay : benefit kWh rate power supply contact : DIP switch : thermostat switchbox heater : thermostat expansion vessel heater : Transformer 24V for PCB : Spark suppression 1, 2 : Terminal strips : Connector Wire colour NC valve Notes: Domestic hot water tank Only for *KHWE*V3 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58016-1 132 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EDLQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth 230V 3 core 3 or4 core Optional parts Only for EKRP1HB & EKSOLHWAV1 230V X1M:1-2-3-Earth A4P: Y1 Alarm output A4P: Y2 Cooling/Heating on/off output 2 way valve Power supply booster heater A4P: Y3 Solar input 2 core 2x0.75 X7M X5M F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 NO valve: X2M: 6-7 NC valve: X2M: 5-7 X4M:1-2-Earth Alarm indication 230V X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core X3M: L1-L2-Earth or L-N-Earth Q*L Clixon 7 1 core A4P: YC X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 3 2 core Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT X2M: 16-160 User interface communication 3TW58016-2A • AlthermaTM • Monobloc 133 • Monobloc • EDLQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EDLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 134 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EDLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 • AlthermaTM • Monobloc 135 • Monobloc • EDLQ011-016AA6V3 9 Installation 9-1 Service space EDLQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 136 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6V3 10 Operation range EDLQ011-016AA6V3 3 Outdoor temp. (°CDB) Cooling mode only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58013-1A • AlthermaTM • Monobloc 137 • Monobloc • EDLQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EDLQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. 138 • AlthermaTM • Monobloc 4TW58019-2 • Monobloc • EDLQ011-016AA6W1 TABLE OF CONTENTS EDLQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 141 142 143 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 Heating capacity tables 5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 148 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 151 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 150 152 153 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156 139 • Monobloc • EDLQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnL Dlo E•MA Features Heating only monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 140 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 Heating capacity Nominal kW 11.20 14.00 16.00 Heating PI Nominal kW 2.51 3.22 3.72 COP Nominal 4.46 4.35 4.30 Heating capacity Nominal kW 10.87 13.10 15.06 Heating PI Nominal kW 3.12 3.98 4.58 COP Nominal 3.48 3.29 3.29 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EDLQ011AA6W1 Colour Unit Weight Packing EDLQ016AA6W1 Painted galvanised steel Height mm 1,418 Width mm 1,435 Depth mm Height mm Width mm Depth mm 430 430 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Packing 2 Ivory white Material Dimensions EDLQ014AA6W1 3 382 382 382 1,557 1,500 Material Wood Carton Plastic foil Weight Operation Range Heating - Ambient kg 20 20 20 Min °CDB -15 -15 -15 Max 35 °CDB 35 35 Heating - Waterside Min °C 15 15 15 Max °C 55 55 55 Domestic hot water -Ambient Min °CDB -15 -15 -15 Max °CDB 43 43 43 Domestic hot water - Waterside Min °C 25 25 25 Max °C 80 80 80 Sound Level (nominal) Heating Sound Pressure dBA 49 51 53 Sound Level (Night quiet) Heating Sound Pressure dBA 42 42 43 Refrigerant Type Charge R-410A kg 2.95 Control Nr of Circuits Refrigerant Oil 1 Type Charged Volume 2.95 2.95 Electronic expansion valve 1 1 Daphne FVC68D l 1.0 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee • AlthermaTM • Monobloc 141 • Monobloc • EDLQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 3 60 Tube type Hi-XSS Fin 2 Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 Discharge direction Motor Quantity 2 Model Motor Fan Speed (nominal) Steps Motor Crankcase Heater Pump Type 8 8 8 760 760 760 Output W 70 70 70 Direct drive 1 JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven W 33 Heating 2 2 2 52.5 43.5 35 W 210 210 210 Brazed plate Quantity l Water flow rate Min. Water flow rate Nom. Heating Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 l/min 32.1 40.1 45.9 l/min 58 58 58 Insulation material Foamed synthetic elastomer Volume l 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material 10 Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 3 Manometer Yes Drain valve / Fill valve yes Shut off valve yes Air purge valve yes Total water volume (6) 142 33 kPa Type Water volume Water circuit 33 1 Water cooled Power input Water filter 1 Model Output Nominal ESP unit Expansion vessel 2 rpm Nr. of speed Water side Heat exchanger 2 Heating Quantity Motor Motor 2 Brushless DC Drive Compressor 2 Horizontal l • AlthermaTM • Monobloc 5.5 5.5 3 5.5 • Monobloc • EDLQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power Voltage range EDLQ011AA6W1 EDLQ014AA6W1 Name W1 Phase 3N~ EDLQ016AA6W1 Frequency Hz 50 50 50 Voltage V 400 400 400 Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A 5.8 5.8 5.8 Maximum running current Heating A 14 14 14 Power supply compressor component Current Recomended A fuses 20 20 20 Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply Current Running Current Current back-up heater 3 2 6W1 Phase 3~ Frequency Hz 50 50 50 Voltage V 400 400 400 Running Current Back-up heater A 8.7 8.7 8.7 Back-up heater + booster heater +EK*V3 A 21.7(8.7+13) +EK*Z2 A 16.2(8.7+7.5) Minimum Ssc value +EK*V3 kVa Equipment complying with EN/IEC 61000-3-12(**) +EK*Z2 kVa Equipment complying with EN/IEC 61000-3-12(**) • AlthermaTM • Monobloc 143 • Monobloc • EDLQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDLQ011AA6W1 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDLQ016AA6W1 -10% Quantity of wires 3 EDLQ014AA6W1 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 144 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 3 Options EDLQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 145 • Monobloc • EDLQ011-016AA6W1 3 Options EDLQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1 A K2 A Boiler thermostat A uxiliary contact (normal closed) Heating only room thermostat A uxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) A uxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q * unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5 146 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EDLQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 147 • Monobloc • EDLQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDLQ011-016AA6W1 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 148 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EDLQ011-016AA6W1 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58135-1A • AlthermaTM • Monobloc 149 • Monobloc • EDLQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EDLQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.5 Page 2 Only for E(D/B)LO* 3 7 Reactor terminal position Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. Position of compressor terminal Option A1P A2P A3P BS1∼BS4 C1∼C4 DS1 E1HC E1H F1U F2U F3U F4U F5U F6U F7U F8U, F9U H1P∼7P (A1P) HAP (A1P) HAP (A2P) K1M∼K2M K1R (A1P) K1R (A2P) K2R (A1P) K3R (A1P) L1R∼L3R L4R M1C M1F M2F PS Q1DI R1∼R4 R1T R2T R3T R4T R5T R6T R7T S1NPH S1PH V1R, V2R V3R X1M Y1E Y1S Y3S Z1C∼Z9C Z1F∼Z4F Optional connector X6A X77A X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Push button switch Capacitor DIP switch Crankcase heater Bottomplate heater Fuse (T 31,5A/250V) Fuse (T 31,5A/250V) Fuse (T 6.3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 5,0A/250V) Fuse (T 1,0A/250V) Pilotlamp (service monitor - orange) Pilotlamp (service monitor - green) Pilotlamp (service monitor - green) Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (Y2S) Magnetic relay (E1HC) Reactor Reactor (For outdoor fan motor) Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Earth leakage protector Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Thermistor (Fin) Pressure sensor Pressure switch (High) Power module Diode module Terminal strip Electronic expansion valve Solenoid valve (4 way valve) Solenoid valve Noise filter Noise filter Connector Connector Connector Wiring dependent on model Reactor box Arrow A El. comp. Assy (Position of elements) Arrow B 2TW58136-1 EDLQ011-016AA6W1 Only for E(D/B)LO* Option Only for EKSOLHWAV1 Option Power supply E11H-E12H-E13H / E4H Domestic hot water tank Domestic hot water tank Solar pump connection >> See note 2 << See note 9 Only for *KHWE*V3 Option Only for *KHW(S/E)* Option Only for *KHWS*Z2 Option See note 7 For *KHWSU*V3 Option User interface From compressor module switchbox (B.7 PageA) Cooling/heating on/off output See note 8 Standard 6kw (_) See note 10 230V AC heating cooling Domestic hot water tank Domestic hot water tank Only for *KHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHWS*Z2 Option Only for *KHW* Option Only for *KRTW Option Solar input Only for EKRP1HB & ESOLHWAV1 Option Alarm output Outdoor unit supply from PCB Only for *KRTR Option 3 wire type (SPST) Only for *KHW* Option NO valve Only for EKSOLHWAV1 Option Only for EKHW(S/E)* Option Only for EKRTETS Option Example field supply thermostat Reduced 3.5kw ( ) See note 10 Wiring dependent on model Option PCB Field wiring Field wiring Wire colour Electric heater fuse Model 6WN F1B 16A KHW kit fuse F2B 20A A11P A12P A3P (*KRTW) A4P (*KRTR) A4P (EKRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump M1P : Pump M2S : 2 way valve for cooling mode M3S : 3 way valve: floorheating/domestic hot water PHC1 : Optocoupler input circuit Q1DI : Earth leakage protector Q1L : Thermal protector backup heater Q2L/Q3L : Thermal protector 1/2Booster heater R1H (*KRTR)) : Humidity sensor R1T (*KRTW/R) : Ambient sensor R2T (EKRTETS) : External sensor (floor or ambient) R11T : Outlet water heat-exchanger thermistor R12T : Outlet water backup heater thermistor R13T : Refrigerant liquid side thermistor R14T : Inlet water thermistor R5T (*KHW*) : Domestic hot water thermistor S1L : Flowswitch S1S : Solar pumpstation relay S2S : benefit kWh rate power supply contact SS1 : DIP switch S1T : thermostat switchbox heater S2T : thermostat expansion vessel heater TR1 : Transformer 24V for PCB V1S, V2S : Spark suppression 1, 2 X1M-X10M : Terminal strips X2Y : Connector NC valve Notes: Domestic hot water tank Domestic hot water tank Only for *KHWE*V3 Option Only for *KHWE*Z2 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58136-1 150 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EDLQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth 230V 3 core 3 or4 core Optional parts Only for EKRP1HB & EKSOLHWAV1 230V X1M:1-2-3-Earth A4P: Y1 Alarm output A4P: Y2 Cooling/Heating on/off output 2 way valve Power supply booster heater A4P: Y3 Solar input 2 core 2x0.75 X7M X5M F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 NO valve: X2M: 6-7 NC valve: X2M: 5-7 X4M:1-2-Earth Alarm indication 230V X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core X3M: L1-L2-Earth or L-N-Earth Q*L Clixon 7 1 core A4P: YC X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 3 2 core Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT X2M: 16-160 User interface communication 3TW58016-2A • AlthermaTM • Monobloc 151 • Monobloc • EDLQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EDLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 152 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EDLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 • AlthermaTM • Monobloc 153 • Monobloc • EDLQ011-016AA6W1 9 Installation 9-1 Service space EDLQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 154 • AlthermaTM • Monobloc • Monobloc • EDLQ011-016AA6W1 10 Operation range Outdoor temp. (°CDB) Cooling mode EDLQ011-016AA6W1 3 only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58133-1A • AlthermaTM • Monobloc 155 • Monobloc • EDLQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EDLQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. 