Download Daikin EBHQ011AA6W1 Technical data

Transcript
EEDEN09-720
technical data
AlthermaTM
AlthermaTM
Daikin’s unique position as a
manufacturer of air conditioning
equipment, compressors and
refrige-rants has led to its close
involvement in environmental
issues. For several years Daikin has
had the intention to become a
leader in the provision of products
that have limited impact on the
environment. This challenge
demands the eco design and
development of a wide range of
products and an energy
management system, resulting in
energy conservation and a
reduction of waste.
ISO14001 assures an effective environmental
management system in order to help protect
human health and the environment from
potential impact of our activities, products and
services and to assist in maintaining and
improving the quality of the environment.
Daikin Europe N.V. is approved by LRQA for its
Quality Management System in accordance
with the ISO9001 standard. ISO9001 pertains
to quality assurance regarding design,
development, manufacturing as well as to
services related to the product.
“The present publication is drawn up by way of information only and
does not constitute an offer binding upon Daikin Europe N.V.. Daikin
Europe N.V. has compiled the content of this publication to the best
of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of
its content and the products and services presented therein.
Specifications are subject to change without prior notice. Daikin
Europe N.V. explicitly rejects any liability for any direct or indirect
damage, In the broadest sense, arising from or related to the use
and/or interpretation of this publication. All content is copyrighted by
Daikin Europe N.V..”
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Ostend, Belgium
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende
EEDEN0 9 - 7 2 0
EEDEN09-720 - 03/2009
Printed in Belgium by Goekint Graphics
Copyright © Daikin
Daikin units comply with the European
regulations that guarantee the safety of the
product.
EEDEN09-720
technical data
AlthermaTM
• AlthermaTM
rA e0 h1 t4 l- RA
Heating only
Heat pump
4
• AlthermaTM
• AlthermaTM
AlthermaTM Small Capacity
Indoor - Outdoor
Heating only Heating and Cooling
PAGE
1
2
Oudoor unit - 1~
1
ERHQ006-008AD
9
Indoor unit - 1~
1
EKHBH(X)008AA
21
3
AlthermaTM Large Capacity
Indoor - Outdoor
Heating only Heating and Cooling
Oudoor unit - 1~
2
ERHQ011-016AA
35
Oudoor unit - 3~
2
ERHQ011-016AAW1
53
Indoor unit - 1~
2
EKHBH(X)016AB
69
5
Without bottom plate heater - 1~
3
EDHQ011-016AA6V3
83
6
Without bottom plate heater - 3~
3
EDHQ011-016AA6W1
103
Bottom plate heater - 1~
3
EDLQ011-016AA6V3
121
Bottom plate heater - 3~
3
EDLQ011-016AA6W1
139
Without bottom plate heater - 1~
3
EBHQ011-016AA6V3
157
Without bottom plate heater - 3~
3
EBHQ011-016AA6W1
177
Bottom plate heater - 1~
3
EBLQ011-016AA6V3
197
Bottom plate heater - 3~
3
EBLQ011-016AA6W1
217
4
AlthermaTM Monobloc
Heating only
Heating and Cooling
7
8
9
10
11
AlthermaTM Optional comfort
Stainless steel domestic
hot water tank
4
EKHWS-B
237
Enameled domestic
hot water tank
4
EKHWE
245
Solar kit
4
EKSOLHWAV1
251
Wired room thermostat
4
EKRTW
259
Wireless room thermostat
4
EKRTR
265
12
13
14
15
16
• AlthermaTM
5
EEDEN09-720
technical data
AlthermaTM
Part 1/4:
ERHQ006-008AD
EKHBH/X008AA
• Outdoor units • ERHQ006-008AD
TABLE OF CONTENTS
ERHQ006-008AD
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
3
Cooling/Heating capacity tables
4
11
13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
16
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• AlthermaTM • Outdoor units
19
9
• Outdoor units • ERHQ006-008AD
1
D iA n8 0u 0 a - r m 6 o r 0 o e 0 dh Q t H uRl EA•O
1
Features
Small capacity outdoor unit
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
1
10
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ006-008AD
2
Specifications
2-1 NOMINAL CAPACITY AND
NOMINAL INPUT
For
combination
indoor units +
outdoor units
Indoor Units
Condition 1
Heating
capacity
Nominal
Capacity
ERHQ007AD
ERHQ008AD
EKHBH008AA
kW
4.36
4.36
Nominal
kW
5.75
6.84
8.43
Maximum kW
7.45
8.79
9.58
Heating PI
Nominal
1.26
1.58
2.08
COP
Nominal
4.56
4.34
4.05
Heating
capacity
Minimum
kW
3.87
3.87
3.87
Nominal
kW
4.36
kW
5.03
6.10
7.64
Maximum kW
6.68
7.98
8.76
Heating PI
Nominal
1.58
1.95
2.54
COP
Nominal
3.18
3.13
3.00
Indoor Units
Condition 1
Heating
capacity
kW
EKHBX008AA
Minimum
kW
4.36
4.36
Nominal
kW
5.75
6.84
8.43
Maximum kW
7.45
8.79
9.58
Minimum
kW
4.82
4.82
4.82
Nominal
kW
7.20
8.16
8.37
Maximum kW
7.20
8.50
8.91
Heating PI
Nominal
kW
1.26
1.58
2.08
Cooling PI
Nominal
kW
2.27
2.78
2.97
COP
Nominal
4.56
4.34
4.05
Cooling
capacity
EER
Nominal
Heating
capacity
Minimum
kW
Nominal
4.36
3.17
2.94
2.82
3.87
3.87
3.87
kW
5.03
6.10
7.64
Maximum kW
6.68
7.98
8.76
Minimum
kW
3.67
3.67
3.67
Nominal
kW
5.12
5.86
6.08
Maximum kW
5.12
6.13
7.10
Heating PI
Nominal
kW
1.58
1.95
2.54
Cooling PI
Nominal
kW
2.16
2.59
2.75
COP
Nominal
3.18
3.13
3.00
EER
Nominal
2.37
2.26
2.21
Cooling
capacity
1
2
Minimum
For
combination
indoor units +
outdoor units
Nominal
Capacity
ERHQ006AD
Notes
Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C) - heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
2-2
TECHNICAL SPECIFICATIONS
Casing
ERHQ006AD
Colour
Unit
Packing
Weight
Packing
ERHQ008AD
Ivory white
Material
Dimensions
ERHQ007AD
Polyester painted galvanised steel
Height
mm
735
735
735
Width
mm
825
825
825
Depth
mm
300
300
300
Height
mm
797
797
797
Width
mm
960
960
960
Depth
mm
390
390
390
Unit
kg
56
56
56
Packed Unit
kg
61
61
61
Material
EPS
Carton
Weight
kg
5
• AlthermaTM • Outdoor units
5
5
11
• Outdoor units • ERHQ006-008AD
2
2-2
1
Specifications
TECHNICAL SPECIFICATIONS
Heat
Exchanger
Dimensions
Length
mm
Nr of Rows
2
Fin Pitch
mm
Nr of Stages
ERHQ006AD
ERHQ007AD
ERHQ008AD
845
845
845
2
2
2
1.8
1.8
1.8
32
32
32
Tube type
Fin
Hi-Xa(8)
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
1
Discharge direction
Motor
Quantity
Output
Compressor
W
Quantity
Motor
Heating
Cooling
Sanitary water
Sound Level
(nominal)
Heating
Cooling
Refrigerant
1
1
1
53
53
1
1
1
Model
2YC63BXD#C
Hermetically sealed swing compressor
Motor
Output
W
1,920
Min
°CWB
-20
-20
-20
Max
°CWB
25
25
25
Min
°CDB
10
10
10
Max
°CDB
43
43
43
-20
Min
°CDB
-20
-20
Max
°CDB
43
43
43
Sound
Power
dBA
61
61
62
Sound
Pressure
dBA
48
48
49
Sound
Power
dBA
63
63
63
Sound
Pressure
dBA
48
48
50
kg
1.7
Type
R-410A
Charge
Control
1
Type
Liquid (OD)
l
mm
Type
0.75
0.75
Flare connection
mm
Quantity
15,9
1
1
1
Socket
Diameter
(OD)
mm
Minimum
m
3
3
3
Maximum m
30
30
30
Additional Refrigerant
Charge
kg/m
Max. internunit level
difference
m
18
18
18
0.02>10m
20
20
Defrost Method
Reverse cycle
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
12
1
6,35
Type
Piping Length
1
Flare connection
Diameter
(OD)
Drain
0.75
Type
Diameter
(OD)
Gas
1.7
FVC50K
Charged Volume
Piping
connections
1.7
Expansion valve(electronic type)
Nr of Circuits
Refrigerant Oil
1
53
Type
Operation
Range
1
Horizontal
Inverter controlled
• AlthermaTM • Outdoor units
20
• Outdoor units • ERHQ006-008AD
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Standard
Accessories
ERHQ006AD
Item
ERHQ007AD
ERHQ008AD
Installation manual
Quantity
1
Item
1
1
2
Drain plug
Quantity
1
Notes
1
1
1
See operation range drawing
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value
depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
2-3
ELECTRICAL SPECIFICATIONS
Power Supply
ERHQ006AD
Name
1~
Frequency
Hz
50
50
50
Voltage
V
230
230
230
Voltage range
Minimum
V
-10%
Maximum V
+10%
Starting current Heating
A
11
11
Cooling
A
11
11
11
Heating
A
18
18
18
Cooling
A
16.25
16.25
16.25
A
Maximum
running
Current
Recomended fuses
Wiring
connections
ERHQ008AD
V3
Phase
Current
ERHQ007AD
11
20
20
20
Quantity
3
3
3
For connection Quantity
with indoor
Remark
4
4
4
For Power
Supply
• AlthermaTM • Outdoor units
Included earth wiring
13
• Outdoor units • ERHQ006-008AD
3
Capacity tables
3-1
Cooling/Heating capacity tables
COOLING
1
Model
3
006
007
008
Tamb (°C)
LWE (°C)
7
11
13
16
20
7
11
13
16
20
7
11
13
16
20
20
CC
6.01
6.81
7.23
7.88
8.80
7.15
8.09
8.57
9.33
10.4
8.24
9.26
9.79
10.6
11.7
25
PI
1.56
1.57
1.57
1.56
1.55
2.05
2.09
2.11
2.13
2.16
2.43
2.49
2.52
2.57
2.63
CC
5.73
6.50
6.90
7.54
8.42
6.84
7.73
8.20
8.92
9.9
7.90
8.87
9.38
10.17
11.3
30
PI
1.75
1.77
1.78
1.78
1.79
2.28
2.34
2.36
2.40
2.44
2.68
2.76
2.80
2.86
2.94
CC
5.43
6.17
6.56
7.17
8.03
6.50
7.34
7.79
8.49
9.48
7.52
8.45
8.93
9.69
10.75
35
PI
1.95
1.98
2.00
2.01
2.03
2.52
2.59
2.63
2.68
2.73
2.94
3.05
3.10
3.17
3.26
CC
5.12
5.83
6.20
6.79
7.63
6.13
6.94
7.36
8.03
8.99
7.10
7.79
8.14
8.68
9.39
40
PI
2.16
2.21
2.23
2.26
2.29
2.77
2.87
2.91
2.97
3.04
3.23
3.31
3.36
3.41
3.48
CC
4.80
5.30
5.56
5.95
6.48
5.35
5.84
6.09
6.46
6.96
5.68
6.12
6.34
6.67
7.09
43
PI
2.39
2.32
2.28
2.22
2.13
2.68
2.62
2.59
2.53
2.44
2.86
2.80
2.77
2.71
2.61
CC
4.59
4.98
5.18
5.46
5.82
4.89
5.21
5.36
5.57
5.82
4.87
5.18
5.33
5.55
5.80
PI
2.53
2.38
2.30
2.18
1.99
2.59
2.43
2.34
2.20
1.99
2.59
2.43
2.35
2.20
1.99
HEATING (Peak values)
Model
006
007
008
LWC
Tamb
-15
-10
-7
-2
2
7
-15
-10
-7
-2
2
7
-15
-10
-7
-2
2
7
30
HC
3.93
4.65
5.14
6.06
6.89
8.03
4.87
5.67
6.21
7.23
8.14
9.40
5.42
6.27
6.84
7.92
8.9
10.2
35
PI
1.48
1.52
1.54
1.57
1.57
1.57
1.82
1.88
1.91
1.95
1.97
1.98
2.06
2.13
2.17
2.22
2.26
2.28
HC
3.67
4.32
4.77
5.62
6.38
7.45
4.62
5.34
5.83
6.77
7.61
8.79
5.16
5.93
6.46
7.45
8.35
9.58
40
PI
1.59
1.65
1.68
1.72
1.74
1.75
1.94
2.02
2.07
2.13
2.16
2.19
2.19
2.29
2.34
2.41
2.46
2.51
HC
3.47
4.07
4.49
5.28
6.00
7.00
4.43
5.09
5.55
6.42
7.21
8.32
4.97
5.68
6.17
7.10
7.93
9.10
45
PI
1.71
1.79
1.83
1.88
1.91
1.94
2.08
2.18
2.24
2.32
2.37
2.42
2.34
2.46
2.53
2.62
2.69
2.76
HC
3.33
3.89
4.28
5.03
5.72
6.68
4.30
4.92
5.35
6.17
6.92
7.98
4.86
5.51
5.97
6.85
7.65
8.76
50
PI
1.84
1.94
1.99
2.06
2.11
2.15
2.23
2.36
2.42
2.52
2.59
2.66
2.51
2.65
2.73
2.85
2.93
3.02
HC
3.25
3.78
4.15
4.87
5.53
6.47
4.24
4.82
5.23
6.02
6.74
7.78
4.80
5.42
5.86
6.70
7.47
8.56
PI
1.99
2.10
2.16
2.25
2.31
2.37
2.40
2.55
2.63
2.75
2.83
2.92
2.70
2.86
2.95
3.10
3.20
3.31
HEATING (integrated values*)
Model
006
007
008
LWC
Tamb
-15
-10
-7
-2
2
7
-15
-10
-7
-2
2
7
-15
-10
-7
-2
2
7
30
HC
3.50
4.14
4.52
5.27
5.92
8.03
4.34
5.04
5.46
6.29
7.00
9.40
4.82
5.58
6.02
6.89
7.6
10.2
35
PI
1.40
1.45
1.45
1.46
1.45
1.57
1.73
1.79
1.80
1.81
1.81
1.98
1.96
2.03
2.04
2.07
2.08
2.28
HC
3.27
3.85
4.20
4.89
5.49
7.45
4.11
4.75
5.13
5.89
6.55
8.79
4.59
5.28
5.69
6.48
7.18
9.58
40
PI
1.51
1.56
1.58
1.60
1.60
1.75
1.85
1.92
1.94
1.98
1.99
2.19
2.08
2.17
2.20
2.25
2.27
2.51
HC
3.09
3.62
3.95
4.59
5.16
7.00
3.94
4.53
4.88
5.59
6.20
8.32
4.43
5.06
5.43
6.17
6.82
9.10
45
PI
1.62
1.70
1.72
1.75
1.76
1.94
1.98
2.07
2.10
2.15
2.18
2.42
2.23
2.34
2.37
2.44
2.47
2.76
HC
2.97
3.46
3.77
4.38
4.92
6.68
3.83
4.38
4.71
5.37
5.96
7.98
4.32
4.91
5.26
5.96
6.58
8.76
HC
PI
LWE
LWC
Tamb
14
PI
1.75
1.84
1.87
1.92
1.94
2.15
2.12
2.24
2.28
2.35
2.38
2.66
2.39
2.52
2.57
2.65
2.70
3.02
HC
2.89
3.36
3.65
4.24
4.76
6.47
3.77
4.29
4.60
5.23
5.80
7.78
4.27
4.82
5.15
5.83
6.43
8.56
PI
1.89
2.00
2.03
2.10
2.13
2.37
2.28
2.42
2.47
2.56
2.61
2.92
2.56
2.72
2.78
2.88
2.94
3.31
* The integrated heating capacity and power
input, is the average heating capacity and
power input during 1 cycle. (from end of
defrost till end of the next defrost).
3TW57782-1A
NOTES
SYMBOLS
CC
50
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Outdoor units
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 60 W (according EN14511).
For the optional model with heatertape (V38) when ambient temperature
becomes lower than 4°C: add power input of 60W
• Outdoor units • ERHQ006-008AD
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
unit (mm)
ERHQ006-008 AD
Drain outlet
(I.D. J 15.9 hose for connection)
4
Wall height on air outlet side
= less than 1200
Minimum space for air passage
1
In case of removing stop valve cover
4 x holes for anchor bolts (M8 or M10)
Name plate
Brand name label
Wiring inlet
Terminal strip with
earth terminal
Outdoor air temperature
thermistor
Liquid stop valve
(J6.4 CuT)
Service port
• AlthermaTM • Outdoor units
Gas stop valve
(J15.9 CuT)
3D060289
15
• Outdoor units • ERHQ006-008AD
1
4
Dimensional drawing & centre of gravity
4-2
Centre of gravity
ERHQ006-008 AD
4
The position of foundation bolt
4D042258L
16
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ006-008AD
5
Piping diagram
ERHQ006-008AD
1
Outdoor unit
Heat exchanger
5
Outdoor air temperature thermistor
Capillary tube 1
Capillary tube 2
Capillary tube 3
Heat exchanger
thermistor
Muffler with
filter
Refrigerant flow
Cooling
Heating
Capillary tube 4
Filter
Motor operated
valve
Propeller fan
Filter
Four way valve
on : heating
Muffler with filter
Field piping
Muffler
Liquid stop valve
Muffler
Field piping
Discharge pipe
thermistor
Compressor
Accumulator
Gas stop valve with service
port
3D052750F
• AlthermaTM • Outdoor units
17
• Outdoor units • ERHQ006-008AD
1
6
Wiring diagram
6-1
Wiring diagram
ERHQ006-008AD
6
Power supply
To indoor unit
Sheet
metal
Indoor
g
Field wiring
(outdoor) (discharge)
(Condenser)
Outdoor
Z1C∼Z7C
X1M, X2M
Y1E
V2, V3, V5, V9, V100
SA2
FU1, FU2, FU3:
AC1, AC2
U, V, W, X11A, X12A
E1, E2
HR1, HR2
18
: Ferrite core
: Terminal strip
: Electronic expansion valve coil
: Varistor
: Surge arrester
: Fuse
: Connector
MRM10, MRM20
MRC/W
R1T∼R3T
S2∼S102
LEDA
L
N
SW1
SW4
M1C
M1F
L1R
: Magnetic relay
: Thermistor
: Connector
: Pilot lamp
: Live
: Neutral
: Forced operation on/off switch SW (SW1)
: Local setting SW (SW4)
: Compressor motors
: Fan motor
: Reactor
• AlthermaTM • Outdoor units
Q1L
PM1
PCB1,2
Y1R
Sheet metal
: Overload protector
: Power module
: Printed circuit board
: Reversing solenoide valve coil
: Terminal strip fixed plate
3D052296E
• Outdoor units • ERHQ006-008AD
7
Sound data
7-1
Sound pressure spectrum
ERHQ008AA
HEATING
1
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ007AA
HEATING
Sound pressure level (dB)
ERHQ006AA
HEATING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
7
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
ERHQ008AA
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ007AA
COOLING
Sound pressure level (dB)
ERHQ006AA
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW57557-1A
• AlthermaTM • Outdoor units
19
• Indoor units • EKHBH-X008AA
TABLE OF CONTENTS
EKHBH-X008AA
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
24
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 28
Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
7
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
8
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Static pressure drop unit
• AlthermaTM • Indoor units
32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
21
• Indoor units • EKHBH-X008AA
1
t A i A n8 0u a 0 m X r r - o e H o h B d tH nKl E•IA
1
Features
Small capacity indoor unit
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
1
22
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X008AA
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
EKHBH008AA
Outdoor units
ERHQ008ADV3
Nominal input (Indoor only)
Casing
W
230
Colour
Packing
Unit
Weight
Packing
230
RAL9010
Material
Dimensions
EKHBX0008AA
1
2
Epoxy polyester painted galvanised steel
Height
mm
Width
mm
660
1,225
660
Depth
mm
610
610
Height
mm
922
922
Width
mm
502
502
Depth
361
mm
361
Unit
kg
52
52
Packed Unit
kg
67
67
Material
EPS
Wood
Carton
PP (Straps)
Weight
kg
10
Type
10
Main
components
Pump
Water cooled
Nr. of speed
3
3
Pump
Nominal ESP
unit
Heating
38
38
Cooling
kPa
Main
components
Pump
Power
input
W
130
130
Water side
Heat
exchanger
Type
kPa
48
Brazed plate
Qty
1
1
0.67
0.67
12
Water
volume
l
Water
flow rate
Min.
l/min
12
l/min
24.1
Water side
Heat
exchanger
Water flow rate Heating
Nom.
Cooling
Main
components
Water side
Heat
exchanger
Insulation material
Expansion
vessel
Volume
l
10
10
Max.
water
pressure
bar
3
3
Pre
pressure
bar
1
1
Diameter mm
perforatio
ns
1
1
Water filter
17.4
Polyurethane foam
Material
Water circuit
Piping connections
diameter
24.1
l/min
Brass
inch
Piping
inch
Safety valve
bar
G1 (MALE)
1-1/4’’
3
Manometer
3
Yes
Drain valve / Fill valve
Yes
Shut off valve
Yes
Air purge valve
Yes
Total water volume (6)
l
Refrigerant
Circuit
Gas side diameter
mm
Liquid side diameter
mm
Sound level
Sound Pressure
dBA
28
28
Sound Power
dBA
42
42
• AlthermaTM • Indoor units
5.5
5.5
15,9
6,35
23
• Indoor units • EKHBH-X008AA
2
2-1
1
Specifications
TECHNICAL SPECIFICATIONS
Operation
range
2
Ambient
Waterside
2-2
°C
Cooling
°C
Heating
°C
Cooling
°C
ELECTRICAL SPECIFICATIONS
Electric heater
Current
Current
Electric heater
EKHBH008AA
EKHBX0008AA
3V3
Phase
1~
Frequenc Hz
y
50
50
Voltage
V
230
230
Running
Current
A
13
13
List
No requirements
0.25 + j0.15
Current
Minimum Ssc value
Voltage range
Minimum
-10%
Maximum
+10%
Type
Power Supply
Current
Equipment complying with EN/IEC 61000-3-12
Quantity of wires
Type of wires
3G
Select diameter and type according to national and local regulations
6V3
Phase
1~
Frequenc Hz
y
50
50
Voltage
V
230
230
Running
Current
A
26
26
Z-max
Text
0.25 + j0.15
Zmax electric
heater +
booster heater
(EKSWW*
Models)
Text
0.15 + j0.09
Current
Minimum Ssc value
Voltage range
Minimum
-10%
Maximum
+10%
Wiring
connections
For power
supply backup
heater
Electric heater
Type
Power Supply
Current
Electric heater
5~22
Text
Electric heater
Current
10~43
15~50
Zmax electric
heater +
booster heater
(EKSWW*
Models)
For power
supply backup
heater
Electric heater
EKHBX0008AA
-20~25
Z-max
Wiring
connections
Current
EKHBH008AA
Type
Power Supply
24
Heating
Equipment complying with EN/IEC 61000-3-12
Quantity of wires
Type of wires
3G
Select diameter and type according to national and local regulations
6WN
Phase
3~
Frequenc Hz
y
50
50
Voltage
V
400
400
Running
Current
A
8.7
8.7
Z-max
List
No requirements
Zmax electric
heater +
booster heater
(EKSWW*
Models)
List
No requirements
Current
Minimum Ssc value
Voltage range
Minimum
-10%
Maximum
+10%
• AlthermaTM • Indoor units
Equipment complying with EN/IEC 61000-3-12
• Indoor units • EKHBH-X008AA
2
2-2
Specifications
ELECTRICAL SPECIFICATIONS
Wiring
connections
For power
supply backup
heater
Electric heater
Type
Power Supply
EKHBH008AA
Quantity of wires
Type of wires
Current
Electric heater
Wiring
connections
Electric heater
Phase
Electric heater
Wiring
connections
Electric heater
Voltage
V
230
230
Running
Current
A
15.1
15.1
List
Out of scope
List
Out of scope
Current
Minimum Ssc value
Voltage range
Minimum
-10%
Maximum
+10%
Quantity of wires
Type of wires
4G
Select diameter and type according to national and local regulations
9WN
Phase
3~
Frequenc Hz
y
50
50
Voltage
V
400
400
Current
Running
Current
A
13
13
Z-max
List
No requirements
Zmax electric
heater +
booster heater
(EKSWW*
Models)
List
No requirements
Current
Minimum Ssc value
Voltage range
Minimum
-10%
Maximum
+10%
For power
supply backup
heater
Equipment complying with EN/IEC 61000-3-12
Quantity of wires
Type of wires
4G
Select diameter and type according to national and local regulations
Type
9T1
Phase
3~
Frequenc Hz
y
Current
Electric heater
Equipment complying with EN/IEC 61000-3-12
Type
Power Supply
Current
2
50
Z-max
For power
supply backup
heater
1
3~
50
Zmax electric
heater +
booster heater
(EKSWW*
Models)
Power Supply
Current
Select diameter and type according to national and local regulations
6T1
Frequenc Hz
y
Current
EKHBX0008AA
4G
50
50
Voltage
V
230
230
Running
Current
A
22.6
22.6
Z-max
List
Out of scope
Zmax electric
heater +
booster heater
(EKSWW*
Models)
List
Out of scope
Current
Minimum Ssc value
Voltage range
Minimum
-10%
Maximum
+10%
• AlthermaTM • Indoor units
Equipment complying with EN/IEC 61000-3-12
25
• Indoor units • EKHBH-X008AA
2
2-2
1
Specifications
ELECTRICAL SPECIFICATIONS
Wiring
connections
2
For power
supply backup
heater
EKHBH008AA
Quantity of wires
Type of wires
Select diameter and type according to national and local regulations
Connection type
For power supply connection to Optional Warm Water Tank + Q2L
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
(4) For more details of the voltage range and current refer to installation manual EKHBH/X008AA*
Connection type
For connection with R5T
Quantity of wires
wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
For connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual EKHB/X008AA*
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Connection type
For connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Connection type
For connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Notes
EKHBX0008AA
4G
Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
In accordance with EN/IEC 61000-3-11(*), it may be necessary to consult the distribution network operator to ensure
that the equipment is connected only to a supply with Zsys(**) <= Zmax
(*) European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker
in public low-voltage supply systems for equipment with rated current <= 75A
(**) System impedance
26
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X008AA
3
Options
Factory mounted optional equipment for EKHB(H/X)008AA**
Reference
1
Description
Heating only model EKHBH008A...