156 • AlthermaTM • Monobloc 4TW58019-2 • Monobloc • EBHQ011-016AA6V3 TABLE OF CONTENTS EBHQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 159 160 161 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 Heating capacity tables Cooling capacity tables 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 167 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 169 170 171 172 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175 157 • Monobloc • EBHQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tHn Blo E•MA Features Reversible monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 158 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.47 3.20 3.79 Cooling PI Nominal kW 3.78 5.65 6.28 COP Nominal 4.54 4.37 4.22 EER Nominal 3.39 2.83 2.66 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.10 Heating PI Nominal kW 3.22 3.91 4.62 Cooling PI Nominal kW COP Nominal EER Nominal 3.60 5.30 5.85 3.37 3.35 3.26 2.78 2.36 2.24 3 2 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EBHQ011AA6V3 Colour Unit Packing Painted galvanised steel Height mm 1,418 Width mm 1,435 Depth mm Height mm Width mm Depth mm 430 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Packing Weight EBHQ016AA6V3 Ivory white Material Dimensions EBHQ014AA6V3 382 382 382 1,557 1,500 Material 430 Wood Carton Plastic foil Weight Operation Range Heating - Ambient Min Max 20 -15 -15 -15 °CDB 35 35 35 15 15 15 Max °C 55 55 55 Min °CDB 10 10 10 46 °CDB 46 46 Cooling - Waterside Min °C 5 5 5 Max °C 22 22 22 Domestic hot water -Ambient Min °CDB -15 -15 -15 Max °CDB 43 43 43 Domestic hot water - Waterside Min °C 25 25 25 Max °C 80 80 80 Heating Sound Power dBA 64 64 66 Sound Pressure dBA 51 51 52 Sound Power dBA 65 66 69 Sound Pressure dBA 50 52 54 Heating Sound Pressure dBA 42 42 43 Cooling Sound Pressure dBA 45 45 46 Cooling Refrigerant 20 °CDB °C Max Sound Level (Night quiet) 20 Heating - Waterside Min Cooling - Ambient Sound Level (nominal) kg Type Charge R-410A kg 2.95 Control 2.95 2.95 Electronic expansion valve Nr of Circuits 1 • AlthermaTM • Monobloc 1 1 159 • Monobloc • EBHQ011-016AA6V3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBHQ011AA6V3 Type Charged Volume l 1.0 2 EBHQ016AA6V3 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBHQ014AA6V3 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee 2-3 MAIN COMPONENTS Air heat exchanger Specifications Length EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 60 Tube type Hi-XSS Fin Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 2 2 90 90 100 97 Air Flow Rate (nominal at 230V) Heating High m³/min 90 Cooling High m³/min 96 Fan Discharge direction Horizontal Motor Quantity 2 Model Motor Speed (nominal) Steps Motor 8 8 8 760 760 760 Cooling rpm 780 780 780 Output W 70 70 70 Drive Compressor Direct drive Quantity 1 Motor Motor Crankcase Heater Pump Type JT100G-VD Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven Output W 33 33 1 33 Water cooled Nominal ESP unit Heating Cooling Power input 2 2 2 kPa 52.5 43.5 35.0 kPa 55.9 49.1 46.8 W 210 210 210 Type Brazed plate Quantity Water volume l Water flow rate Min. Water flow rate Nom. Heating Cooling Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 l/min 32.1 40.1 45.9 l/min 36.8 45.9 48.0 l/min 58 58 58 Insulation material 160 1 Model Nr. of speed Water side Heat exchanger 2 rpm Heating Fan 2 Brushless DC Foamed synthetic elastomer • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer Drain valve / Fill valve yes Shut off valve yes l ELECTRICAL SPECIFICATIONS Main Power 3 2 yes Total water volume (6) Power supply compressor component 3 Yes Air purge valve 2-4 3 5.5 5.5 5.5 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Name V3 Phase 1 1 1 Frequency Hz 50 50 50 230 230 230 Voltage V Voltage range Minimum V Maximum V Current Minimum Ssc value kVa Current Maximum running current Cooling A Power supply compressor component Current Recomended A fuses Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply -10% +10% Equipment complying with EN/IEC 61000-3-12(×) 22.8 27.4 31.9 32 32 32 See installiation manual 6V3 Phase 1~ Frequency Hz 50 50 50 Voltage V 230 230 230 Running Current Back-up heater A 26 26 26 Running Current Back-up heater + booster heater +EK*V3 A Current back-up heater Z-max Back-up heater A 0.29 0.29 0.29 Back-up heater + booster heater A 0.17 0.17 0.17 Minimum Ssc value +EK*V3 kVa • AlthermaTM • Monobloc 39(26+13) Equipment complying with EN/IEC 61000-3-12(**) 161 • Monobloc • EBHQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EBHQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 3G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBHQ016AA6V3 -10% Quantity of wires 3 EBHQ014AA6V3 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 162 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 3 Options EBHQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 1-Phase Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 Reference Description EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 163 • Monobloc • EBHQ011-016AA6V3 3 Options EBHQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 164 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EBHQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 165 • Monobloc • EBHQ011-016AA6V3 4 Capacity tables 4-2 Cooling capacity tables EBHQ011-016AA6V3 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 166 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W • Monobloc • EBHQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBHQ011-016AA6V3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve 3 Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 • AlthermaTM • Monobloc 167 • Monobloc • EBHQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EBHQ011-016AA6V3 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Stop valve (with service port 5/16’ flare) Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58015-1A 168 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EBHQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Fuse (F 1,0A/250V) Light Emit. Diode (Serv. Monitor-Orange) Prepare, Test --------- Flickering Malfunction Detection -- Light up Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip (Power supply) Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1C∼Z3C Z1F∼Z4F Optional connector X1Y 3 7 Connector Position of compressor terminal Wire entrance Option Wiring dependent on model Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. El. comp. Assy (Position of elements) 2TW58016-1 EBHQ011-016AA6V3 Outdoor unit Only for EC/BLQOption Only for EKSOLHWAV1Option Domestic hot water tank Solar pump connection Power supply 230V 1N∼50Hz Only for *KHWE*Option See note 9 >> See note 2 << Only for *KHW(S/E)*Option See note 7 For *KHWSU*V3 Option User interface F1B heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 Domestic hot water tank Only for *KHW Option Only for *KRTW* Option Solar input Alarm output Standard 6kw (_) See note 10 Cooling/heating on/off output From compressor module switchbox (B.7 PageA) supply from PCB Only for *KRTR* Option 3 wire type (SPST) NO valve Only forEKHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHW(S/E)* Option Only for EKHW Option Wiring dependent on model Only for EKRTETS* Option Field wiring Example field supply thermostat Reduced 3kw See note 10 Electric heater fuse 32A 230V AC Only for EKSOLHWAV1 Option Option Field wiring F2B PCB *KHW kit fuse 20A A11P A12P A3P (*KRTW) A4P (EKRTR) A4P (*KRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M K7M M1P M2S M3S PHC1 Q1DI Q1L Q2L R1H (*KRTR) R1T (*KRTW/R) R2T (EKRTETS) R11T R12T R13T R14T R5T (*KHW*) S1L S1S S2S SS1 S1T S2T TR1 V1S, V2S X1M-X10M X2Y : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection : Relay for solar pump : Pump : 2 way valve for cooling mode : 3 way valve: floorheating/domestic hot water : Optocoupler input circuit : Earth leakage protector : Thermal protector backup heater : Thermal protector 1/2Booster heater : Humidity sensor : Ambient sensor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Outlet water backup heater thermistor : Refrigerant liquid side thermistor : Inlet water thermistor : Domestic hot water thermistor : Flowswitch : Solar pumpstation relay : benefit kWh rate power supply contact : DIP switch : thermostat switchbox heater : thermostat expansion vessel heater : Transformer 24V for PCB : Spark suppression 1, 2 : Terminal strips : Connector Wire colour NC valve Notes: Domestic hot water tank Only for *KHWE*V3 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58016-1 • AlthermaTM • Monobloc 169 • Monobloc • EBHQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EBHQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT 230V Optional parts 3 or4 core 3 core 7 Only for EKRP1HB & EKSOLHWAV1 1 core A4P: YC X3M: L1-L2-Earth or L-N-Earth 2 way valve Q*L Clixon Power supply booster heater A4P: Y1 Alarm output X7M A4P: Y2 Cooling/Heating on/off output F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 X4M:1-2-Earth Alarm indication 230V NO valve: X2M: 6-7 NC valve: X2M: 5-7 X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core A4P: Y3 Solar input 2 core 2x0.75 X5M 230V X1M:1-2-3-Earth X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 2 core 3 Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth X2M: 16-160 User interface communication 3TW58016-2A 170 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EBHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 EBHQ011-016AA6V3 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-1 • AlthermaTM • Monobloc 171 • Monobloc • EBHQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EBHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 EBHQ011-016AA6V3 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-3 172 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 9 Installation 9-1 Service space EBHQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 • AlthermaTM • Monobloc 173 • Monobloc • EBHQ011-016AA6V3 10 Operation range EBHQ011-016AA6V3 Outdoor temp. (°CDB) 10 Cooling mode 3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58013-1A 174 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EBHQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. • AlthermaTM • Monobloc 4TW58019-2 175 • Monobloc • EBHQ011-016AA6W1 TABLE OF CONTENTS EBHQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 179 180 181 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185 Heating capacity tables Cooling capacity tables 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 