Reversible model EKHBX008A...
Back up heater 3kW 1∼230 V
Back up heater 6kW 1∼230 V
Back up heater 6kW 3∼400 V
Back up heater 6kW 3∼230 V
Back up heater 9kW 3∼400 V
Back up heater 9kW 3∼230 V
3V3
6V3
6WN
6T1
9WN
9T1
A3V3
A3V3
V
⎯
⎯
⎯
⎯
⎯
V
⎯
⎯
⎯
⎯
⎯
A6V3
⎯
V
⎯
⎯
⎯
⎯
A6V3
⎯
V
⎯
⎯
⎯
⎯
A6WN
⎯
⎯
V
⎯
⎯
⎯
A6WN
⎯
⎯
V
⎯
⎯
⎯
A6T1
⎯
⎯
⎯
V
⎯
⎯
A6T1
⎯
⎯
⎯
V
⎯
⎯
A9WN
A9WN
⎯
⎯
⎯
⎯
V
⎯
⎯
⎯
⎯
⎯
V
⎯
A9T1
⎯
⎯
⎯
⎯
⎯
V
A9T1
⎯
⎯
⎯
⎯
⎯
V
3
Outdoor combination table for EKHB(H/X) 008AA**
EKHBH008AA*
EKHBX008AA*
Heating only indoor unit
Reversible indoor unit
ERHQ006ADV3(8)
V
V
ERHQ007ADV3(8)
V
V
ERHQ008ADV3(8)
V
V
Bottom plate heater (1) (3)
drain plug kit (3)
drain stop kit (3)
ERHQ006ADV3
V
V
V
ERHQ007ADV3
V
V
V
ERHQ008ADV3
V
V
V
A3V3
A6V3
Kit availability for ERHQ006-008AD*
EKBPHT08
EKDK02
EKDK03
Kit availability for EKHB(H/X)008AA*
Reference
Description
EKHWS150(A/B)3V3
EKHWS200(A/)B3V3
EKHWS300(A/B)3V3
EKHWS200(A/B)3Z2
EKHWS300(A/B)3Z2
EKHWSU150(A/B)3V3
EKHWSU200(A/B)3V3
EKHWSU300(A/B)3V3
EKHWE150A3V3
EKHWET150A3V3
EKHWE200A3V3
EKHWE300A3V3
EKHWE200A3Z2
EKHWE300A3Z2
EKHBDP
EKRP1HB
EKRTW
EKRTR
EKRTETS
Heating only model EKHBH008A...
Reversible model EKHBX008A...
Domestic hot water tank 150l 1-230V
Domestic hot water tank 200l 1-230V
Domestic hot water tank 300l 1-230V
Domestic hot water tank 200l 2-400V
Domestic hot water tank 300l 2-400V
Domestic hot water tank 150l 1-230V
Domestic hot water tank 200l 1-230V
Domestic hot water tank 300l 1-230V
Enamel domestic hot water tank 150l 1∼230V
Wallmounted enamel domestic hot water tank 150l
1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
Option kit for condensate free cooling operation
Digital I/O PCB (2)
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (4)
A3V3
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
A6V3
V
V
V
V
V
V
V
A6WN
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
A6WN
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
A6T1
V
V
V
V
V
V
V
A6T1
V
V
V
V
V
V
V
A9WN
A9WN
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
A9T1
V
V
V
V
V
V
V
A9T1
V
V
V
V
V
V
V
V
V
V
V
V(*)
V(*)
V
V
V(*)
V(*)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V(*)
V(*)
V
V
V
V
V
V
V(*)
V(*)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V(*)
V(*)
V
V
V
V
V
V
V(*)
V(*)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
150(A/B)
200(A/B)
300(A/B)
V
V
V
-
V
-
(*) If neutral line is available
Kit available for EKHWS*
Reference
EKUHWA
EKUHWB
EKUHW2WB
EKSOLHWAV1
EKWBSWW150
Description
EKHWE(T)*3(V3/Z2)
EKHWS*3(V3/Z2)
EKHWSU*3V3
Option kit for UK EKHWSU150-300V3
Option kit 1 for UK EKHWSU150-300V3 (8)
Option kit 2 for UK EKHWSU150-300V3 (8)
Solarkit (5)
Wall bracket for EKHWS(U)150(A/B)3V3 or EKSWW150V3
150A
200A
300A
V
V
V
-
V
-
150A
V
V(6)
V(6)
V
V
200A
V
V(6)
V(6)
V
-
300A
V
V(6)
V(6)
V
-
150B
V
V
V(7)
V
V
200B
V
V
V(7)
V
-
300B
V
V
V(7)
V
-
Remarks: Other combinations than mentioned in this option TW are not guaranteed.
(1) Heater tape that can be fixed on the bottom plate to prevent ice formation.
(2) Address card that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included.
(3) It is not allowed to combine bottom plate heater and drain plug/stop kit
(4) EKRTETS can only be used in combination with EKRTR
(5) Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
(6) If installation on tank A version both kits are required
(7) Kit is only necessary when installing EKSOLHWAV1 on a UK tank B-series (EKHWSU(150/200/300)B3V3)
(8) EKUHWB = EKUHWA - (2 way valve and 2 way valve accessories)
EKUHW2WB = 2 way valve and 2 way valve accessories
3TW57789-2G
• AlthermaTM • Indoor units
27
• Indoor units • EKHBH-X008AA
1
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKHBH008AA
FIXATION
4
Service door
(Closed) 361
(Open) 553
G 1 (Male)
Center of gravity
j
1 Pump + switch for speed setting
j
2 Remocon
j
3 Water IN connection G 1 1/2 (female)
j
4 Water OUT connection G 1 1/2 (female)
j
5 Power supply intake (+ domestic hot water tank)
j
6 Air purge
j
7 Expansion vessel+j
7A nipple+j
7B Drain
j
8 Blow off valve
j
9 Blow off drain (flexible hose J20)
j
10 Pressure gauge
j
11 Water filter
j
12 Suction pipe connection J15.9 flare connection
j
13 Liquid pipe connection J6.35 flare connection
j
14 Shut off valves with drain/fill valve (accessory
delivered with unit)
j
15 Holes for fixation
j
16 Switchbox terminals
j
17 Switchbox terminals option domestic hot water tank
j
18 Wallbracket
Dimensions
wallbracket
Minimum space for service & ventilation
Min. 150
Min. 200
3TW57784-1A
EKHBX008AA
FIXATION
Service door
(Closed) 361
(Open) 553
G 1 (Male)
Dimensions
wallbracket
Minimum space for service & ventilation
Min. 150
Min. 200
Center of gravity
j
1 Pump + switch for speed setting
j
2 Remocon
j
3 Water IN connection G 1 1/2 (female)
j
4 Water OUT connection G 1 1/2 (female)
j
5 Power supply intake (+ domestic hot water
tank)
j
6 Air purge
j
7 Expansion vessel+j
7A nipple+j
7B Drain
j
8 Blow off valve
j
9 Blow off drain (flexible hose J20)
j
10 Pressure gauge
j
11 Water filter
j
12 Suction pipe connection J15.9 flare
connection
j
13 Liquid pipe connection J6.35 flare
connection
j
14 Shut off valves with drain/fill valve (accessory
delivered with unit)
j
15 Holes for fixation
j
16 Switchbox terminals
j
17 Switchbox terminals option domestic hot
water tank
j
18 Wallbracket
3TW57784-2A
28
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X008AA
5
Piping diagram
EKHBH(X)008AA
R4T
R3T
R2T
R1T
Water side
1
Inlet water thermistor
Refrigerant liquid side thermistor
Outlet water backup heater thermistor
Outlet water heat-exchanger thermistor
Field installation
5
Filter
Inlet
Shut off valve
Refrigerant side
Safety valve
Drain valve
Pressure gauge
Drain
Expansion
vessel
Cooling (EKHBX)
Heating (EKHBX + EKHBH)
Option backup
heater
Drain valve
Field installation
Air purge
Flowswitch
Pump
Outlet
Shut off valve
Overview
Electric heater body
Evaporator
Condensor
Outdoor unit
Refr. out
Refr. in
Water inlet
Refrigerant
side
Water side
Refr. in
Water outlet
Refr. out
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe
• AlthermaTM • Indoor units
3TW56715-1
29
• Indoor units • EKHBH-X008AA
1
6
Wiring diagram
6-1
Wiring diagram
EKHBH(X)008AA3V3
Power supply
230V 1N∼50Hz
Only for EKSOLHWAV1
Option
Outdoor unit
Solar pump connection
>> See note 2 <<
Domestic hot
water tank
Only
See note 9
6
for EKHW Option
Only for EKHW(S/E) Option
See note 7
For EKHWSU*V3
Option
User interface
Alarm output
Solar input
Cooling/heating
on/off output
Only for EKHW Option
Only for EKRTW Option
230V AC
heating
cooling
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
Domestic hot
supply from
PCB
Only for EKRTR Option
water tank
Only for EKHWS*V3
Option
See note 7
For EKHWSU*V3 Option
3 wire type
(SPST)
Only for EKSOLHWAV1
Option
Only for EKHW
Option
NO valve
Only
for EKHW(S/E) Option
for EKRTETS Option
F1B
NC valve
F2B
: Terminal strips
: Spark suppression 2
: Spark suppression 1
: Fuse 3.15A T 250V
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Earth leakage protector
: Thermal protector booster heater
: Thermal protector backup heater
: Solar pumpstation relay
: DIP switch
: Transformer 24V for PCB
: Domestic hot water thermistor
: Inlet water thermistor
: Refrigerant liquid side thermistor
: Outlet water backup heater thermistor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Humidity sensor
: Ambient sensor
: Flowswitch
: Booster heater (3kW)
: Backup heater element 1
: 3way valve: floorheating/domestic hot water
: 2 way valve for cooling mode
: Pump
: Optocoupler input circuit
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M
: Contactor backup heater Step 1
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse backup heater
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
Electric heater fuse
20A
Only
Example field
supply
thermostat
X1M-X9M
V2S
V1S
FU1
FU2
FuS, FuR
Q1DI
Q2L
Q1L
S1S
SS1
TR1
R5T
R4T
R3T
R2T
R2T (EKRTETS)
R1T
R1H (EKRTR)
R1T (EKRTW/R)
S1L
E4H
E1H
M3S
M2S
M1P
PHC1
K5M
EKHW kit fuse
20A
Notes:
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit. (L,N)
9 For EKSOLHWAV1, refer to option manual
Domestic hot water
tank
Only for EKHWE*V3
Option
Wiring dependent
on model
Field wiring
PCB
Option
Field wiring
Wire colour
3TW57786-2B
EKHBH(X)008AA6V3
Outdoor unit
Power supply
230V 1N∼50Hz
Only for EKSOLHWAV1
Option
Domestic hot water
Solar pump connection
>> See note 2 <<
See note 9
tank
Only
for EKHWE*Option
Only
for EKHW(S/E)*Option
See note 7
For EKHWSU*V3 Option
User interface
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
heating
cooling
Solar input
Alarm output
Cooling/heating
on/off output
Only for EKHW Option
Only
for EKRTW* Option
230V AC
supply from PCB
Only
for EKRTR* Option
Domestic hot water
tank
3 wire type (SPST)
Only forEKHWS*V3
Option
See note 7
For EKHWSU*V3 Option
NO valve
Only for EKHW
Option
Only for EKSOLHWAV1
Option
Only
for EKHW(S/E)* Option
Electric heater fuse
32A
F1B
Only
for EKRTETS* Option
Example field
supply
thermostat
NC valve
F2B
X1M-X9M
: Terminal strips
V2S
: Spark suppression 2
V1S
: Spark suppression 1
FU1
: Fuse 3.15A T 250V
FU2
: Fuse 5A T 250V
FuS, FuR
: Fuse 5A 250V for solar/remote alarm PCB
Q1DI
: Earth leakage protector
Q2L
: Thermal protector booster heater
Q1L
: Thermal protector backup heater
S1S
: Solar pumpstation relay
SS1
: DIP switch
TR1
: Transformer 24V for PCB
R5T
: Domestic hot water thermistor
R4T
: Inlet water thermistor
R3T
: Refrigerant liquid side thermistor
R2T
: Outlet water backup heater thermistor
R2T (EKRTETS) : External sensor (floor or ambient)
R1T
: Outlet water heat-exchanger thermistor
R1H (EKRTR) : Humidity sensor
R1T (EKRTW/R) : Ambient sensor
S1L
: Flowswitch
E4H
: Booster heater (3kW)
E1H-E2H
: Backup heater element 1-2
M3S
: 3way valve: floorheating/domestic hot water
M2S
: 2 way valve for cooling mode
M1P
: Pump
PHC1
: Optocoupler input circuit
K5M
: Contactor for backup heater all-pole disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M/K2M
: Contactor backup heater step 1/2
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse backup heater
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
EKHW kit fuse
20A
Domestic hot water
tank
Notes:
See note 7
For EKHWE Option
Wiring dependent
on model
Field wiring
Option
Field wiring
PCB
Wire colour
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit. (N,L)
9 For EKSOLHWAV1, refer to option manual
3TW57786-3B
30
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X008AA
6
Wiring diagram
6-1
Wiring diagram
EKHBH(X)008AA6WN/9WN
Power supply
3(/N)∼400(/230V) 50Hz
Domestic hot
water tank
Only for EKSOLHWAV1
Option
Outdoor unit
1
Domestic hot
water tank
Solar pump connection
>> See note 2 <<
Only
See note 9
for EKHWE Option
6
Only for EKHWS*Z2
Option
Only for EKHW(S/E)* Option
See note 7
Only for EKHW
Option
Only
for EKRTW Option
230V AC
heating
cooling
Only for EKRP1HB &
ESOLHWAV1
Option
See note 8
supply from PCB
Only
for EKRTR* Option
Domestic hot water
tank
Domestic hot water
tank
User interface
Solar input
Cooling/heating
on/off output
Alarm output
For EKHWSU*V3 Option
3 wire type (SPST)
Only for EKHW
Option
NO valve
Only
for EKHW(S/E)* Option
Only forEKHS*V3
Only forEKHWS*Z2
Option
Option
See note 7
For EKHWSU*V3 Option
Only
for EKRTETS* Option
Model
F1B
Example field
supply
thermostat
Only
for EKSOLHWAV1
Option
Electric heater fuse
6WN
16A
X1M-X9M
V2S
V1S
FU1
FU2
FuS, FuR
Q1DI
Q2L
Q1L
S1S
SS1
TR1
R5T
R4T
R3T
R2T
R2T (EKRTETS)
R1T
R1H (EKRTR)
R1T (EKRTW/R)
S1L
E4H
E1H-E3H
M3S
: Terminal strips
: Spark suppression 2
: Spark suppression 1
: Fuse 3.15A T 250V
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Earth leakage protector
: Thermal protector booster heater
: Thermal protector backup heater
: Solar pumpstation relay
: DIP switch
: Transformer 24V for PCB
: Domestic hot water thermistor
: Inlet water thermistor
: Refrigerant liquid side thermistor
: Outlet water backup heater thermistor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Humidity sensor
: Ambient sensor
: Flowswitch
: Booster heater (3kW)
: Backup heater element 1-3
: 3way valve: floorheating/domestic hot
water
M2S
: 2 way valve for cooling mode
M1P
: Pump
PHC1
: Optocoupler input circuit
K5M
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M/K2M
: Contactor backup heater step 1/2
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse backup heater
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
9WN
20A
NC valve
F2B
EKHW kit fuse
20A
Notes:
Domestic hot water
tank
Domestic hot water
tank
Only forEKHWE*V3
Option
Only forEKHWE*Z2
Option
Wiring dependent
on model
Field wiring
Option
PCB
Field wiring
Wire colour
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit. (N,L)
9 For EKSOLHWAV1, refer to option manual
3TW57786-4B
EKHBH(X)008AA6T1/9T1
Power supply
3∼230V 50Hz
>> See note 2 <<
Only for EKSOLHWAV1
Option
Outdoor unit
Domestic hot water
Solar pump connection
See note 9
tank
Only for EKHWE
Option
Only for EKHW(S/E) Option
Only for EKHW
Option
Only for EKRTW
Option
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
230V AC
heating
cooling
Alarm output
User interface
Solar input
Cooling/heating
on/off output
See note 7
For EKHWSU*V3
Option
supply from PCB
Only for EKRTR Option
Domestic hot water
tank
3 wire type (SPST)
Only for EKHW Only for EKSOLHWAV1
Option
Option
NO valve
Only for EKHW(S/E)
Option
Only for EKHWS*V3
Option
See note 7
For EKHWSU*V3 Option
Only for EKRTETS
Option
Example field
supply
thermostat
Model
F1B
Electric heater fuse
6T1
20A
X1M-X9M
V2S
V1S
FU1
FU2
FuS, FuR
Q1DI
Q2L/Q3L
Q1L
S1S
SS1
R5T
R4T
R3T
R2T
R2T (EKRTETS)
R1T
R1H (EKRTR)
R1T (EKRTW/R)
S1L
E4H
E1H-E3H
M3S
M2S
M1P
PHC1
K5M
: Terminal strips
: Spark suppression 2
: Spark suppression 1
: Fuse 3.15A T 250V
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Earth leakage protector
: Thermal protector booster heater
: Thermal protector backup heater
: Solar pumpstation relay
: DIP switch
: Domestic hot water thermistor
: Inlet water thermistor
: Refrigerant liquid side thermistor
: Outlet water backup heater thermistor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Humidity sensor
: Ambient sensor
: Flowswitch
: Booster heater (3kW)
: Backup heater element 1-3
: 3way valve: floorheating/domestic hot water
: 2 way valve for cooling mode
: Pump
: Optocoupler input circuit
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M/K2M
: Contactor backup heater step 1/2
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse backup heater
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
9T1
32A
NC valve
F2B
EKHW kit fuse
20A
Notes:
Domestic hot water
tank
Only for EKHWE*V3
Option
Wiring dependent
on model
Field wiring
Option
Field wiring
PCB
Wire colour
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit. (L,N)
9 For EKSOLHWAV1, refer to option manual
3TW57786-6B
• AlthermaTM • Indoor units
31
• Indoor units • EKHBH-X008AA
1
6
6
Wiring diagram
6-2
External connection diagram
EKHBH(X)008AA
Standard parts
Power supply
Outdoor unit
3 core
Unit power supply: 230V + earth
For more details please check unit wiring
diagram
X1M:L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Optional power supply
X2M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
4 core
3 or4 core
3 core
Optional parts
Field supply
X1M:9-10-11-Earth
Sanitary tank
2 way valve
2 core
Q3L - Q1T
Clixon
Thermostat
2 way valve
Only for EKSWWU*V3
Power supply booster
heater
5 core
230V or400V
Q2L - Clixon booster heater
NO valve:
NC valve:
2 core
Thermistor cable
Note: min. distance to
power cable = 3cm
Room thermostat
A3P (optional)
2 core
2 core
R5T - Thermistor water
temperature
Signal
4 core
X1M:7-8-Earth
2 way valve
M2S (EKHBX Units)
for cooling mode
3 way valve
M3S (when EKSWW is installed)
selection sanitary-floorheating
Indoor unit
User interface
3TW56719-6A
32
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X008AA
7
Operation range
Outdoor temp. (°CDB)
EKHBH(X)008AA
ERHQ006-008AD
1
Cooling mode
7
Leaving evaporator water temperature (°C)
Outdoor temp. (°CDB)
Heating mode
: Units with optional back up
heater
Leaving condenser water temperature (°C)
50
Domestic hot water
Outdoor temp. (°CDB)
: Booster heater operation only
: Units with optional back up
heater or booster heater
operation only
Water temperature sanitary tank (°C)
4TW57553-1A
• AlthermaTM • Indoor units
33
• Indoor units • EKHBH-X008AA
1
8
Hydraulic performance
8-1
Static pressure drop unit
EKHBH(X)008AA
ESP [kPa]
8
Flow (l/min)
III: High speed
II: medium speed
I: Low speed
ESP: External static pressure
Flow: waterflow through the unit
Warning:
1. Selecting a flow outside the curves can cause
damage to or malfunction of the unit. See also
minimum and maximum allowed water flowrange in
the technical specifications.
2. Water quality must be according to EN directive EC
98/83 EC.