187 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 189 190 191 192 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 177 • Monobloc • EBHQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tHn Blo E•MA Features Reversible monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 178 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.51 3.22 3.72 Cooling PI Nominal kW 3.78 5.32 6.06 COP Nominal 4.46 4.35 4.30 EER Nominal 3.39 3.01 2.76 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.10 Heating PI Nominal kW 3.12 3.98 4.58 Cooling PI Nominal kW 3.60 4.98 5.65 COP Nominal 3.48 3.29 3.29 EER Nominal 2.78 2.51 2.32 3 2 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EBHQ011AA6W1 Colour Unit Packing Weight Packing EBHQ016AA6W1 Ivory white Material Dimensions EBHQ014AA6W1 Painted galvanised steel Height mm Width mm Depth mm Height mm 1,418 1,435 382 382 382 1,557 Width mm Depth mm 430 1,500 430 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Material Wood Carton Plastic foil Weight Operation Range Heating - Ambient Refrigerant 20 20 -15 -15 -15 Max 35 °CDB 35 35 °C 15 15 15 Max °C 55 55 55 Min °CDB 10 10 10 Max °CDB 46 46 46 Cooling - Waterside Min °C 5 5 5 Max °C 22 22 22 Domestic hot water -Ambient Min °CDB -15 -15 -15 Max °CDB 43 43 43 Domestic hot water - Waterside Min °C 25 25 25 Max °C 80 80 80 Heating Sound Power dBA 64 64 66 Sound Pressure dBA 49 51 53 Sound Power dBA 65 66 69 Sound Pressure dBA 50 52 54 Heating Sound Pressure dBA 42 42 43 Cooling Sound Pressure dBA 45 45 46 Cooling Sound Level (Night quiet) 20 °CDB Heating - Waterside Min Cooling - Ambient Sound Level (nominal) kg Min Type Charge R-410A kg 2.95 Control 2.95 2.95 Electronic expansion valve Nr of Circuits 1 • AlthermaTM • Monobloc 1 1 179 • Monobloc • EBHQ011-016AA6W1 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBHQ011AA6W1 Type Charged Volume l 1.0 2 EBHQ016AA6W1 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBHQ014AA6W1 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee 2-3 MAIN COMPONENTS Air heat exchanger Specifications Length EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 60 Tube type Hi-XSS Fin Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 Discharge direction Motor Quantity 2 Model Motor Speed (nominal) Motor Motor Crankcase Heater Pump Type 8 8 8 760 760 Cooling rpm 780 780 780 Output W 70 70 70 Direct drive 1 JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven Output W 33 33 1 33 Water cooled Nominal ESP unit 2 2 2 Heating kPa 52.5 43.5 35.0 Cooling kPa 55.9 49.1 46.8 W 210 210 210 Power input Type Brazed plate Quantity Water volume l Water flow rate Min. Water flow rate Nom. Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 Heating l/min 32.1 40.1 45.9 Cooling l/min 36.8 45.9 48.0 l/min 58 58 58 Insulation material 180 1 Model Nr. of speed Water side Heat exchanger 2 760 Quantity Motor 2 rpm Drive Compressor 2 Brushless DC Steps Heating Fan 2 Horizontal Foamed synthetic elastomer • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer Drain valve / Fill valve yes Shut off valve yes l 5.5 ELECTRICAL SPECIFICATIONS Main Power EBHQ011AA6W1 Name 5.5 EBHQ014AA6W1 5.5 EBHQ016AA6W1 3N~ Frequency Hz 50 50 50 Voltage V 400 400 400 Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A Maximum running current Heating A 14 14 14 Cooling A 13.5 13.5 13.5 Power supply compressor component Current Recomended A fuses 20 20 20 Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply Current Running Current Current back-up heater 5.8 5.8 5.8 See installation manual 6W1 Phase 3~ Frequency Hz 50 50 50 Voltage V 400 400 400 Running Current Back-up heater A 8.7 8.7 8.7 Back-up heater + booster heater +EK*V3 A 21.7(8.7+13) +EK*Z2 A 16.2(8.7+7.5) +EK*V3 kVa Equipment complying with EN/IEC 61000-3-12(**) +EK*Z2 kVa Equipment complying with EN/IEC 61000-3-12(**) Minimum Ssc value 2 W1 Phase Voltage range 3 yes Total water volume (6) Power supply compressor component 3 Yes Air purge valve 2-4 3 • AlthermaTM • Monobloc 181 • Monobloc • EBHQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component EBHQ011AA6W1 Voltage range Minimum V Maximum V Wiring connections Connection type +10% for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBHQ016AA6W1 -10% Quantity of wires 3 EBHQ014AA6W1 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 182 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 3 Options EBHQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 183 • Monobloc • EBHQ011-016AA6W1 3 Options EBHQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 184 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EBHQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 185 • Monobloc • EBHQ011-016AA6W1 4 Capacity tables 4-2 Cooling capacity tables EBHQ011-016AA6W1 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 186 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W • Monobloc • EBHQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBHQ011-016AA6W1 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve 3 Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 • AlthermaTM • Monobloc 187 • Monobloc • EBHQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EBHQ011-016AA6W1 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58135-1A 188 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EBHQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.5 Page 2 Only for E(D/B)LO* Reactor terminal position Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. Position of compressor terminal Option A1P A2P A3P BS1∼BS4 C1∼C4 DS1 E1HC E1H F1U F2U F3U F4U F5U F6U F7U F8U, F9U H1P∼7P (A1P) HAP (A1P) HAP (A2P) K1M∼K2M K1R (A1P) K1R (A2P) K2R (A1P) K3R (A1P) L1R∼L3R L4R M1C M1F M2F PS Q1DI R1∼R4 R1T R2T R3T R4T R5T R6T R7T S1NPH S1PH V1R, V2R V3R X1M Y1E Y1S Y3S Z1C∼Z9C Z1F∼Z4F Optional connector X6A X77A X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Push button switch Capacitor DIP switch Crankcase heater Bottomplate heater Fuse (T 31,5A/250V) Fuse (T 31,5A/250V) Fuse (T 6.3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 5,0A/250V) Fuse (T 1,0A/250V) Pilotlamp (service monitor - orange) Pilotlamp (service monitor - green) Pilotlamp (service monitor - green) Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (Y2S) Magnetic relay (E1HC) Reactor Reactor (For outdoor fan motor) Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Earth leakage protector Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Thermistor (Fin) Pressure sensor Pressure switch (High) Power module Diode module Terminal strip Electronic expansion valve Solenoid valve (4 way valve) Solenoid valve Noise filter Noise filter 3 7 Connector Connector Connector Wiring dependent on model Reactor box Arrow A El. comp. Assy (Position of elements) Arrow B 2TW58136-1 EBHQ011-016AA6W1 Only for E(D/B)LO* Option Only for EKSOLHWAV1 Option Power supply E11H-E12H-E13H / E4H Domestic hot water tank Domestic hot water tank Solar pump connection >> See note 2 << See note 9 Only for *KHWE*V3 Option Only for *KHW(S/E)* Option Only for *KHWS*Z2 Option See note 7 For *KHWSU*V3 Option User interface From compressor module switchbox (B.7 PageA) Cooling/heating on/off output See note 8 Standard 6kw (_) See note 10 230V AC heating cooling Domestic hot water tank Domestic hot water tank Only for *KHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHWS*Z2 Option Only for *KHW* Option Only for *KRTW Option Solar input Only for EKRP1HB & ESOLHWAV1 Option Alarm output Outdoor unit supply from PCB Only for *KRTR Option 3 wire type (SPST) Only for *KHW* Option NO valve Only for EKSOLHWAV1 Option Only for EKHW(S/E)* Option Only for EKRTETS Option Example field supply thermostat Reduced 3.5kw ( ) See note 10 Wiring dependent on model Option PCB Field wiring Field wiring Wire colour Electric heater fuse Model 6WN F1B 16A KHW kit fuse F2B 20A A11P A12P A3P (*KRTW) A4P (*KRTR) A4P (EKRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump M1P : Pump M2S : 2 way valve for cooling mode M3S : 3 way valve: floorheating/domestic hot water PHC1 : Optocoupler input circuit Q1DI : Earth leakage protector Q1L : Thermal protector backup heater Q2L/Q3L : Thermal protector 1/2Booster heater R1H (*KRTR)) : Humidity sensor R1T (*KRTW/R) : Ambient sensor R2T (EKRTETS) : External sensor (floor or ambient) R11T : Outlet water heat-exchanger thermistor R12T : Outlet water backup heater thermistor R13T : Refrigerant liquid side thermistor R14T : Inlet water thermistor R5T (*KHW*) : Domestic hot water thermistor S1L : Flowswitch S1S : Solar pumpstation relay S2S : benefit kWh rate power supply contact SS1 : DIP switch S1T : thermostat switchbox heater S2T : thermostat expansion vessel heater TR1 : Transformer 24V for PCB V1S, V2S : Spark suppression 1, 2 X1M-X10M : Terminal strips X2Y : Connector NC valve Notes: Domestic hot water tank Domestic hot water tank Only for *KHWE*V3 Option Only for *KHWE*Z2 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58136-1 • AlthermaTM • Monobloc 189 • Monobloc • EBHQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EBHQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT 230V 3 core Optional parts 3 or4 core 7 Only for EKRP1HB & EKSOLHWAV1 1 core A4P: YC X3M: L1-L2-Earth or L-N-Earth 2 way valve X5M Power supply booster heater X6M A4P: Y1 Alarm output X7M A4P: Y2 Cooling/Heating on/off output F28 230V Only for EKHWSU*V3 5 core G5 x 2.5 X4M:1-2-Earth Alarm indication 230V NO valve: X2M: 6-7 NC valve: X2M: 5-7 X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application Solar pump 230V Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core A4P: Y3 Solar input 2 core 2x0.75 Q*L Clixon 230V X1M:1-2-3-Earth X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 2 core 3 Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth X2M: 16-160 User interface communication 3TW58016-2A 190 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EBHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 EBHQ011-016AA6W1 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-1 • AlthermaTM • Monobloc 191 • Monobloc • EBHQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EBHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 EBHQ011-016AA6W1 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-3 192 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 9 Installation 9-1 Service space EBHQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 • AlthermaTM • Monobloc 193 • Monobloc • EBHQ011-016AA6W1 10 Operation range 10 Outdoor temp. (°CDB) 3 Cooling mode EBHQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58133-1A 194 • AlthermaTM • Monobloc • Monobloc • EBHQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EBHQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. • AlthermaTM • Monobloc 4TW58019-2 195 • Monobloc • EBLQ011-016AA6V3 TABLE OF CONTENTS EBLQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 199 200 201 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 Heating capacity tables Cooling capacity tables 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 207 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 209 210 211 212 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215 197 • Monobloc • EBLQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hQo tLn Blo E•MA Features Reversible monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 