4TW57789-1
34
• AlthermaTM • Indoor units
EEDEN09-720
technical data
AlthermaTM
Part 2/4:
ERHQ011-016AA
ERHQ011-016AAW1
EKHBH(X)016AB
• Outdoor units • ERHQ011-016AAV3
TABLE OF CONTENTS
ERHQ011-016AAV3
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
3
Heating capacity tables
Cooling capacity tables
4
39
41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 44
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
45
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Wiring diagram
7
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
Service space
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• AlthermaTM • Outdoor units
49
51
37
• Outdoor units • ERHQ011-016AAV3
1
A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H uRl EA•O
Features
Single phase large capacity outdoor unit
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
2
1
38
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAV3
2
Specifications
2-1 NOMINAL CAPACITY AND
NOMINAL INPUT
ERHQ011AA
ERHQ014AA
ERHQ016AA
For
combination
indoor units +
outdoor units
Indoor Units
Condition 1
Heating
capacity
Nominal
kW
11.2
14.0
16.0
Heating PI
Nominal
kW
2.46
3.17
3.83
COP
Nominal
4.55
4.42
4.18
Heating
capacity
Nominal
kW
10.3
13.1
15.2
Heating PI
Nominal
kW
3.06
3.88
4.66
COP
Nominal
3.37
3.38
3.26
Nominal
Capacity
EKHBH016AB
2
For
combination
indoor units +
outdoor units
Indoor Units
Condition 1
Heating
capacity
Nominal
kW
11.2
14.0
16.0
Cooling
capacity
Nominal
kW
13.9
17.3
17.8
Heating PI
Nominal
kW
2.46
3.17
3.83
Cooling PI
Nominal
kW
3.79
5.78
6.77
COP
Nominal
4.55
4.42
4.18
Nominal
Capacity
2
EKHBX016AB
EER
Nominal
3.67
2.99
2.63
Heating
capacity
Nominal
kW
10.3
13.1
15.2
Cooling
capacity
Nominal
kW
10.0
12.5
13.1
Heating PI
Nominal
kW
3.06
3.88
4.66
Cooling PI
Nominal
kW
3.60
5.29
5.95
COP
Nominal
3.37
3.38
3.26
EER
Nominal
2.78
2.36
2.20
Notes
Condition 1: cooling Ta 35°C - LWE 18°C - heating Ta DB/WB 7°C/6°C - LWC 35°C ( DT = 5°C )
Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
2-2
TECHNICAL SPECIFICATIONS
Casing
ERHQ011AA
Colour
Unit
Packing
Weight
Packing
ERHQ016AA
Ivory white
Material
Dimensions
ERHQ014AA
Painted galvanised steel plate
Height
mm
Width
mm
900
1,170
900
900
Depth
mm
320
320
320
Height
mm
Width
mm
980
1,349
980
980
Depth
mm
420
420
420
Unit
kg
103
103
103
Packed Unit
kg
114
114
114
Material
EPS
Carton
Wood
PP (Straps)
Weight
kg
11
• AlthermaTM • Outdoor units
11
11
39
• Outdoor units • ERHQ011-016AAV3
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Heat
Exchanger
Dimensions
Length
mm
Nr of Rows
Fin Pitch
2
mm
Nr of Passes
Face
Area
2
m²
Nr of Stages
ERHQ011AA
ERHQ014AA
ERHQ016AA
857
857
857
2
2
2
1.4
1.4
1.4
6
6
6
0.98
0.98
0.98
52
52
52
Tube type
Fin
Hi-XSS(8)
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
2
Air Flow Rate
(nominal at
230V)
Heating
High
m³/min
90
90
90
Cooling
High
m³/min
96
100
97
Fan
Discharge direction
Motor
2
Horizontal
Quantity
2
Model
Motor
Fan
Speed
(nominal)
Steps
Motor
8
8
8
760
760
760
Cooling
rpm
800
850
830
Output
W
70
70
70
Direct drive
Quantity
Motor
1
Model
W
2,200
Starting Method
Operation
Range
Heating
Cooling
Sanitary water
Sound Level
(nominal)
Refrigerant
Inverter driven
Output
W
33
33
33
Min
°CWB
-20
-20
-20
Max
°CWB
35
35
35
Min
°CDB
10
10
10
Max
°CDB
46
46
46
-20
Min
°CDB
-20
-20
Max
°CDB
43
43
43
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
49
51
53
Sound
Power
dBA
64
66
69
Sound
Pressure
dBA
50
52
54
Heating
Sound
Pressure
dBA
42
42
43
Cooling
Sound
Pressure
dBA
45
45
46
kg
3.7
Heating
Cooling
Sound Level
(Night quiet)
Type
Charge
R-410A
Control
40
1
Type
Charged Volume
3.7
3.7
Expansion valve(electronic type)
Nr of Circuits
Refrigerant Oil
1
Hermetically sealed scroll compressor
Motor
Output
Crankcase
Heater
1
JT100G-VD
Type
Motor
2
rpm
Heating
Drive
Compressor
2
Brushless DC motor
1
1
Daphne FVC68D
l
1.0
• AlthermaTM • Outdoor units
1.0
1.0
• Outdoor units • ERHQ011-016AAV3
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Piping
connections
Liquid (OD)
Quantity
ERHQ011AA
ERHQ014AA
ERHQ016AA
1
1
1
Type
Flare connection
Diameter
(OD)
Gas
mm
Quantity
9,52
1
Type
mm
Quantity
2
3
3
3
Hole
Diameter
(OD)
mm
Minimum
26
26
26
m
5
5
5
Maximum m
75
75
75
Equivalent m
95
95
95
Chargeless m
30
30
30
Additional Refrigerant
Charge
Installation
height
difference
2
15,9
Type
Piping Length
1
Flare connection
Diameter
(OD)
Drain
1
kg/m
Maximum m
See installation manual outdoor unit 4PW37976-1B
30
Heat Insulation
30
30
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Safety Devices
Fan motor thermal protector
Fuse
High pressure switch
Standard
Accessories
Item
Tie-wraps
Quantity
2
Item
2
2
Installation manual
Quantity
1
Notes
1
1
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value
depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
Down to 3m with recharging of the outdoor unit. Refer to the installation manual of the outdoor unit.
2-3
ELECTRICAL SPECIFICATIONS
Power Supply
ERHQ011AA
Name
1~
Frequency
Hz
50
50
50
Voltage
V
230
230
230
Voltage range
Minimum
V
-10%
Maximum V
+10%
Minimum Ssc value
Maximum
running
Current
kVa
Cooling
Recomended fuses
Wiring
connections
For Power
Supply
Equipment complying with EN/IEC 61000-S-12 (1)
A
22.8
A
32
27.4
31.9
32
32
Remark
See installation manual outdoor unit 4PW37976-1B
For connection Remark
with indoor
See installation manual outdoor unit 4PW37976-1B
Power Supply Intake
Notes
ERHQ016AA
V3
Phase
Current
ERHQ014AA
Outdoor unit only
(1) European/international technical standard setting the limits for harmonic currents produced by equipment
connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase.
• AlthermaTM • Outdoor units
41
• Outdoor units • ERHQ011-016AAV3
3
Capacity tables
3-1
Heating capacity tables
Maximum Heating Capacity (Peak values)
Model
2
3
ERHQ11
ERHQ14
ERHQ16
LWC
Tamb
-20
-15
-7
-2
2
7
12
15
20
-20
-15
-7
-2
2
7
12
15
20
-20
-15
-7
-2
2
7
12
15
20
30
HC
5.66
6.48
8.04
9.18
10.2
11.6
13.1
14.1
15.9
7.24
8.19
10.1
11.5
12.7
14.4
16.3
17.6
19.9
8.35
9.38
11.5
13.0
14.4
16.3
18.5
20.0
22.5
35
PI
2.17
2.21
2.24
2.24
2.23
2.21
2.18
2.15
2.10
2.72
2.78
2.84
2.87
2.87
2.88
2.86
2.85
2.82
3.25
3.33
3.42
3.46
3.48
3.50
3.51
3.51
3.50
HC
5.48
6.25
7.74
8.84
9.81
11.2
12.7
13.6
15.4
7.14
8.01
9.78
11.1
12.3
14.0
15.9
17.1
19.3
8.31
9.33
11.3
12.7
14.1
16.0
18.1
19.5
22.0
40
PI
2.37
2.42
2.46
2.47
2.47
2.46
2.43
2.41
2.36
2.97
3.04
3.11
3.14
3.16
3.17
3.16
3.15
3.13
3.54
3.63
3.73
3.78
3.81
3.83
3.85
3.86
3.85
HC
5.44
6.17
7.63
8.71
9.68
10.8
12.2
13.2
14.9
7.05
7.85
9.51
11.1
12.2
13.5
15.4
16.5
18.7
8.27
9.28
11.1
12.5
13.8
15.6
17.6
19.0
21.4
PI
2.37
2.42
2.46
2.33
2.39
2.46
2.43
2.41
2.36
2.97
3.04
3.11
2.96
3.05
3.17
3.16
3.15
3.13
3.54
3.63
3.64
3.56
3.45
3.83
3.85
3.86
3.85
HC
4.84
5.49
6.54
7.06
7.75
10.8
12.2
13.2
14.9
6.28
6.99
7.62
8.95
9.65
13.5
15.4
16.5
18.7
7.36
8.26
8.63
10.1
10.6
15.6
17.6
19.0
21.4
45
PI
2.61
2.67
2.72
2.74
2.74
2.74
2.72
2.70
2.65
3.26
3.34
3.43
3.47
3.48
3.50
3.50
3.50
3.48
3.89
3.98
4.10
4.15
4.19
4.22
4.24
4.25
4.25
50
55
HC
PI
HC
PI
HC
PI
7.50
8.57
9.52
10.3
11.8
12.7
14.4
3.02
3.05
3.06
3.06
3.04
3.03
2.99
8.18
9.10
9.94
11.3
12.2
13.8
3.36
3.38
3.42
3.41
3.40
3.37
8.72
9.53
10.9
11.7
13.3
3.77
3.82
3.81
3.81
3.78
9.25
10.7
11.8
13.1
14.9
16.0
18.1
3.79
3.74
3.76
3.88
3.89
3.89
3.87
10.4
11.4
12.7
14.4
15.5
17.5
4.14
4.17
4.30
4.32
4.32
4.31
11.1
12.3
13.9
15.0
17.0
4.62
4.77
4.79
4.80
4.80
10.9
12.2
13.5
15.2
17.2
18.5
20.8
4.52
4.58
4.62
4.66
4.69
4.69
4.70
12.0
13.1
14.8
16.7
18.0
20.3
5.06
5.11
5.15
5.18
5.20
5.21
11.9
13.4
15.1
16.6
18.7
5.35
5.40
5.44
5.75
5.77
HC
PI
HC
PI
HC
PI
6.43
6.94
7.63
10.3
11.8
12.7
14.4
3.02
2.87
2.96
3.06
3.04
3.03
2.99
6.63
7.29
9.94
11.3
12.2
13.8
3.17
3.26
3.42
3.41
3.40
3.37
6.99
9.53
10.9
11.7
13.3
3.64
3.82
3.81
3.81
3.78
7.42
8.65
9.32
13.1
14.9
16.0
18.1
3.79
3.52
3.64
3.88
3.89
3.89
3.87
8.38
9.02
12.7
14.4
15.5
17.5
3.90
4.03
4.30
4.32
4.32
4.31
8.73
12.3
13.9
15.0
17.0
4.47
4.77
4.79
4.80
4.80
8.49
9.91
10.4
15.2
17.2
18.5
20.8
4.41
4.31
4.18
4.66
4.69
4.69
4.70
9.71
10.2
14.8
16.7
18.0
20.3
4.77
4.62
5.15
5.18
5.20
5.21
9.19
13.4
15.1
16.6
18.7
4.84
5.40
5.44
5.75
5.77
Maximum Heating Capacity (integrated values*)
Model
ERHQ11
ERHQ14
ERHQ16
LWC
Tamb
-20
-15
-7
-2
2
7
12
15
20
-20
-15
-7
-2
2
7
12
15
20
-20
-15
-7
-2
2
7
12
15
20
30
HC
5.04
5.77
6.89
7.43
8.16
11.6
13.1
14.1
15.9
6.45
7.29
8.06
9.27
10.0
14.4
16.3
17.6
19.9
7.44
8.35
8.91
10.5
11.1
16.3
18.5
20.0
22.5
35
PI
2.17
2.21
2.24
2.11
2.16
2.21
2.18
2.15
2.10
2.72
2.78
2.84
2.70
2.78
2.88
2.86
2.85
2.82
3.25
3.33
3.34
3.26
3.15
3.50
3.51
3.51
3.50
HC
4.88
5.56
6.63
7.16
7.86
11.2
12.7
13.6
15.4
6.35
7.13
7.84
9.00
9.71
14.0
15.9
17.1
19.3
7.39
8.30
8.77
10.3
10.9
16.0
18.1
19.5
22.0
40
45
PI
2.61
2.67
2.72
2.58
2.65
2.74
2.72
2.70
2.65
3.26
3.34
3.43
3.26
3.37
3.50
3.50
3.50
3.48
3.86
3.98
4.00
3.91
3.79
4.22
4.24
4.25
4.25
Symbols
HC
PI
LWC
Tamb
42
55
3TW57752-1B
Conditions
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
Note
1
50
For the optional model with heatertape (V38) when ambient temperature
becomes lower than 4°C: add power input of 95W
• AlthermaTM • Outdoor units
1
2
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
• Outdoor units • ERHQ011-016AAV3
3
Capacity tables
3-2
Cooling capacity tables
Maximum Cooling Capacity
ERHQ11
ERHQ14
ERHQ16
Tamb (°C)
LWE (°C)
7
10
13
15
18
22
7
10
13
15
18
22
7
10
13
15
18
22
20
CC
11.7
12.9
14.1
14.9
16.2
18.0
14.5
16.0
17.6
18.6
20.2
22.5
15.3
16.9
18.5
19.6
21.0
23.3
25
PI
2.56
2.58
2.59
2.60
2.61
2.62
3.85
3.94
4.02
4.08
4.17
4.29
4.37
4.48
4.60
4.68
4.97
5.21
CC
11.2
12.3
13.4
14.2
15.5
17.2
13.9
15.3
16.8
17.8
19.3
21.5
14.7
16.2
17.7
18.7
20.0
22.2
30
PI
2.86
2.89
2.92
2.93
2.96
2.99
4.27
4.37
4.47
4.54
4.65
4.80
4.84
4.97
5.10
5.19
5.52
5.79
CC
10.6
11.6
12.8
13.5
14.7
16.4
13.2
14.6
15.9
16.9
18.4
20.4
13.9
15.3
16.7
17.7
18.9
21.0
35
PI
3.21
3.25
3.29
3.31
3.35
3.40
4.75
4.86
4.98
5.06
5.18
5.36
5.37
5.51
5.66
5.76
6.12
6.42
CC
10.0
11.0
12.1
12.8
13.9
15.5
12.5
13.7
15.0
15.9
17.3
19.3
13.1
14.4
15.7
16.6
17.8
19.7
Symbols
CC
PI
LWE
Tamb
CC
9.39
10.3
11.3
12.0
13.1
14.7
11.7
12.9
14.1
14.9
16.2
17.0
12.2
13.3
14.6
15.4
16.4
17.0
45
PI
4.03
4.09
4.15
4.20
4.26
4.35
5.90
6.04
6.18
6.28
6.44
5.33
6.59
6.75
6.93
7.04
6.69
5.33
CC
8.75
9.65
10.6
11.3
12.3
13.3
11.1
11.2
11.9
12.2
12.9
13.3
11.1
11.2
11.9
12.2
12.9
13.3
PI
4.50
4.58
4.65
4.70
4.78
3.93
5.92
5.46
5.04
4.79
4.42
3.93
5.92
5.46
5.04
4.79
4.42
3.93
2
3
3TW57752-1B
Conditions
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Ambient temperature (°C) RH=85%
Note
1
40
PI
3.60
3.65
3.70
3.73
3.79
3.86
5.29
5.42
5.55
5.64
5.78
5.98
5.95
6.11
6.27
6.38
6.77
7.10
1
2
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For the optional model with heatertape (V38) when ambient temperature
becomes lower than 4°C: add power input of 95W
• AlthermaTM • Outdoor units
43
• Outdoor units • ERHQ011-016AAV3
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
ERHQ011-016
Hole for anchor
bolt 4-M12
1
2
3
4
5
6
7
8
2
4
Gas pipe connection ∅15.9 flare
Liquid pipe connection ∅9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock out hole ∅34)
control wiring intake (knock out hole ∅27)
Drain outlet
3TW57764-1
44
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAV3
4
Dimensional drawing & centre of gravity
4-2
Centre of gravity
ERHQ011-016
2
4
4TW57919-5
• AlthermaTM • Outdoor units
45
• Outdoor units • ERHQ011-016AAV3
5
Piping diagram
ERHQ011-016AAV3
2
Electronic expansion valve
5
Filter
Filter
Heat exchanger
4-Way-Valve
High Pressure
Low Pressure Switch
Sensor
EKHB 016
Field Piping ø9.5 C 1220T-0
Service
Port
5/16’
Compressor
Field Piping ø15.9 C 1220T-0
Accumulator
Outdoor Unit
Indoor Unit
Heating
Cooling
Stop Valve (With Service Port 5/16’ Flare)
Check Valve
Flare Conn.