198 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.47 3.20 3.79 Cooling PI Nominal kW 3.78 5.65 6.28 COP Nominal 4.54 4.37 4.22 EER Nominal 3.39 2.83 2.66 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.10 Heating PI Nominal kW 3.22 3.91 4.62 Cooling PI Nominal kW COP Nominal EER Nominal 3.60 5.30 5.85 3.37 3.35 3.26 2.78 2.36 2.24 3 2 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing EBLQ011AA6V3 Colour Unit Packing Painted galvanised steel Height mm 1,418 Width mm 1,435 Depth mm Height mm Width mm Depth mm 430 430 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Packing Weight EBLQ016AA6V3 Ivory white Material Dimensions EBLQ014AA6V3 382 382 382 1,557 1,500 Material Wood Carton Plastic foil Weight Operation Range Heating - Ambient Refrigerant 20 20 -15 -15 -15 Max 35 °CDB 35 35 °C 15 15 15 Max °C 55 55 55 Min °CDB 10 10 10 Max °CDB 46 46 46 Cooling - Waterside Min °C 5 5 5 Max °C 22 22 22 -15 Domestic hot water -Ambient Min °CDB -15 -15 Max °CDB 43 43 43 Domestic hot water - Waterside Min °C 25 25 25 Max °C 80 80 80 Heating Sound Power dBA 64 64 66 Sound Pressure dBA 51 51 52 Sound Power dBA 65 66 69 Sound Pressure dBA 50 52 54 Heating Sound Pressure dBA 42 42 43 Cooling Sound Pressure dBA 45 45 46 Cooling Sound Level (Night quiet) 20 °CDB Heating - Waterside Min Cooling - Ambient Sound Level (nominal) kg Min Type Charge R-410A kg 2.95 Control 2.95 2.95 Electronic expansion valve Nr of Circuits 1 • AlthermaTM • Monobloc 1 1 199 • Monobloc • EBLQ011-016AA6V3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBLQ011AA6V3 Type Charged Volume l 1.0 2 EBLQ016AA6V3 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBLQ014AA6V3 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee 2-3 MAIN COMPONENTS Air heat exchanger Specifications Length EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 60 Tube type Hi-XSS Fin Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 2 2 90 90 100 97 Air Flow Rate (nominal at 230V) Heating High m³/min 90 Cooling High m³/min 96 Fan Discharge direction Horizontal Motor Quantity 2 Model Motor Speed (nominal) Steps Motor 8 8 8 760 760 760 Cooling rpm 780 780 780 Output W 70 70 70 Drive Compressor Direct drive Quantity 1 Motor Motor Crankcase Heater Pump Type JT100G-VD Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven Output W 33 33 1 33 Water cooled Nominal ESP unit Heating Cooling Power input 2 2 2 kPa 52.5 43.5 35.0 kPa 55.9 49.1 46.8 W 210 210 210 Type Brazed plate Quantity Water volume l Water flow rate Min. Water flow rate Nom. Heating Cooling Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 l/min 32.1 40.1 45.9 l/min 36.8 45.9 48.0 l/min 58 58 58 Insulation material 200 1 Model Nr. of speed Water side Heat exchanger 2 rpm Heating Fan 2 Brushless DC Foamed synthetic elastomer • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer Drain valve / Fill valve yes Shut off valve yes l ELECTRICAL SPECIFICATIONS Main Power 3 2 yes Total water volume (6) Power supply compressor component 3 Yes Air purge valve 2-4 3 5.5 5.5 5.5 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Name V3 Phase 1 1 1 Frequency Hz 50 50 50 230 230 230 Voltage V Voltage range Minimum V Maximum V Current Minimum Ssc kVa value Current Maximum running current Cooling A 22.8 27.4 31.9 Power supply compressor component Current Recomende d fuses A 32 32 32 Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply -10% +10% Equipment complying with EN/IEC 61000-3-12(×) See installation manual 6V3 Phase 1~ Frequency Hz 50 50 50 Voltage V 230 230 230 Running Current Back-up heater A 26 26 26 Running Current Back-up heater + booster heater +EK*V3 A Current back-up heater Z-max Back-up heater A 0.29 0.29 0.29 Back-up heater + booster heater A 0.17 0.17 0.17 Minimum Ssc value +EK*V3 kVa • AlthermaTM • Monobloc 39(26+13) Equipment complying with EN/IEC 61000-3-12(**) 201 • Monobloc • EBLQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EBLQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 3G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBLQ016AA6V3 -10% Quantity of wires 3 EBLQ014AA6V3 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 202 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 3 Options EBLQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 203 • Monobloc • EBLQ011-016AA6V3 3 Options EBLQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 204 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EBLQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 205 • Monobloc • EBLQ011-016AA6V3 4 Capacity tables 4-2 Cooling capacity tables EBLQ011-016AA6V3 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 206 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W • Monobloc • EBLQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBLQ011-016AA6V3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve 3 Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 • AlthermaTM • Monobloc 207 • Monobloc • EBLQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EBLQ011-016AA6V3 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Stop valve (with service port 5/16’ flare) Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58015-1A 208 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EBLQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Fuse (F 1,0A/250V) Light Emit. Diode (Serv. Monitor-Orange) Prepare, Test --------- Flickering Malfunction Detection -- Light up Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip (Power supply) Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1C∼Z3C Z1F∼Z4F Optional connector X1Y 3 7 Connector Position of compressor terminal Wire entrance Option Wiring dependent on model Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. El. comp. Assy (Position of elements) 2TW58016-1 EBLQ011-016AA6V3 Outdoor unit Only for EC/BLQOption Only for EKSOLHWAV1Option Domestic hot water tank Solar pump connection Power supply 230V 1N∼50Hz Only for *KHWE*Option See note 9 >> See note 2 << Only for *KHW(S/E)*Option See note 7 For *KHWSU*V3 Option User interface F1B heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 Domestic hot water tank Only for *KHW Option Only for *KRTW* Option Solar input Alarm output Standard 6kw (_) See note 10 Cooling/heating on/off output From compressor module switchbox (B.7 PageA) supply from PCB Only for *KRTR* Option 3 wire type (SPST) NO valve Only forEKHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHW(S/E)* Option Only for EKHW Option Wiring dependent on model Only for EKRTETS* Option Field wiring Example field supply thermostat Reduced 3kw See note 10 Electric heater fuse 32A 230V AC Only for EKSOLHWAV1 Option Option Field wiring F2B PCB *KHW kit fuse 20A A11P A12P A3P (*KRTW) A4P (EKRTR) A4P (*KRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M K7M M1P M2S M3S PHC1 Q1DI Q1L Q2L R1H (*KRTR) R1T (*KRTW/R) R2T (EKRTETS) R11T R12T R13T R14T R5T (*KHW*) S1L S1S S2S SS1 S1T S2T TR1 V1S, V2S X1M-X10M X2Y : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection : Relay for solar pump : Pump : 2 way valve for cooling mode : 3 way valve: floorheating/domestic hot water : Optocoupler input circuit : Earth leakage protector : Thermal protector backup heater : Thermal protector 1/2Booster heater : Humidity sensor : Ambient sensor : External sensor (floor or ambient) : Outlet water heat-exchanger thermistor : Outlet water backup heater thermistor : Refrigerant liquid side thermistor : Inlet water thermistor : Domestic hot water thermistor : Flowswitch : Solar pumpstation relay : benefit kWh rate power supply contact : DIP switch : thermostat switchbox heater : thermostat expansion vessel heater : Transformer 24V for PCB : Spark suppression 1, 2 : Terminal strips : Connector Wire colour NC valve Notes: Domestic hot water tank Only for *KHWE*V3 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58016-1 • AlthermaTM • Monobloc 209 • Monobloc • EBLQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EBLQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT 230V Optional parts 3 or4 core 3 core 7 Only for EKRP1HB & EKSOLHWAV1 1 core A4P: YC X3M: L1-L2-Earth or L-N-Earth 2 way valve Q*L Clixon Power supply booster heater A4P: Y1 Alarm output X7M A4P: Y2 Cooling/Heating on/off output F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 X4M:1-2-Earth Alarm indication 230V NO valve: X2M: 6-7 NC valve: X2M: 5-7 X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core A4P: Y3 Solar input 2 core 2x0.75 X5M 230V X1M:1-2-3-Earth X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 2 core 3 Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth X2M: 16-160 User interface communication 3TW58016-2A 210 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EBLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 EBLQ011-016AA6V3 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-1 • AlthermaTM • Monobloc 211 • Monobloc • EBLQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EBLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 EBLQ011-016AA6V3 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-3 212 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 9 Installation 9-1 Service space EBLQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 • AlthermaTM • Monobloc 213 • Monobloc • EBLQ011-016AA6V3 10 Operation range EBLQ011-016AA6V3 Outdoor temp. (°CDB) 10 Cooling mode 3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58013-1A 214 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EBLQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. • AlthermaTM • Monobloc 4TW58019-2 215 • Monobloc • EBLQ011-016AA6W1 TABLE OF CONTENTS EBLQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 219 220 221 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223 4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225 Heating capacity tables Cooling capacity tables 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228 Piping diagram 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 227 Dimensional drawing 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 229 230 231 232 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234 11 Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 Static pressure drop unit • AlthermaTM • Monobloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 217 • Monobloc • EBLQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hQo tLn Blo E•MA Features Reversible monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 218 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.51 3.22 3.72 Cooling PI Nominal kW 3.78 5.32 6.06 COP Nominal 4.46 4.35 4.30 EER Nominal 3.39 3.01 2.76 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.10 Heating PI Nominal kW 3.12 3.98 4.58 Cooling PI Nominal kW 3.60 4.98 5.65 COP Nominal 3.48 3.29 3.29 EER Nominal 2.78 2.51 2.32 3 2 Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) Notes Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) 2-2 TECHNICAL SPECIFICATIONS Casing Colour Dimensions Unit EBLQ011AA6W1 Painted galvanised steel Height mm 1,418 Width mm 1,435 Depth mm Height mm Width mm Depth mm 430 430 Unit kg 180 180 180 Packed unit kg 200 200 200 Packing Packing EBLQ016AA6W1 Ivory white Material Weight EBLQ014AA6W1 382 382 382 1,557 1,500 Material 430 Wood Carton Plastic foil Weight Operation Range Heating - Ambient kg 20 20 20 Min °CDB -15 -15 -15 Max °CDB 35 35 35 Heating - Waterside Min °C 15 15 15 Max °C 55 55 55 Min °CDB 10 10 10 Max °CDB 46 46 46 Cooling - Waterside Min °C 5 5 5 Max °C 22 22 22 -15 Cooling - Ambient Domestic hot water Min -Ambient Max Sound Level (nominal) °CDB -15 -15 °CDB 43 43 43 Domestic hot water Min - Waterside Max °C 25 25 25 °C 80 80 80 Heating Sound Power dBA 64 64 66 Sound Pressure dBA 49 51 53 Sound Power dBA 65 66 69 Sound Pressure dBA 50 52 54 Heating Sound Pressure dBA 42 42 43 Cooling Sound Pressure dBA 45 45 46 Cooling Sound Level (Night quiet) Refrigerant Type Charge R-410A kg 2.95 Control 2.95 2.95 Electronic expansion valve Nr of Circuits 1 • AlthermaTM • Monobloc 1 1 219 • Monobloc • EBLQ011-016AA6W1 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBLQ011AA6W1 Type Charged Volume l 1.0 2 EBLQ016AA6W1 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBLQ014AA6W1 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) Conditions: Ta 35°C - LWE 7°C (DT = 5°C) 15°-25°C: BUH only, no heat pump operation = during commisioning including piping + PHE + back-up heater / excluding expansion vessel E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity guarantee 2-3 MAIN COMPONENTS Air heat exchanger Specifications Length EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.131 60 60 mm Nr of Rows Fin pitch Nr of Passes Face area Nr of Stages 60 Tube type Hi-XSS Fin Type WF fin Treatment Fan Anti-corrosion treatment (PE) Type Propeller Quantity 2 Discharge direction Motor Quantity 2 Model Motor Speed (nominal) Motor Motor Crankcase Heater Pump Type 8 8 8 760 760 Cooling rpm 780 780 780 Output W 70 70 70 Direct drive 1 JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven Output W 33 33 1 33 Water cooled Nominal ESP unit Heating Cooling Power input 2 2 2 kPa 52.5 43.5 35.0 kPa 55.9 49.1 46.8 W 210 210 210 Type Brazed plate Quantity Water volume l Water flow rate Min. Water flow rate Nom. Heating Cooling Water flow rate Max. 1 1 1 1.01 1.01 1.01 l/min 16 16 16 l/min 32.1 40.1 45.9 l/min 36.8 45.9 48.0 l/min 58 58 58 Insulation material 220 1 Model Nr. of speed Water side Heat exchanger 2 760 Quantity Motor 2 rpm Drive Compressor 2 Brushless DC Steps Heating Fan 2 Horizontal Foamed synthetic elastomer • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer Drain valve / Fill valve yes Shut off valve yes l ELECTRICAL SPECIFICATIONS Main Power 5.5 5.5 5.5 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Name 3N~ Frequency Hz 50 50 50 Voltage V 400 400 400 Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A Maximum running current Heating A 14 14 14 Cooling A 13.5 13.5 13.5 Power supply compressor component Current Recomended A fuses 20 20 20 Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply Phase Current Running Current Current back-up heater 2 W1 Phase Voltage range 3 yes Total water volume (6) Power supply compressor component 3 Yes Air purge valve 2-4 3 5.8 5.8 5.8 See installation manual 6W1 3~ Frequency Hz 50 50 50 Voltage V 400 400 400 Running Current Back-up heater A 8.7 8.7 8.7 Back-up heater + booster heater +EK*V3 A 21.7(8.7+13) +EK*Z2 A 16.2(8.7+7.5) Minimum Ssc value +EK*V3 kVa Equipment complying with EN/IEC 61000-3-12(**) +EK*Z2 kVa Equipment complying with EN/IEC 61000-3-12(**) • AlthermaTM • Monobloc 221 • Monobloc • EBLQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component EBLQ011AA6W1 Voltage range Minimum V Maximum V Wiring connections Connection type +10% for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBLQ016AA6W1 -10% Quantity of wires 3 EBLQ014AA6W1 3G Type of wires Select diameter and type according to national and local regulations Type of wires For more details on voltage range and current refer to installation manual Connection type for connection with R5T Quantity of wires Wire included in option EKHWS* Type of wires Wire included in option EKHWS* Connection type for connection with A3P Quantity of wires Depends on thermostat type, refer to installation manual Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M2S Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Connection type for connection with M3S Quantity of wires 3G or 4G Type of wires Select diameter and type according to national and local regulations Type of wires Voltage 230V / Maximum current: 100mA / Minimum 0.75mm² Notes Power supply compressor compartment is for compressor, fan, pump and controller In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax. Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Instructions see installation manual. Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to 5A. Instructions see installation manual. (1)European/International Technical Standard setting the limits for voltage changes , voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A. (2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16A =< 75A per phase. (3) System impedance Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank has a separate power supply. Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) 222 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 3 Options EBLQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 1-Phase Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 Reference Description EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKDK04 drain plug kit - - - V (2) V (2) V (2) - - - V (2) V (2) V (2) EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 Stainless domestic hot water tank 150l 1∼230V Stainless domestic hot water tank 200l 1∼230V Stainless domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWS200B3Z2 EKHWS300B3Z2 Stainless domestic hot water tank 200l 2∼400V Stainless domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 Enamel domestic hot water tank 150l 1∼230V Enamel domestic hot water tank 200l 1∼230V Enamel domestic hot water tank 300l 1∼230V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V EKHWE200A3Z2 EKHWE300A3Z2 Enamel domestic hot water tank 200l 2∼400V Enamel domestic hot water tank 300l 2∼400V V V V V V V V V V V V V V V V V V V V V V V V V EKHWET150A3V3 Wallmounted enamel domestic hot water tank 150l 1∼230V V V V V V V V V V V V V EKSOLHWAV1 Solarkit (4) V V V V V V V V V V V V EKRTW EKRTR EKRTETS Wired room thermostat option kit Wireless room thermostat option kit (incl. receiver) External temperature sensor option kit (3) V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V 3 3 Remark: Other combinations are not guaranteed. (1) (2) (3) (4) Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included It is not allowed to combine bottom plate heater and drain plug kit EKRTETS can only be used in combination with EKRTR Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating. Note: E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. 3TW58019-1 • AlthermaTM • Monobloc 223 • Monobloc • EBLQ011-016AA6W1 3 Options EBLQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. Boiler thermostat Auto / Boiler 1 2 3 4 Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the hydro module, including when the boiler is in operation for space heating. The auxiliary boiler can be integrated in the pipework and in the field wiring according to the illustrations below. Boiler thermostat C th K1A K2A Boiler thermostat Auxiliary contact (normal closed) Heating only room thermostat Auxiliary relay for activation of E(D/B)(H/L)Q * unit (field supply) Auxiliary relay for activation of boiler (field supply) Operation When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating, depending on the position of the auxiliary contact ( C ) Make sure that auxiliary contact ( C ) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun. Frequent switching may cause corrosion of the boiler in an early stage.Contact the manufacturer of the boiler. During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature. During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller. Never set the target leaving water temperature setpoint on the boiler controller above 55°C. Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Altherma unit. Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q * switch box correctly. Refer to ’ Room thermostat installation configuration’ in the installation manual supplied with the unit. 1 Compressor module 2 Hydro module 3 Heat exchanger 4 Pump 5 Shut-off valve 6 Collector (field supply) 7 Motorised 3-way valve (field supply) 8 Booster heater 9 Heat exchanger coil 10 Domestic hot water tank 11 Boiler (field supply) 12 Aquastat valve (field supply) 13 Shut-off valve (field supply) 14 Non-return valve (field supply) FHL 1...3 Floor heating loop (field supply) I User interface Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never exceeds 55°C. For this reason, never put the target leaving water temperature setpoint on the boiler controller above 55°C and it required, install an aquastat(*) valve in the return water flow of the E(D/B)(H/L)Q* unit. Daikin shall not be held liable fo any damage resulting from failure to observe this rule. (*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again. 3TW58019-5A 224 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EBLQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% (a) : only E(D/B)L* HC • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W 225 • Monobloc • EBLQ011-016AA6W1 4 Capacity tables 4-2 Cooling capacity tables EBLQ011-016AA6W1 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 226 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85% • AlthermaTM • Monobloc 1 2 3 Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Capacity values may not be extrapolated below 7°C leaving water temperature Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511). For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W • Monobloc • EBLQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBLQ011-016AA6W1 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21. Center of gravity Drain outlet Waterpiping outlet Waterpiping inlet Power supply cables intake Field wiring intake Service door switchbox Service door hydraulic module Service port Service door compresor module Pump REMOCON kit (to be installed indoors) Shut off valve Blow off valve Blow off drain (flexible base) Pressure gauge Water filter loadup ctrl motor + (18a) nipple Switchbox terminals Switchbox terminals option sanitary warm water tank Drain & fill valve 3 Center of gravity 5 Cutaway2 Cutaway1 Cutaway3 3TW58014-1 • AlthermaTM • Monobloc 227 • Monobloc • EBLQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EBLQ011-016AA6W1 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermistor (middle) Thermistor (Liquid 2) Pressure sensor Electronic expansion valve Crankcase heater Y1S Y3S S1PH M*F M*C R11T R12T R13T R14T : : : : : : : : : 4-way valve Injection valve High pressure switch Fan motor Compressor Outlet water heat-exchanger thermistor Outlet water backup heater thermistor Refrigerant liquid side thermistor Inlet water thermistor Heating Cooling 3TW58135-1A 228 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EBLQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.5 Page 2 Only for E(D/B)LO* Reactor terminal position Notes: 1 This wiring diagram only applies to the compressor module switchbox 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 NOT APPLICABLE 5 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’. Position of compressor terminal Option A1P