Screw Conn.
Flange Conn.
Pinched Pipe
Spinned Pipe
3TW57765-1
46
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAV3
6
Wiring diagram
6-1
Wiring diagram
ERHQ011-016AAV3
Option
EKBPHT16Y
Only for
*RHQ01*AAV3(7)
Only for *RHQ01*AAV38
Indoor
Outdoor
(Note 4)
HAP
Position of
compressor
El. comp. Assy
(Position of elements)
terminal
Wire entrance
Notes:
1 This wiring diagram only applies to the outdoor unit
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Relay connector
p : Noiseless earth
G : Terminal
4 Refer to the option manual, for connecting wiring to x6A.
5 Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1∼ BS4 and DS1 switch.
6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches by service. When the unit is shipped by factory all switches are set to be off.
9
Option
(Back)
A1P
A2P
A3P
A4P
BS1∼BS4
C1∼C4
DS1
E1H
E1HC
F1U, F3U, F4U
F6U
H1P∼7P (A2P)
HAP (A1P)
K1R
K4R
K10R
K11R
L1R
M1C
M1F
M2F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
RC
R10T
S1NPH
S1PH
TC
V1R
V2R, V3R
V1T
X1M
Y1E
Y1S
Z1C∼Z3C
Z1F∼Z4F
Optional Connector
X1Y
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Printed circuit board
Push button switch
Capacitor
DIP switch
Electrical heatertape (fuse: 5A/250V)
Crankcase heater
Fuse (T 6.3A/250V)
Fuse (T 5.0A/250V)
Light emitting diode (service monitor green)
Light emitting diode (service monitor green)
Magnetic relay (Y1S)
Magnetic relay (E1HC)
Magnetic relay
Magnetic relay
Reactor
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Field earth leakage breaker (300mA)
Resistor
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Signal receiver circuit
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Signal transmission circuit
Power module
Diode module
IGBT
Terminal strip for power source
Electronic expansion valve
Solenoid valve (4 way valve)
Noise filter (ferrity core)
Noise filter
2
6
Connector
(Front)
Wiring dependent
on model
2TW57986-1A
• AlthermaTM • Outdoor units
47
• Outdoor units • ERHQ011-016AAV3
7
Sound data
7-1
Sound pressure spectrum
ERHQ011-016
ERHQ011AAV3
HEATING
ERHQ014AAV3
HEATING
ERHQ016AAV3
HEATING
2
Octave band center frequency (Hz)
Sound pressure level (dB)
Sound pressure level (dB)
Sound pressure level (dB)
7
Octave band center frequency (Hz)
Octave band center frequency (Hz)
3TW57767-2A
NOTES
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room).
dBA = A-Weighted sound pressure level. (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa.
If sound is measured under actual installation conditions, the measured value
will be higher due to environmental noise and sound reflections.
Measuring location
(Discharge side)
ERHQ011-016
ERHQ014AAV3
COOLING
Octave band center frequency (Hz)
ERHQ016AAV3
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ011AAV3
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
3TW57767-1A
NOTES
1
2
3
4
48
Data is valid at free field condition (measured in a semi-anachoic room).
dBA = A-Weighted sound pressure level. (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa.
If sound is measured under actual installation conditions, the measured value
will be higher due to environmental noise and sound reflections.
• AlthermaTM • Outdoor units
Measuring location
(Discharge side)
• Outdoor units • ERHQ011-016AAV3
7
Sound data
7-2
Sound pressure night quiet mode
ERHQ011-016
ERHQ011AAV3
HEATING
ERHQ014AAV3
HEATING
ERHQ016AAV3
HEATING
2
Octave band center frequency (Hz)
Sound pressure level (dB)
Sound pressure level (dB)
Sound pressure level (dB)
7
Octave band center frequency (Hz)
Octave band center frequency (Hz)
3TW57767-4
NOTES
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room).
dBA = A-Weighted sound pressure level. (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa.
If sound is measured under actual installation conditions, the measured value
will be higher due to environmental noise and sound reflections.
Measuring location
(Discharge side)
ERHQ011-016
ERHQ014AAV3
COOLING
Octave band center frequency (Hz)
ERHQ016AAV3
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ011AAV3
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
3TW57767-3
NOTES
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room).
dBA = A-Weighted sound pressure level. (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa.
If sound is measured under actual installation conditions, the measured value
will be higher due to environmental noise and sound reflections.
• AlthermaTM • Outdoor units
Measuring location
(Discharge side)
49
• Outdoor units • ERHQ011-016AAV3
8
Installation
8-1
Service space
ERHQ011-016
A. Non stacked installation
Legend
2
Unit: mm
Suction side obstacle
8
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
50
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAV3
9
Operation range
ERHQ011-016AAV3
Outdoor temp. (°CDB)
2
Cooling mode
9
Leaving evaporator
Water temperature (°C)
Outdoor temp. (°CDB)
Heating mode
No heat pump operation, back up heater
only
* ERHQ_V18 units include special equipment (insulation heater sheet, ...) to
ensure good operation in areas where low ambient temperature can
occur together with high humidity conditions. In such conditions the
ERHQ_V3 models may experience problems with severe ice build up on
the aircooled coil. In case such conditions are expected, the ERHQ-V38
must be installed instead. These models contain countermeasures
(insulation, heater sheet, ...) to prevent freeze up.
leaving condensor
Water temperature (°C)
Domestic hot water mode
Outdoor temp. (°CDB)
Booster heater operation only
Water temperature domestic hot
water tank (C°)
4TW57753-1B
• AlthermaTM • Outdoor units
51
• Outdoor units • ERHQ011-016AAW1
TABLE OF CONTENTS
ERHQ011-016AAW1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
55
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
55
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
3
Heating capacity tables
Cooling capacity tables
4
55
57
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 60
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
61
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Wiring diagram
7
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66
Service space
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• AlthermaTM • Outdoor units
65
67
53
• Outdoor units • ERHQ011-016AAW1
1
A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H uRl EA•O
Features
Three phase large capacity outdoor unit
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
2
1
54
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAW1
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
For combination
indoor units +
outdoor units
Condition 1
Nominal Capacity
For combination
indoor units +
outdoor units
Condition 1
Nominal Capacity
ERHQ011AAW1
Indoor Units
ERHQ014AAW1
ERHQ016AAW1
EKHBH016AB
Heating capacity
Nominal
kW
11.32
14.50
16.05
Heating PI
Nominal
kW
2.54
3.33
3.73
2
COP
Nominal
4.46
4.35
4.30
2
Heating capacity
Nominal
kW
10.98
13.57
15.11
Heating PI
Nominal
kW
3.15
4.12
4.60
COP
Nominal
3.48
3.29
3.29
Indoor Units
EKHBX016AB
Heating capacity
Nominal
kW
11.32
14.50
16.05
Cooling capacity
Nominal
kW
15.05
16.06
16.76
Heating PI
Nominal
kW
2.54
3.33
3.73
Cooling PI
Nominal
kW
4.44
5.33
6.06
COP
Nominal
4.46
4.35
4.30
EER
Nominal
Heating capacity
Nominal
3.39
3.01
2.76
kW
10.98
13.57
15.11
Cooling capacity
Nominal
kW
11.72
12.55
13.12
Heating PI
Nominal
kW
3.15
4.12
4.60
Cooling PI
Nominal
kW
4.22
5.00
5.65
COP
Nominal
3.48
3.29
3.29
EER
Nominal
2.78
2.51
2.32
Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C) - heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
2-2
TECHNICAL SPECIFICATIONS
Casing
ERHQ011AAW1
Colour
Unit
Packing
ERHQ016AAW1
Ivory white
Material
Dimensions
ERHQ014AAW1
Painted galvanised steel plate
Height
mm
Width
mm
900
1,345
900
900
Depth
mm
320
320
320
Height
mm
Width
mm
980
980
980
Depth
mm
420
420
420
1,524
Weight
Unit
kg
108 (ERHQ*W1*)110 (ERHQ*W18*)
Packed Unit
kg
120 (ERHQ*W1*)122 (ERHQ*W18*)
Packing
Material
EPS
Carton
Wood
PP (Straps)
Weight
Heat Exchanger
Dimensions
Length
kg
12
12
12
mm
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
Nr of Rows
Fin Pitch
Nr of Passes
Face Area
Nr of Stages
60
Tube type
Fin
Hi-XSS(8)
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
Discharge direction
Motor
2
2
Horizontal
Quantity
Model
• AlthermaTM • Outdoor units
2
2
2
Brushless DC motor
55
• Outdoor units • ERHQ011-016AAW1
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Motor
Speed (nominal)
ERHQ011AAW1
ERHQ014AAW1
8
8
8
rpm
760
760
760
Cooling
rpm
780
780
780
Output
W
70
70
70
Steps
Heating
2
2
Fan
Motor
Drive
Compressor
Direct drive
Quantity
Motor
1
1
Model
JT1G-VDYR@S
Type
Hermetically sealed scroll compressor
Motor Output W
1
2,200
Starting Method
Inverter driven
Motor
Crankcase Heater
Output
W
33
33
33
Operation Range
Heating
Min
°CWB
-20
-20
-20
Max
°CWB
35
35
35
Min
°CDB
10
10
10
Max
°CDB
46
46
46
Min
°CDB
-20
-20
-20
Max
°CDB
43
43
43
Sound Power dBA
64
64
66
Sound
Pressure
51
51
52
Cooling
Sanitary water
Sound Level
(nominal)
Heating
Cooling
Sound Level (Night
quiet)
Refrigerant
dBA
Sound Power dBA
64
66
69
Sound
Pressure
dBA
50
52
54
Heating
Sound
Pressure
dBA
42
42
43
Cooling
Sound
Pressure
dBA
45
45
46
Type
R-410A
Charge
kg
2.95
Control
Refrigerant Oil
Type
Piping connections
Liquid (OD)
1
l
Quantity
Diameter
(OD)
1
1.0
1.0
1
1
1
Flare connection
mm
Quantity
9,52
1
Type
Diameter
(OD)
mm
Quantity
Diameter
(OD)
1
1
Flare connection
15,9
3
Type
3
3
Hole
mm
Quantity
26
1
Type
Piping Length
1
1.0
Type
Drain
2.95
Daphne FVC68D
Charged Volume
Gas
2.95
Expansion valve(electronic type)
Nr of Circuits
26
26
1
1
Hole
Diameter
(OD)
mm
18
18
18
Minimum
m
5
5
5
Maximum
m
75
75
75
Equivalent
m
95
95
95
Chargeless
m
10
10
10
Additional Refrigerant Charge
kg/m
Installation height
difference
m
Maximum
Heat Insulation
See installation manual outdoor unit 4PW42025-1
30
30
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
56
ERHQ016AAW1
Inverter controlled
• AlthermaTM • Outdoor units
30
• Outdoor units • ERHQ011-016AAW1
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
ERHQ011AAW1
Safety Devices
ERHQ014AAW1
ERHQ016AAW1
High pressure switch
Fan motor thermal protector
Fuse
Standard
Accessories
Item
Tie-wraps
Quantity
2
2
Item
2
Installation manual
Quantity
1
Notes
1
2
2
1
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Down to 3m with recharging of the outdoor unit. Refer to the installation manual of the outdoor unit.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (
Conditions: Ta 35°C - LWE 7°C ( DT = 5°C)
2-3
ELECTRICAL SPECIFICATIONS
Power Supply
ERHQ011AAW1
Name
3N~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Nominal running
current (RLA)
Heating (A)
A
Maximum running
Current
Heating
A
Cooling
A
Recomended fuses
Wiring connections
ERHQ016AAW1
W1
Phase
Current
ERHQ014AAW1
A
5.8
5.8
13.5 (ERHQ*W1*) / 14 (ERHQ*W18*)
13.5 (ERHQ*W1*) / 14 (ERHQ*W18*)
20
20
For Power Supply
Remark
See installation manual outdoor unit 4PW42025-1
For connection with
indoor
Remark
See installation manual outdoor unit 4PW42025-1
Power Supply Intake
5.8
20
Outdoor unit only
Notes
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
• AlthermaTM • Outdoor units
57
• Outdoor units • ERHQ011-016AAW1
3
Capacity tables
3-1
Heating capacity tables
ERHQ011-016AAW1
Maximum Heating Capacity (Peak values)
Model
2
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW57912-1A
SYMBOLS
CC
HC
PI
LWE
LWC
Tamb
58
NOTES
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Outdoor units
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For ERHQ011-16AAW1 models only: if Tamb < 4°C: bottom plate heater power input to be added = 95 W
• Outdoor units • ERHQ011-016AAW1
3
Capacity tables
3-2
Cooling capacity tables
ERHQ011-016AAW1
Maximum Cooling Capacity
Model
Tamb
LWE [°C]
20
CC [kW]
25
PI [kW]
CC [kW]
30
PI [kW]
CC [kW]
35
PI [kW]
CC [kW]
40
PI [kW]
CC [kW]
45
PI [kW]
CC [kW]
PI [kW]
2
3
3TW57912-1A
NOTES
SYMBOLS
CC
HC
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Outdoor units
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For ERHQ011-16AAW1 models only: if Tamb < 4°C: bottom plate heater power
input to be added = 95 W
59
• Outdoor units • ERHQ011-016AAW1
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
ERHQ011-016AAW1
1.
2.
3.
4.
5.
6.
7.
8.
Hole for anchor bolt 4-M12
2
Gas pipe connection J15.9 flare
Liquid connection pipe "9.5 flare
Service port (in the unit)
Electronic connection and grounding terminal MS (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock hole J34)
Control wiring intake (knock hole J27)
Drain outlet
4
4TW57914-1
60
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAW1
4
Dimensional drawing & centre of gravity
4-2
Centre of gravity
ERHQ011-016
2
4
4TW57919-5
• AlthermaTM • Outdoor units
61
• Outdoor units • ERHQ011-016AAW1
5
Piping diagram
ERHQ011-016AAW1
2
5
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
Y1S
Y3S
S1PH
M*F
M*C
: Thermistor (Air)
: Thermistor (discharge)
: Thermistor (Suction)
: Thermistor (Liquid 1)
: Thermistor (middle)
: Thermistor (Liquid 2)
: Pressure sensor
:
: Crankcase heater
: 4-way valve
: Injection valve
: High pressure switch
: Fan motor
:Compressor
filter (strainer)
filter (strainer)
Heat exchanger
Distributor
Capillary tube
Service port
5/16″
Field piping J 9.5 C 1220T-0
Field piping J15.9 C 1220T-0
Accumulator
Indoor unit
Outdoor unit
Stop valve
(with service port 5/16’ flare)
62
• AlthermaTM • Outdoor units
Heating
Cooling
3TW57915-1A
• Outdoor units • ERHQ011-016AAW1
6
Wiring diagram
6-1
Wiring diagram
ERHQ011-016AAW1
EKBPHT16Y
Only for
*RHQ01*AAW1
Power supply
3N∼
400V
50Hz
Only for *RHQ01*AAW18
Indoor
Outdoor
Reactor terminal position
Note: 4
Notes:
1 This wiring diagram only applies to the outdoor unit
2 L: Live, N: Neutral, g: Field wiring
3 D : Terminal strip
F : Connector
GM: Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 Refer to the option manual, for connecting wiring to x6A and X77A
5 Refer to the ’wiring diagram sticker’ (on the back of front plate) on how to
use BS1-BS4 and DS1 switch.
6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG:
orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service
manual.
Factory setting of all switches: ’Off’
9
: Option
: Wiring dependent on model
Compressor
terminal position
A1P
A2P
A3P
BS1∼BS4
C1∼C4
DS1
E1HC
E1H
F1U
F2U
F3U
F4U
F5U
F6U
F7U
F8U, F9U
HAP (A1P)
HAP (A2P)
H1P∼7P (A1P)
K1M-K2M
K1R (A1P)
K1R (A2P)
K2R (A1P)
K3R (A1P)
L1R∼L3R
L4R
M1C
M1F
M2F
PS
R1∼R4
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1PH
V1R∼V2R
V3R
X1M
Y1E
Y1S
Y3S
Z1C∼Z9C
Z1F∼Z4F
Q1DI
Optional connector
X6A
X77A
X1Y
Printed circuit board
Printed circuit board (INV)
Printed circuit board (Noise filter)
Push button switch
Capacitor
DIP switch
Crankcase heater
Bottomplate heater
Fuse (31.5A 500V)
Fuse (31.5A 500V)
Fuse (T 6.3A / 250V)
Fuse (T 6.3A / 250V)
Fuse (T 6.3A / 250V)
Fuse (T 6.3A / 250V)
Fuse (T 5.0A / 250V)
Fuse (F 1.0A / 250V)
Pilot lamp (Service monitor-green)
Pilot lamp (Service monitor-green)
Pilot lamp (Service monitor-orange)
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay
Magnetic relay (Y2S)
Magnetic relay (E1HC)
Reactor
Reactor (For outdoor fan motor)
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (Heat exchanger middle)
Thermistor (liquid)
Thermistor (Fin)
Pressure sensor
Pressure switch (high)
Power module
Diode module
Terminal strip
Electronic expansion valve
Solenoid valve (4 way valve)
Solenoid valve
Noise filter
Noise filter
Earth leakage protector
2
6
Connector
Connector
Connector
Reactor box A
El. comp. Assy Front
arrow A
arrow B
2TW57916-1C
• AlthermaTM • Outdoor units
63
• Outdoor units • ERHQ011-016AAW1
7
Sound data
7-1
Sound pressure spectrum
ERHQ016AAW1*
HEATING
Sound pressure level (dB)
7
ERHQ014AAW1*
HEATING
Sound pressure level (dB)
2
Sound pressure level (dB)
ERHQ011AAW1*
HEATING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW57919-2
ERHQ016AAW1*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ014AAW1*
COOLING
Sound pressure level (dB)
ERHQ011AAW1*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW57919-1
64
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAW1
7
Sound data
7-2
Sound pressure night quiet mode
ERHQ016AAW1*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ014AAW1*
HEATING
Sound pressure level (dB)
ERHQ011AAW1*
HEATING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
2
7
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW57919-4
ERHQ016AAW1*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ014AAW1*
COOLING
Sound pressure level (dB)
ERHQ011AAW1*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW57919-3
• AlthermaTM • Outdoor units
65
• Outdoor units • ERHQ011-016AAW1
8
Installation
8-1
Service space
ERHQ011-016
A. Non stacked installation
Legend
2
Unit: mm
Suction side obstacle
8
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
66
• AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAW1
9
Operation range
ERHQ011-016AAW1
Outdoor temp. (°CDB)
2
Cooling mode
9
Leaving evaporator
Water temperature (°C)
6
Outdoor temp. (°CDB)
Units with optional back up heater
Heating mode
operation possible, but no guarantee of capacity
(if outdoor temperature < -25°C unit will stop)
ERHQ_W18 units include special equipment (insulation heater sheet, à) to
ensure good operation in areas where low ambient temperature can
occur together with high humidity conditions. In such conditions the
ERHQ_W1 models may experience problems with severe ice build up on
the aircooled coil. In case such conditions are expected, the ERHQ-W18
must be installed instead. These models contain countermeasures
(insulation, heater sheet, à) to prevent freeze up.
leaving condensor
Water temperature (°C)
Domestic hot water mode
Outdoor temp. (°CDB)
Booster heater operation only
Water temperature domestic hot
water tank (C°)
4TW57913-1A
• AlthermaTM • Outdoor units
67
• Indoor units • EKHBH-X016AB
TABLE OF CONTENTS
EKHBH-X016AB
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
72
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
74
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 75
Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
77
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
Drainage instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
8
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
81
9
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
7
Static pressure drop unit
• AlthermaTM • Indoor units
79
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
69
• Indoor units • EKHBH-X016AB
1
t B i A n6 1u a 0 m X r r - o e H o h B d tH nKl E•IA
Features
Large capacity indoor unit
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
2
1
70
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X016AB
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
EKHBH016AB
Outdoor units
ERHQ16AAV3
Nominal input (Indoor only)
Casing
Colour
Dimensions
Packing
W
230
2
Epoxy polyester painted galvanised steel
Unit
Packing
230
RAL9010
Material
Weight
EKHBX016AB
Height
mm
1,225
Width
mm
660
Depth
mm
610
610
Height
mm
922
922
660
Width
mm
502
502
Depth
mm
361
361
Unit
kg
55
55
Packed Unit
kg
65
65
Material
2
EPS
Wood
Carton
PP (Straps)
Weight
kg
Main components
Pump
Pump
Nominal ESP unit
Heating
kPa
Cooling
kPa
Main components
Pump
Power input
W
Water side Heat
exchanger
Type
10
Type
Nr. of speed
2
2
35.0
35.0
46.8
210
1
1
1.01
1.01
l/min
16
16
45.9
45.9
Water volume l
Water side Heat
exchanger
Water flow rate Nom. Heating
l/min
Cooling
l/min
Main components
Water side Heat
exchanger
Water flow
rate Max.
l/min
37.6
58
Insulation material
Expansion vessel
Water filter
Polyurethane foam
l
10
10
Max. water
pressure
bar
3
3
Pre pressure
bar
1
1
Diameter
perforations
mm
1
1
Piping connections diameter
Brass
inch
Piping
inch
Safety valve
bar
G 1-1/4 (MALE)
1-1/4’’
3
3
Manometer
Yes
Drain valve / Fill valve
Yes
Shut off valve
Yes
Air purge valve
Refrigerant Circuit
58
Volume
Material
Water circuit
210
Brazed plate
Qty
Water flow
rate Min.