A2P A3P BS1∼BS4 C1∼C4 DS1 E1HC E1H F1U F2U F3U F4U F5U F6U F7U F8U, F9U H1P∼7P (A1P) HAP (A1P) HAP (A2P) K1M∼K2M K1R (A1P) K1R (A2P) K2R (A1P) K3R (A1P) L1R∼L3R L4R M1C M1F M2F PS Q1DI R1∼R4 R1T R2T R3T R4T R5T R6T R7T S1NPH S1PH V1R, V2R V3R X1M Y1E Y1S Y3S Z1C∼Z9C Z1F∼Z4F Optional connector X6A X77A X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Push button switch Capacitor DIP switch Crankcase heater Bottomplate heater Fuse (T 31,5A/250V) Fuse (T 31,5A/250V) Fuse (T 6.3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (T 5,0A/250V) Fuse (T 1,0A/250V) Pilotlamp (service monitor - orange) Pilotlamp (service monitor - green) Pilotlamp (service monitor - green) Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (Y2S) Magnetic relay (E1HC) Reactor Reactor (For outdoor fan motor) Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Earth leakage protector Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Thermistor (Fin) Pressure sensor Pressure switch (High) Power module Diode module Terminal strip Electronic expansion valve Solenoid valve (4 way valve) Solenoid valve Noise filter Noise filter 3 7 Connector Connector Connector Wiring dependent on model Reactor box Arrow A El. comp. Assy (Position of elements) Arrow B 2TW58136-1 EBLQ011-016AA6W1 Only for E(D/B)LO* Option Only for EKSOLHWAV1 Option Power supply E11H-E12H-E13H / E4H Domestic hot water tank Domestic hot water tank Solar pump connection >> See note 2 << See note 9 Only for *KHWE*V3 Option Only for *KHW(S/E)* Option Only for *KHWS*Z2 Option See note 7 For *KHWSU*V3 Option User interface From compressor module switchbox (B.7 PageA) Cooling/heating on/off output See note 8 Standard 6kw (_) See note 10 230V AC heating cooling Domestic hot water tank Domestic hot water tank Only for *KHWS*V3 Option See note 7 For *KHWSU*V3 Option Only for *KHWS*Z2 Option Only for *KHW* Option Only for *KRTW Option Solar input Only for EKRP1HB & ESOLHWAV1 Option Alarm output Outdoor unit supply from PCB Only for *KRTR Option 3 wire type (SPST) Only for *KHW* Option NO valve Only for EKSOLHWAV1 Option Only for EKHW(S/E)* Option Only for EKRTETS Option Example field supply thermostat Reduced 3.5kw ( ) See note 10 Wiring dependent on model Option PCB Field wiring Field wiring Wire colour Electric heater fuse Model 6WN F1B 16A KHW kit fuse F2B 20A A11P A12P A3P (*KRTW) A4P (*KRTR) A4P (EKRTR) E11H-E12H-E13H E4H E5H E6H F1B F1T F2B F8U, F9U FU1 FU2 FuS, FuR K1M K3M K4M K5M : Main PCB : User interface PCB : Thermostat (PC=power circuit) : Solar/remote alarm PCB : Receiver PCB : Backup heater element 1-2-3 (6 kW) : Booster heater (3kW) : Switchbox heater : Expansion vessel heater : Fuse backup heater : Thermal fuse backup heater : Fuse booster heater : Fuse 1,0A F 250V : Fuse 3,15A T 250V for PCB : Fuse 5A T 250V : Fuse 5A 250V for solar/remote alarm PCB : Contactor backup heater step : Contactor booster heater : pump relay : Contactor for backup heater all-pole disconnection K7M : Relay for solar pump M1P : Pump M2S : 2 way valve for cooling mode M3S : 3 way valve: floorheating/domestic hot water PHC1 : Optocoupler input circuit Q1DI : Earth leakage protector Q1L : Thermal protector backup heater Q2L/Q3L : Thermal protector 1/2Booster heater R1H (*KRTR)) : Humidity sensor R1T (*KRTW/R) : Ambient sensor R2T (EKRTETS) : External sensor (floor or ambient) R11T : Outlet water heat-exchanger thermistor R12T : Outlet water backup heater thermistor R13T : Refrigerant liquid side thermistor R14T : Inlet water thermistor R5T (*KHW*) : Domestic hot water thermistor S1L : Flowswitch S1S : Solar pumpstation relay S2S : benefit kWh rate power supply contact SS1 : DIP switch S1T : thermostat switchbox heater S2T : thermostat expansion vessel heater TR1 : Transformer 24V for PCB V1S, V2S : Spark suppression 1, 2 X1M-X10M : Terminal strips X2Y : Connector NC valve Notes: Domestic hot water tank Domestic hot water tank Only for *KHWE*V3 Option Only for *KHWE*Z2 Option 1 2 3 4 5 6 7 8 9 10 This wiring diagram only applies to the compressor module Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option :Field wiring No/Nc normal open/normal closed SPST - single pole single throw. :Terminal strip :Connector :Terminal :Protective earth Do not operate the unit by short-circuiting any protection device. BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet For *KHWSU*V3, refer to option manual Option PCB works with an external 230V AC power supply unit. (N,L) For EKSOLHWAV1, refer to option manual Backupheater kW reduction, refer to installation manual 2TW58136-1 • AlthermaTM • Monobloc 229 • Monobloc • EBLQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EBLQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Only for EKBPHT 230V Optional parts 3 or4 core 3 core 7 Only for EKRP1HB & EKSOLHWAV1 1 core A4P: YC X3M: L1-L2-Earth or L-N-Earth 2 way valve Q*L Clixon Power supply booster heater A4P: Y1 Alarm output X7M A4P: Y2 Cooling/Heating on/off output F28 230V Only for EKHWSU*V3 X6M 5 core G5 x 2.5 X4M:1-2-Earth Alarm indication 230V NO valve: X2M: 6-7 NC valve: X2M: 5-7 X2M: 17-18 Room thermostat 230V 1 core solar interlock 2 core 230V 2 core 230V A3P 230V Note: min. distance to power cable * 5cm 2 core X9A: (PCB A1P) Possibility 2 Signal 3 core for C/H application 2 core for H only application 230V Solar pump Possibility 3 230V 5 core for C/H application 4 core for H only application X2M: 1-2-3-4 230V Only for EKSOLHWAV1 3 way valve M3S (when EKHWE is intalled) selection domestic hot water-floorheating User interface 230V Only for EKRTETS 2 core (3m included) Only for EKTR (wireless room thermostat) A4P: X1M: H-C-COM X2M: L-N R2T External sensor (floor or ambient) A3P: X1M:1-3 Signal 2 core 2 x 0.75 3 core SPST: X2M: 8-9-10 Optional parts Only for EKRTW (wired room thermostat) A3P: X1M: C-COM-H X2M: 1-2-3-4 X2M: 19-20 X8M M2S (E(B/D)(H/L)* Units) for cooling mode benefit kWh rate power supply contact Only for field supplied room thermostat X2M: 1-2-3-4 2 core Q*L Clixon 2 way valve 4 core X2M: 13-14 R5T - Thermistor water temperature Cooling/Heating on/off indication 230V Possibility 1 230V or 400V Q2L - Clixon booster heater 1 core 1 core A4P: Y3 Solar input 2 core 2x0.75 X5M 230V X1M:1-2-3-Earth X1M: L1-L2-L3-N-Earth or L-N-Earth Domestic hot water tank 2 core 3 Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth X2M: 16-160 User interface communication 3TW58016-2A 230 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EBLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-2 EBLQ011-016AA6W1 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-1 • AlthermaTM • Monobloc 231 • Monobloc • EBLQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EBLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-4 EBLQ011-016AA6W1 Octave band center frequency (Hz) E(D/B)(H/L)Q016* COOLING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* COOLING Sound pressure level (dB) E(D/B)(H/L)Q011* COOLING Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Measuring location (discharge side) 3TW58017-3 232 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 9 Installation 9-1 Service space EBLQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 • AlthermaTM • Monobloc 233 • Monobloc • EBLQ011-016AA6W1 10 Operation range 10 Outdoor temp. (°CDB) 3 Cooling mode EBLQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead. Both E(D/B)L* and E(D/B)H* models have a freeze prevention function using the pump and back up heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen we recommend to use glycol. (**) only E(D/B)L* Leaving condenser water temperature Booster heater operation only only E(D/B)L* Outdoor temp. (°CDB) Sanitary mode (**) Water temperature sanitary tank (C°) 4TW58133-1A 234 • AlthermaTM • Monobloc • Monobloc • EBLQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EBLQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC. • AlthermaTM • Monobloc 4TW58019-2 235 EEDEN09-720 technical data AlthermaTM Part 4/4: EKHWS-B EKHWE EKSOLHWAV1 EKRTW EKRTR • Domestic hot water tank • EKHWS-B TABLE OF CONTENTS EKHWS-B 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 243 Dimensional drawing 5 241 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242 Cooling capacity tables 4 241 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 • AlthermaTM • Domestic hot water tank 239 • Domestic hot water tank • EKHWS-B 1 o h c a i m Bt r - s e S e h W mtH oKl •DEA Features Stainless steel domestic hot water tank • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 4 1 240 • AlthermaTM • Domestic hot water tank • Domestic hot water tank • EKHWS-B 2 2-1 Specifications TECHNICAL SPECIFICATIONS Casing Dimensions Packing EKHWS200B 3V3 EKHWS300B 3V3 EKHWS200B 3Z2 EKHWS300B 3Z2 Colour Neutral white Material Epoxy-coated mild steel Packing Unit Weight EKHWS150B 3V3 EKHWSU150 B3V3 EKHWSU200 B3V3 EKHWSU300 B3V3 1,735 Height mm 950 1,200 1,650 1,200 1,650 1,040 1,280 Width mm 600 600 600 600 600 600 600 600 Depth mm 600 600 600 600 600 600 600 600 Height mm 900 1,150 1,600 1,150 1,600 1,015 1,265 1,715 Width mm 580 580 580 580 580 580 580 580 Depth mm 580 580 580 580 580 580 580 580 Unit kg 37 45 59 45 59 38 46 60 Packed Unit kg 42 51 66 51 66 43 52 67 Material EPS 4 2 Carton Weight Main components Tank kg 3 4 5 4 5 3 4 5 l 150 200 300 200 300 150 200 285 Max. temperat ure °C 85 85 85 85 85 85 85 85 Max. water pressure bar 10 10 10 10 10 10 10 10 mm 40 40 40 1 1 1 Water volume Material Tank Insulation Material Min. thickness Main components Heat exchanger Quantity Booster heater Quantity Polyurethane foam Material Capacity 3-Way Valve Stainless steel (DIN 1.4521) 40 40 40 40 40 1 1 1 1 1 1 Duplex steel LDX 2101 kW Coefficien m t of flow (kV) 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12 12 12 12 Inlet inch Rp1 Outlet inch 2xRp1 Temperature sensor Cable length m Piping connections Water inlet H/E Diameter inch G 3/4 (female) Water outlet H/E Diameter inch G 3/4 (female) Cold water in Diameter inch G 3/4 (female) Hot water out Diameter inch G 3/4 (female) Recirculation connection inch G 3/4 (female) 2-2 Unit ELECTRICAL SPECIFICATIONS Power Supply 12 12 12 12 EKHWS150B 3V3 EKHWS200B 3V3 EKHWS300B 3V3 EKHWS200B 3Z2 EKHWS300B 3Z2 EKHWSU150 B3V3 EKHWSU200 B3V3 EKHWSU300 B3V3 Phase 1~ 1~ 1~ 2~ 2~ 1~ 1~ 1~ Frequenc Hz y 50 50 50 50 50 50 50 50 Voltage 230 V 230 230 230 400 400 230 230 Nominal running current A 13 13 13 7.5 7.5 13 13 13 Fuse A 20 20 20 20 20 20 20 20 1~ 1~ 1~ 2~ 2~ 1~ 1~ 1~ Size Phase • AlthermaTM • Domestic hot water tank 241 • Domestic hot water tank • EKHWS-B 3 Capacity tables 3-1 Cooling capacity tables The ALTHERMA by Daikin heat pump in combination with the optional domestic hot water tank provide hot water for household usage. The below mentioned date allow a proper selection of the domestic hot water tank size for maximum comfort and efficiency. (1) Domestic hot water volume: The volume of hot water available for domestic usage depends on the physical volume of the tank, on the domestic water setpoint temperature and on the temperature spreading in the tank. Therefore we define the equivalent hot water volume (EHWV). Definition: EHWV = the volume of hot water available for domestic usage at a temperature of 40°C. 40°C is considered a comfortable domestic hot water temperature. Setpoint temp. (°C) 55 65 75 55 65 75 55 65 75 Tank 4 150L 3 200L 300L Grade ++ + - Usage pattern EHWV (l) 110 150 175 160 200 240 295 385 435 Modest + ++ + ++ ++ ++ ++ ++ Usage pattern Medium + + ++ ++ ++ ++ High + ++ Excessive availability of domestic hot water. Sufficient availability of domestic hot water. Temporary shortage of domestic hot water can occur. Modest Daily demand up tp 220 l -> typcial 2-persons usage pattern. Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern. High Daily demand up to 550 l -> 4 to 6 persons usage pattern. (2) Heat-up time: Definition: Heat-up time The time required to reheat the domestic hot water tank to 55°C after tapping a certain volume of hot water at 40°C. note: changing the field settings (see installation manual) can influence the heat-up time. Tank 150L 200L 300L Heat-up time for 150 L (bath) <min> 60 60 50 Setpoint temp. (°C) 55 55 55 Heat-up time for 50 L (shower) <min> 45 40 30 Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERHQ008 (3) Efficiency of domestic hot water production: In the ALTHERMA by Daikin system both the heat pump and the electric booster heater supply the energy to produce domestic hot water. The higher the portion of energy supplied by the heat pump, the more energy efficient the system is. Lowering the setpoint temperature increases the portion of energy supplied by the heat pump and thus the efficiency of the system. Heat pump portion Definition: Heat pump portion Percentage of energy supplied by the heat pump in the total energy need for domestic hot water. Setpoint temp. (°C) Conditions: Real life condition Outdoor temperature Room temperature Outdoor unit type Tank type Field settings Simulation of a daily usage based upon ′medium′ usage pattern. 7°CDB / 6°CWB 20°CDB ERHQ008 200l Default field settings (see installation manual). 4TW57949-1 242 • AlthermaTM • Domestic hot water tank • Domestic hot water tank • EKHWS-B 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHWS-B j 1 Water mains in G 3/4 (Female) j 2 Water mains out G 3/4 (Female) j 3 Thermistor connection j 4 Flow (from EKHB(H/X)*) G 3/4 (Female) j 5 Return (to EKHB(H/X)*) G 3/4 (Female) j 6 Switchbox j 7 Thermal protector j 8 Anode j 9 Cable entry: power, booster heater and thermal protection cable j 10 Re-circulation connection: G 3/4 (Female) j 11 Cable entry for EKSOLHWAV1: power supply from EKHB(H/X) j 12 Cable entry for EKSOLHWAV1: power supply to EKSOLHWAV1 pump j 13 Thermistor connection (See EKSOLHWAV1) j 14 3 way valve Required service space around the tank 4 4 3 way valve 3TW57944-1 EKHWSU-B Model EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 H1 900 1150 1600 H2 1015 1265 1715 H3 255 410 410 H4 130 200 200 Water connections j 1 j 2 j 3 j 4 j 5 j 6 j 7 j 8 Water IN (cold) Water OUT (hot) Flow from EKHB(H/X)* Return to EKHB(H/X)* Temperature relief valve Thermistor connection Thermistor connection (See EKSOLHWAV1) Re-circulation hole 22MM G 3/4 (Female) G 3/4 (Female) G 3/4 (Female) 15MM G 1/2 (Female) G 3/4 (Combinations compliant to NF-PAC) Water connections kit j 9 j 10 j 11 j 12 j 13 j 14 j 15 j 16 j 17 Pressure reducing valve Expansion relief valve T-piece (to tundish) Tundish T-piece (to expansion vessel) Adapter (expansion vessel) Expansion vessel Drain valve Solenoid valve 22MM-22MM 22MM-22MM 15MM-15MM-G 1/2 (Female) 22MM-15MM 22MM-22MM-22MM 22MM-G 3/4 (Female) G 3/4 (Male) 22MM-G 2/4 (Female) 3/4’’ female BSP-3/4’’ hale BSP Other j 18 EKUHW2WB kit: solenoid valve (only with EKSOLHWAV1) Rp 3/4 - Rp 3/4 j 19 Switchbox j 20 Thermal protector 1+Thermostat j 21 Cable entry: power supply booster heater and thermal protector cable j 22 Cable entry for EKUHW2WB: power supply to solenoid valve j 23 Cable entry: power supply booster heater and thermal protector cable j 24 Blind stop + 2 plastic screw-on closing caps for pressure reducing valve j 25 Thermal protector 2+Thermostat j 26 Cable entry for EKSOLHWAV1: power supply to EKSOLHWAV1 pump j 27 3 way valve 3x Rp1 Typical installation EKUHWA-kit Required service space 3TW57944-2A • AlthermaTM • Domestic hot water tank 243 • Domestic hot water tank • EKHWS-B 5 Piping diagram EKHWSU-B Overview Field installation (delivered with indoor unit) Field installation (Delivered with EKHWSU*B*) 3-way motorized valve Shut off valve Outdoor Load Indoor Shut off valve Water return Water flow Option domestic hot water tank 4 Water flow Water return 5 Option domestic hot water tank Water main OUT Water main IN Pressure reducing valve with integrated non return valve line strainer Expansion relief valve T-piece 2-way solenoid valve (*): Field installation delivered with EKUHWB kit (**): Field installation delivered with EKUHW2WB Tundish Expansion vessel RST Y1S M3S T-piece Drain valve Domestic hot water thermistor Solenoid valve 3-way motorized valve 3TW57945-1 Check valve 244 Flare connection Screw connection Flange connection Pinched pipe Spinned pipe • AlthermaTM • Domestic hot water tank • Domestic hot water tank • EKHWE TABLE OF CONTENTS EKHWE 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 249 Dimensional drawing 5 247 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248 Cooling capacity tables 4 247 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 • AlthermaTM • Domestic hot water tank 245 • Domestic hot water tank • EKHWE 1 o h c a i m t r s e E e h W mtH oKl •DEA Features Enameled domestic hot water tank • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 4 1 246 • AlthermaTM • Domestic hot water tank • Domestic hot water tank • EKHWE 2 2-1 Specifications TECHNICAL SPECIFICATIONS Mounting Casing EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 EKHWET150A3V3 Floor Floor Floor Floor Floor Wall Colour RAL9010 Material Dimensions Packing Unit Epoxy coated steel Height mm 1,460 1,835 1,830 1,835 1,830 1,460 Width mm 615 615 720 615 720 615 Depth mm 625 625 730 625 730 625 Height mm 1,205 1,580 1,572 1,580 1,572 1,205 545 Diameter Weight Packing mm 545 545 660 545 660 Unit kg 80 104 140 104 140 82 Packed Unit kg 92 117 158 117 158 94 Material Carton 4 2 Wood EPS Weight Main components Tank kg 13 13 18 13 18 12 l 150 200 300 200 300 150 Max. temperat ure °C 75 75 75 75 75 75 Max. water pressure bar 10 10 10 10 10 10 mm 47.5 47.5 1 1 Water volume Material Tank Insulation Material Min. thickness Main components Heat exchanger Material 50 47.5 50 47.5 1 1 1 1 Enamel coated steel acc. DIN4753TL2 m² Quantity Capacity 3-Way Valve HFC-free Polyurethane foam Quantity Surface Booster heater Enamel coated steel acc. DIN4753TL2 kW Coefficient m of flow (kV) 0.5 0.8 1.06 0.8 1.06 0.5 1.0 1.0 1.0 1.0 1.0 1.0 3.0 3.0 3.0 3.0 3.0 3.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 Inlet inch RP 1" Outlet inch 2 x RP 1" Temperature sensor Cable length m Piping connections Water inlet H/E Diameter inch Rp 3/4" Water outlet H/E Diameter inch Rp 3/4" Cold water in Diameter inch G 3/4" Hot water out Diameter inch G 3/4" Recirculation connection inch G3/4" 2-2 Unit ELECTRICAL SPECIFICATIONS Power Supply 12.0 12.0 12.0 EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 EKHWET150A3V3 1~ Phase 1~ 1~ 1~ 2~ 2~ Frequency Hz 50 50 50 50 50 50 Voltage 230 230 230 400 400 230 V Nominal running current A 13 13 13 7.5 7.5 13 Fuse A 20 20 20 20 20 20 2 2 2 2 2 2 Size Pole • AlthermaTM • Domestic hot water tank 247 • Domestic hot water tank • EKHWE 3 Capacity tables 3-1 Cooling capacity tables The ALTHERMA by Daikin heat pump in combination with the optional domestic hot water tank provide hot water for household usage. The below mentioned date allow a proper selection of the domestic hot water tank size for maximum comfort and efficiency. (1) Domestic hot water volume: The volume of hot water available for domestic usage depends on the physical volume of the tank, on the domestic water setpoint temperature and on the temperature spreading in the tank. Therefore we define the equivalent hot water volume (EHWV). Definition: EHWV = the volume of hot water available for domestic usage at a temperature of 40°C. 40°C is considered a comfortable domestic hot water temperature. Setpoint temp. (°C) 55 65 75 55 65 75 55 65 75 Tank 4 150L 3 200L 300L Grade ++ + - Usage pattern EHWV (l) 125 165 185 200 230 260 320 400 435 Modest + ++ + ++ ++ ++ ++ ++ Usage pattern Medium + + ++ ++ ++ ++ High + ++ Excessive availability of domestic hot water. Sufficient availability of domestic hot water. Temporary shortage of domestic hot water can occur. Modest Daily demand up tp 220 l -> typcial 2-persons usage pattern. Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern. High Daily demand up to 550 l -> 4 to 6 persons usage pattern. (2) Heat-up time: Definition: Heat-up time The time required to reheat the domestic hot water tank to 55°C after tapping a certain volume of hot water at 40°C. note: changing the field settings (see installation manual) can influence the heat-up time. Tank 150L 200L 300L Heat-up time for 150 L (bath) <min> 60 60 50 Setpoint temp. (°C) 55 55 55 Heat-up time for 50 L (shower) <min> 45 40 30 Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERHQ011 (3) Efficiency of domestic hot water production: In the ALTHERMA by Daikin system both the heat pump and the electric booster heater supply the energy to produce domestic hot water. The higher the portion of energy supplied by the heat pump, the more energy efficient the system is. Lowering the setpoint temperature increases the portion of energy supplied by the heat pump and thus the efficiency of the system. Heat pump portion Definition: Heat pump portion Percentage of energy supplied by the heat pump in the total energy need for domestic hot water. Setpoint temp. (°C) Conditions: Real life condition Outdoor temperature Room temperature Outdoor unit type Tank type Field settings Simulation of a daily usage based upon ′medium′ usage pattern. 7°CDB / 6°CWB 20°CDB ERHQ011 200l Default field settings (see installation manual). (4) Heat losses of domestic hot water tank: Tank Heat losses* EKHWE [kWh/24h] 150L 1.7 200L 1.9 300L 2,5 * Heat losses at _45°C between hot water in tank and surrounding air. 4TW57859-1 248 • AlthermaTM • Domestic hot water tank • Domestic hot water tank • EKHWE 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHWE Required service space around the tank Wall mounted j 1 Cold water inlet: G 3/4 (Male) j 2 Hot water outlet: G 3/4 (Male) j 3 Thermistor hole j 4 Flow (From EKHB(H/X)*): Rp 3/4 (Female) j 5 Return (To EKHB(H/X)*): Rp 3/4 (Female) j 6 Switchbox j 7 Thermal protector j 8 Anode j 9 Cable entry j 10 Re-circulation connection: G 3/4 (Male) j 11 Thermistor hole (See EKSOLHWAV1) j 12 Wall plate 150L Wall-mounted tank j 13 Safety valve connection: G 1/2 (Male) j 14 3 way valve: 3x Rp 1 (Female) 4 4 Wall plate 150L Wall-mounted tank Inside of switchbox 3 way valve Scale 1:5 3TW57854-1A • AlthermaTM • Domestic hot water tank 249 • Domestic hot water tank • EKHWE 5 Wiring diagram 5-1 Wiring diagram EKHWE *KHBH/X* Switchbox *KHBH/X* Switchbox *KHWE**0A3V3 Water tank Switchbox *KHWE**00A3Z2 Water tank Switchbox Setpoint Q2L & Q3L: 89°C Setpoint Q2L: 89°C 4 5 E4H F2B K3M L N Q2L Q3L X2M∼X4M X9M∼X10M : Booster heater : Fuse booster heater : Contactor booster heater : Line : Neutral : Thermal protector Booster heater : Thermal protector 2 Hot water tank : Terminal block : Terminal block Solar pump Solar pump EKSOLHWAV1 (Option) EKSOLHWAV1 (Option) Notes: 1 2 3 : Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet Please refer to the *KHWE* manual for more installation details 3TW57856-1A 250 • AlthermaTM • Domestic hot water tank • Solar Kit • EKSOLHWAV1 TABLE OF CONTENTS EKSOLHWAV1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 253 253 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 254 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254 4 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256 5 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257 Wiring diagram • AlthermaTM • Solar Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257 251 • Solar Kit • EKSOLHWAV1 1 t 1 i V aKA m W r H r e L a hO l tS oKl E•SA Features Connectable to solar collectors • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 4 1 252 • AlthermaTM • Solar Kit • Solar Kit • EKSOLHWAV1 2 2-1 Specifications TECHNICAL SPECIFICATIONS Dimensions Packing Unit Weight Packing Height mm Width mm 340 Depth mm 295 Pump 795 Height mm 770 Width mm 305 Depth mm 270 Unit kg 8 Packed Unit kg 9 Material Carton Weight Heat Exchanger EKSOLHWAV1 kg Type 1 4 Brazed plate 2 Pressure drop Solar side kPa 21.5 Maximum inlet temperature Solar side °C 110 Capacity W/K Logarithmic mean temperature difference (LMTD) K Type 1,400 5 water cooled Number of speeds 3 Power input W Sound Sound Pressure dBA 27 Water circuit Piping connections diameter inch 3/4" FBSP Insulation material Ambient temperature 2-2 EPP Maximum °C 35 Minimum °C 1 ELECTRICAL SPECIFICATIONS Unit Power Supply Phase Voltage EKSOLHWAV1 1~ Frequency Hz Voltage range 46 V 50 220-240 Minimum -10% Maximum +10% Power Supply Intake indoor unit • AlthermaTM • Solar Kit 253 • Solar Kit • EKSOLHWAV1 3 Dimensional drawing & centre of gravity 3-1 Dimensional drawing EKSOLHWAV1+EKHWS EKSOLHWAV1 + EKHWS200-300* EKSOLHWAV1 + EKHWS150* 4 Detail 1 Detail 1 3 Switchbox domestic hot water tank j 11 Cable entry (Altherma indoor unit) j 12 Cable entry (Pump cable) Components j 1 j 2 j 3 j 4 Pump + switch for speed setting Heat exchanger EPP casing Non return valves Accessories (delivered with EKSOLHWAV1) Connection type j 13 Thermistor sockel (thermistor solar pump station) (internal diameter 6.1mm) j 14 Adapter 3/4″M BSP-3/4″M BSP j 15 Adapter 3/4″F BSP-3/4″M BSP j 16 Adapter 3/4″M BSP-3/4″M BSP CONNECTIONS j 5 Inlet connection from solar pump station j 6 Return connection to solar pump station j 7 Inlet connection from Altherma indoor unit j 8 Return connection to Altherma indoor uint j 9 EKSOLHWAV1 return connection to the domestic hot water tank heatexchanger j j 9a 200-300l Tank 9b 150l Tank j 10 EKSOLHWAV1 inlet connection from the domestic hot water tank heatexchanger 254 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP • AlthermaTM • Solar Kit Minimum space for service & ventilation Detail 1 Scale: 1/4 Service space Scale: 1/20 3TW57844-1 • Solar Kit • EKSOLHWAV1 3 Dimensional drawing & centre of gravity 3-1 Dimensional drawing EKSOLHWAV1+EKHWSU EKSOLHWAV1 + EKHWS200-300* EKSOLHWAV1 + EKHWS150* Detail 2 Scale: 1/4 Detail 2 4 Detail 1 3 Switchbox domestic hot water tank j 11 Cable entry (Altherma indoor unit) j 12 Cable entry (Pump cable) Components j 1 j 2 j 3 j 4 Pump + switch for speed setting Heat exchanger EPP casing Non return valves Accessories (delivered with EKSOLHWAV1) Connection type j 13 Thermistor sockel (thermistor solar pump station) (internal diameter 6.1mm) j 14 Adapter 3/4″M BSP-3/4″M BSP j 15 Adapter (Field supply) 3/4″F BSP-3/4″M BSP Minimum space for service & ventilation Model EKHWSU150* EKHWSU200* EKHWSU300* H1 430 400 400 Service space CONNECTIONS j 5 Inlet connection from solar pump station j 6 Return connection to solar pump station j 7 Inlet connection from Altherma indoor unit j 8 Return connection to Altherma indoor uint j 9 EKSOLHWAV1 return connection to the domestic hot water tank heatexchanger j j 9a 200-300l Tank 9b 150l Tank j 10 EKSOLHWAV1 inlet connection from the domestic hot water tank heatexchanger 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP EKUHWA Kit j 16 Solenoid valve 3/4″F BSP-3/4″F BSP j 17 Adapter 3/4″M BSP-3/4″M BSP Solenoid valve 3/4″F BSP • AlthermaTM • Solar Kit Scale: 1/20 3TW57844-2 255 • Solar Kit • EKSOLHWAV1 4 Piping diagram EKSOLHWAV1 Overview Indoor 3-way motorized valve Load Shut off valve Shut off valve Water from indoor Field supply Solar collector Option domestic hot water tank Field supply Solar pump station 4 Solenoid valve 3-way motorized valve Field supply Field installation (delivered with indoor unit) Outdoor Y1S M3S Water to tank Medium from solar collector Option solar kit Medium to solar collector Water from tank 4 * Delivered with EKUHWA kit Water to indoor Detail 1 Only for EKHWSU* Water from indoor Water to tank Detail 1 2-way solenoid valve * Medium from solar collector For EKHW(S/E)* Plate heat exchanger Medium to solar collector Non return valve Pump Water to indoor Water from tank Non return valve Check valve 256 Flare connection Screw connection Flange connection 3TW57845-1 Pinched pipe • AlthermaTM • Solar Kit Spinned pipe • Solar Kit • EKSOLHWAV1 5 Wiring diagram 5-1 Wiring diagram EKSOLHWAV1 with EKHWS*V3 EKHWS*V3 Switchbox EKHB/X* Switchbox Solar pump 4 5 EKHB/X* Switchbox E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S : Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block : Solenoid valve Notes: 1 2 3 : Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual. 3TW57846-1 EKSOLHWAV1 with EKHWS*Z2 EKHWS*Z2 Switchbox EKHB/X* Switchbox Solar pump EKHB/X* Switchbox E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S : Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block : Solenoid valve Notes: 1 2 3 : Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual. 3TW57846-1 • AlthermaTM • Solar Kit 257 • Solar Kit • EKSOLHWAV1 5 Wiring diagram 5-1 Wiring diagram EKSOLHWAV1 with EKHWSU EKHWS*V3 Switchbox EKUHWA EKHB/X* Switchbox 4 Notes: 1 5 2 3 : Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual. EKSOLHWAV1 EKHB/X* Switchbox E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S : Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block : Solenoid valve 3TW57846-1 258 • AlthermaTM • Solar Kit • Room thermostat • • EKRTW TABLE OF CONTENTS EKRTW 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 261 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 263 Dimensional drawing • AlthermaTM • Room thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263 259 • Room thermostat • EKRTW 1 Features s o m r e a h m t r e W mh T otR oKl EAR 4 1 260 • AlthermaTM • Room thermostat • Room thermostat • EKRTW 2 2-1 Specifications TECHNICAL SPECIFICATIONS Dimensions Unit Packing Weight Unit Packing EKRTW Height mm 87 Width mm 125 34 Depth mm Height mm 65 Width mm 175 Depth mm 100 Net g 215 Gross g 440 Material Carton Weight g 55 4 Ambient temperature Storage °C -20~60 Operation °C 0~50 2 Temperature setting range Heating °C 4-37 Cooling °C 4-37 Temperature setting resolution °C Clock 0.5 Yes Regulation function Features Proportional band Item Heating only Heating and cooling Comfort function mode (= comfort setpoint) Reduced function mode (=night setback setpoint) Scheduled function mode(= schedule timer) Number of setpoint changes Note 12/day Item Holiday function mode Off function (with integrated frost protection) Setpoint limitation Keylock function 2-2 ELECTRICAL SPECIFICATIONS Power Supply Voltage Connection Maximum rated switching current (at 230VAC) EKRTW battery powered 3* AA-LR6 (alkaline) Wired A • AlthermaTM • Room thermostat 0.1 261 • Room thermostat • EKRTW 3 Options Additional information: comfort function mode reduced function mode scheduled function mode holiday function mode off function setpoint limitation floor temperature protection Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode) Use this mode for a fixed temperature on reduced level. (reduced setpoint default on 17°C in heating mode, 28°C in cooling mode) Use this mode to let your installation be controlled by the schedule timer. The actions programmed in the schedule timer will be executed automatically according to the actual time. This function uses the scheduled temperature setpoint. Use this mode to set a fixed temperature during a long absence. Use this mode to switch of your installation. Integrated frost protection remains activated. (frost protection default on 4°C in heating mode) Use this function to limit the setpoint range for the end customer. Use this function to set a maximum and a minimum floor temperature. 4TW57991-2 4 3 262 • AlthermaTM • Room thermostat • Room thermostat • EKRTW 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKRTW 4 4 EKRTR 4TW57994-1 • AlthermaTM • Room thermostat 263 • Room thermostat • EKRTR TABLE OF CONTENTS EKRTR 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267 267 3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 269 Dimensional drawing • AlthermaTM • Room thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269 265 • Room thermostat • EKRTR 1 Features s o m r e a h m t r e R mh T otR oKl EAR 4 1 266 • AlthermaTM • Room thermostat • Room thermostat • EKRTR 2 2-1 Specifications TECHNICAL SPECIFICATIONS Dimensions Unit Packing Weight Unit Packing EKRTR thermostat Height mm 87 Width mm 125 34 Depth mm Height mm 70 Width mm 200 Depth mm 140 Net g 210 Gross g 665 Material Carton Weight g 85 4 Ambient temperature Storage °C -20~60 Operation °C 0~50 2 Temperature setting range Heating °C 4-37 Cooling °C 4-37 Temperature setting resolution °C Clock 0.5 Yes Regulation function Features Proportional band Item Heating only Heating and cooling Comfort function mode (= comfort setpoint) Reduced function mode (=night setback setpoint) Scheduled function mode(= schedule timer) Number of setpoint changes Note 12/day Item Holiday function mode Off function (with integrated frost protection) Setpoint limitation Keylock function Floor temperature protection Note 2-2 Only in combination with EKRTETS ELECTRICAL SPECIFICATIONS Power Supply Voltage Connection Maximum distance to receiver EKRTR thermostat battery powered 3* AA-LR6 (alkaline) Wireless Indoor m approx. 30m Outdoor m approx. 100m • AlthermaTM • Room thermostat 267 • Room thermostat • EKRTR 3 Options Additional information: comfort function mode reduced function mode scheduled function mode holiday function mode off function setpoint limitation floor temperature protection Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode) Use this mode for a fixed temperature on reduced level. (reduced setpoint default on 17°C in heating mode, 28°C in cooling mode) Use this mode to let your installation be controlled by the schedule timer. The actions programmed in the schedule timer will be executed automatically according to the actual time. This function uses the scheduled temperature setpoint. Use this mode to set a fixed temperature during a long absence. Use this mode to switch of your installation. Integrated frost protection remains activated. (frost protection default on 4°C in heating mode) Use this function to limit the setpoint range for the end customer. Use this function to set a maximum and a minimum floor temperature. 4TW57991-2 4 3 268 • AlthermaTM • Room thermostat • Room thermostat • EKRTR 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKRTW 4 4 EKRTR 4TW57994-1 • AlthermaTM • Room thermostat 269