10
Water cooled
Yes
Total water volume (6)
l
5,5
Gas side diameter
mm
15,9
Liquid side diameter
mm
Sound level
Sound Pressure
dBA
Operation range
Ambient
Heating
Cooling
°C
Waterside
Heating
°C
Cooling
°C
°C
• AlthermaTM • Indoor units
9,52
28
28
-20~35
10-46
15-55
5-22
71
• Indoor units • EKHBH-X016AB
2
2-2
Specifications
ELECTRICAL SPECIFICATIONS
Electric heater
Type
EKHBX016AB
3V3
Power Supply
Phase
1~
Frequency
Hz
50
50
Voltage
V
230
230
Current back-up
heater
Running
Current
A
13
13
Current back-up
heater + booster
heater (EKHWS*
models)
Z-max
Text
Running Current
*V3
Minimum Ssc value
*V3
Electric heater
Voltage range
Minimum
-10%
Maximum
+10%
2
2
Wiring connections
Electric heater
For power supply
backup heater
0.29
A
0.29
26 (13+13)
Equipment complying with EN/IEC 61000-3-12 **
Quantity of wires
Type of wires
3G
Select diameter and type according to national and local regulations
Type
6V3
Power Supply
Phase
1~
Frequency
Hz
50
50
Voltage
V
230
230
Current back-up
heater
Running
Current
A
26
26
Current back-up
heater
Z-max
Text
0.29
0.29
Electric heater
Current back-up
heater
Minimum Ssc value
Current back-up
heater + booster
heater (EKHWS*
models)
Z-max
Text
Running Current
*V3
Minimum Ssc value
*V3
Electric heater
Voltage range
Minimum
-10%
Maximum
+10%
Wiring connections
Electric heater
For power supply
backup heater
Running Current
Electric heater
Voltage range
0.17
39 (26+13)
Equipment complying with EN/IEC 61000-3-12 **
3G
Select diameter and type according to national and local regulations
Type
Current back-up
heater + booster
heater (EKHWS*
models)
Electric heater
0.17
A
Type of wires
6WN
Phase
Current back-up
heater
Wiring connections
Equipment complying with EN/IEC 61000-3-12 **
Quantity of wires
Power Supply
Minimum Ssc value
For power supply
backup heater
3~
Frequency
Hz
50
50
Voltage
V
400
400
Running
Current
A
8.7
8.7
*V3
A
21,7 (8.7+13)
*Z2
A
16.2 (8.7+7.5)
*V3
Equipment complying with EN/IEC 61000-3-12 **
*Z2
Equipment complying with EN/IEC 61000-3-12 **
Minimum
-10%
Maximum
+10%
Quantity of wires
Type of wires
4G
Select diameter and type according to national and local regulations
Type
6T1
Power Supply
Phase
3~
Frequency
Hz
50
50
Voltage
V
230
230
Current back-up
heater
Running
Current
A
15.1
15.1
Current back-up
heater + booster
heater (EKHWS*
models)
Running Current
*V3
A
Minimum Ssc value
*V3
Electric heater
Voltage range
Minimum
-10%
Maximum
+10%
Wiring connections
72
EKHBH016AB
For power supply
backup heater
Quantity of wires
Type of wires
• AlthermaTM • Indoor units
26.1 (15.1+13)
Equipment complying with EN/IEC 61000-3-12 **
4G
Select diameter and type according to national and local regulations
• Indoor units • EKHBH-X016AB
2
2-2
Specifications
ELECTRICAL SPECIFICATIONS
Electric heater
EKHBH016AB
Type
EKHBX016AB
9WN
Power Supply
Phase
3~
Frequency
Hz
50
50
Voltage
V
400
400
Current back-up
heater
Running
Current
A
13
13
Current back-up
heater + booster
heater (EKHWS*
models)
Running Current
*V3
A
*Z2
A
Electric heater
Voltage range
Wiring connections
Electric heater
Minimum Ssc value
For power supply
backup heater
20.5 (13+7.5)
*V3
Equipment complying with EN/IEC 61000-3-12 **
*Z2
Equipment complying with EN/IEC 61000-3-12 **
Minimum
-10%
Maximum
+10%
4G
Type of wires
Select diameter and type according to national and local regulations
Type
9T1
Phase
Current back-up
heater
3~
Frequency
Hz
50
50
Voltage
V
230
230
Running
Current
A
22.6
22.6
Minimum Ssc value
Current back-up heater Running Current
+ booster heater
Minimum Ssc value
(EKHWS* models)
Wiring connections
Voltage range
For power supply
backup heater
*V3
Equipment complying with EN/IEC 61000-3-12 **
A
35.6 (22.6+13)
*V3
Equipment complying with EN/IEC 61000-3-12 **
Minimum
-10%
Maximum
+10%
Quantity of wires
4G
Type of wires
Select diameter and type according to national and local regulations
Connection type
For power supply connection to Optional Warm Water Tank + Q2L
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details of the voltage range and current refer to installation manual EKHBH/X016AB*
Connection type
For connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
For connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual EKHBH/X016AB*
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Connection type
For connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Connection type
For connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Notes
2
26 (13+13)
Quantity of wires
Power Supply
Electric heater
2
Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Above mentioned power supply of the hydro box is for the backup heater only. The Switch box &
pump of the hydrobox are supplied via the outdoor unit. The optional domestic warm water tank
has a separate power supply.
Optional electric heater has 2 capacity steps except for the 3V3 model which has only 1 capacity
step.
In accordance with EN/IEC 61000-3-11(*), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys(***) <= Zmax
(*) European/International Technical Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A
(**) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current >16A and <= 75A per phase
(***) System impedance
• AlthermaTM • Indoor units
73
• Indoor units • EKHBH-X016AB
3
Options
Factory mounted optional equipment for EKHB(H/X)016AB**
Reference
2
3
Description
Heating only model EKHBH016A...
Reversible model EKHBX016A...
Back up heater 3kW 1∼230 V
Back up heater 6kW 1∼230 V
Back up heater 6kW 3∼400 V
Back up heater 6kW 3∼230 V
Back up heater 9kW 3∼400 V
Back up heater 9kW 3∼230 V
3V3
6V3
6WN
6T1
9WN
9T1
B3V3
B3V3
V
⎯
⎯
⎯
⎯
⎯
V
⎯
⎯
⎯
⎯
⎯
B6V3
B6V3
⎯
V
⎯
⎯
⎯
⎯
⎯
V
⎯
⎯
⎯
⎯
B6WN
⎯
⎯
V
⎯
⎯
⎯
B6T1
B6WN
⎯
⎯
V
⎯
⎯
⎯
⎯
⎯
⎯
V
⎯
⎯
B9WN
B6T1
⎯
⎯
⎯
V
⎯
⎯
B9WN
⎯
⎯
⎯
⎯
V
⎯
⎯
⎯
⎯
⎯
V
⎯
B9T1
B9T1
⎯
⎯
⎯
⎯
⎯
V
⎯
⎯
⎯
⎯
⎯
V
Outdoor combination table for EKHB(H/X)016AB**
EKHBH016AB*
EKHBX016AB*
Note:
ERHQ(W18/V38) units include special equipment (insulation heater
sheet, ...) to ensure good operation in areas where low ambient
temperature can occur together with high humidity conditions. In
such conditions the ERHQ(W1/V3) models may experience
problems with severe ice build up on the aircooled coil. In case such
conditions are expected, the ERHQ(W18/V38) must be installed
instead. These models contain countermeasures (insulation, heater
sheet, ...) to prevent freeze up.
ERHQ011AA(V3*/W1*)
ERHQ014AA(V3*/W1*)
ERHQ016AA(V3*/W1*)
V
V
V
V
V
V
ERHQ011AA(V3/W1)
ERHQ014AA(V38/W18)
ERHQ014AA(V3/W1)
ERHQ014AA(V38/W18)
ERHQ016AA(V3/W1)
ERHQ016AA(V38/W38)
V
V
-
V
V
-
V
V
-
Heating only indoor unit
Reversible indoor unit
Kit availability for ERHQ011-016AA**
EKBPHT16Y
EKDK04
Bottom plate heater (2)
drain plug kit (2)
Kit availability for EKHB(H/X)016AB*
Reference
Description
EKHWS150(A/B)3V3
EKHWS200(A/)B3V3
EKHWS300(A/B)3V3
EKHWS200(A/B)3Z2
EKHWS300(A/B)3Z2
EKHWSU150(A/B)3V3
EKHWSU200(A/B)3V3
EKHWSU300(A/B)3V3
EKHWE150A3V3
EKHWET150A3V3
EKHWE200A3V3
EKHWE300A3V3
EKHWE200A3Z2
EKHWE300A3Z2
EKHBDP
EKRP1HB
EKRTW
EKRTR
EKRTETS
Heating only model EKHBH016A...
Reversible model EKHBX016A...
Stainless domestic hot water tank 150l 1-230V
Stainless domestic hot water tank 200l 1-230V
Stainless domestic hot water tank 300l 1-230V
Stainless domestic hot water tank 200l 2-400V
Stainless domestic hot water tank 300l 2-400V
Stainless domestic hot water tank 150l 1-230V
Stainless domestic hot water tank 200l 1-230V
Stainless domestic hot water tank 300l 1-230V
Enamel domestic hot water tank 150l 1-230V
B3V3
B3V3
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Wallmounted enamel domestic hot water tank 150l 1-230V
Enamel domestic hot water tank 200l 1-230V
Enamel domestic hot water tank 300l 1-230V
Enamel domestic hot water tank 200l 2-400V
Enamel domestic hot water tank 300l 2-400V
Option kit for condensate free cooling operation
Digital I/O PCB (1)
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
B6V3
V
V
V
V
V
V
V
V
V
V
V
V
V
V
B6V3
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
B6WN
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
V(*)
V(*)
V(*)
V
V
V
V
V
V
B6WN
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
V(*)
V(*)
V(*)
V
V
V
V
V
V
V
B6T1
V
V
V
V
V
V
V
V
V
V
V
V
V
V
B6T1
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
B9WN
B9WN
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
V(*)
V(*)
V(*)
V
V
V
V
V
V
V
V (*)
V (*)
V (*)
V
V
V (*)
V (*)
V (*)
V(*)
V(*)
V(*)
V(*)
V
V
V
V
V
V
B9T1
V
V
V
V
V
V
V
V
V
V
V
V
V
V
B9T1
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
(*) If neutral line is available
Kit available for EKHWS*
Reference
EKUHWA
EKUHWB
EKUHW2WB
EKSOLHWAV1
EKWBSWW150
Description
EKHWE(T)*3(V3/Z2)
EKHWS*3(V3/Z2)
EKHWSU*3V3
Option kit for UK EKHWSU150-300V3
Option kit 1 for UK EKHWSU150-300V3 (7)
Option kit 2 for UK EKHWSU150-300V3 (7)
Solarkit (5)
Wall bracket for EKHWS(U)150(A/B)3V3 or EKSWW150V3
150A
200A
300A
V
V
V
-
V
-
150(A/B)
200(A/B)
300(A/B)
V
V
V
-
V
-
150A
V
V(5)
V(5)
V
V
200A
V
V(5)
V(5)
V
-
300A
V
V(5)
V(5)
V
-
150B
V
V
V(6)
V
V
200B
V
V
V(6)
V
-
300B
V
V
V(6)
V
-
Remarks: Other combinations than mentioned in this option TW are not guaranteed.
(1) Address card that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included.
(2) It is not allowed to combine bottom plate heater and drain plug/stop kit
(3) EKRTETS can only be used in combination with EKRTR
(4) Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
(5) If installation on tank A version both kits are required
(6) Kit is only necessary when installing EKSOLHWAV1 on a UK tank B-series (EKHWSU(150/200/300)B3V3
(7) EKUHWB = EKUHWA -(Kit is only necessary when installing EKSOLHWAV1 on a UK tank B-series)
EKUHW2WB = 2 way valve and 2 way valve accessories
3TW57819-2C
74
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X016AB
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKHBH016AB
FIXATION
2
4
Service door
(Closed) 361
(Open) 553
1-1/4″ Male BSP
View A
Scale 1/5
Dimensions
wallbracket
Minimum space for service & ventilation
Min. 150
Min. 200
Center of gravity
j
1 Pump + switch for speed setting
j
2 Remocon
j
3 Water IN connection: 1 1/4’’ M BSP
j
4 Water OUT connection: 1 1/4’’ M BSP
j
5 Power supply intake (+ sanitary warm water tank)
j
6 Air purge
j
7 Expansion vessel+j
7A nipple+j
7B Drain
j
8 Blow off valve
j
9 Blow off drain (flexible hose J20)
j
10 Pressure gauge
j
11 Water filter
j
12 Suction pipe connection J15.9 flare connection
j
13 Liquid pipe connection J9.52 flare connection
j
14 Shut off valves with drain/fill valve (accessory
delivered with unit)
j
15 Holes for fixation
j
16 Switchbox terminals
j
17 Switchbox terminals option sanitary warm water
tank
j
18 Wallbracket
3TW57754-1A
EKHBX016AB
FIXATION
Service door
(Closed) 361
(Open) 553
1-1/4″ Male BSP
View A
Scale 1/5
Dimensions
wallbracket
Minimum space for service & ventilation
Min. 150
Min. 200
Center of gravity
j
1 Pump + switch for speed setting
j
2 Remocon
j
3 Water IN connection: 1 1/4’’ M BSP
j
4 Water OUT connection: 1 1/4’’ M BSP
j
5 Power supply intake (+ sanitary warm water tank)
j
6 Air purge
j
7 Expansion vessel+j
7A nipple+j
7B Drain
j
8 Blow off valve
j
9 Blow off drain (flexible hose J20)
j
10 Pressure gauge
j
11 Water filter
j
12 Suction pipe connection J15.9 flare connection
j
13 Liquid pipe connection J9.52 flare connection
j
14 Shut off valves with drain/fill valve (accessory
delivered with unit)
j
15 Holes for fixation
j
16 Switchbox terminals
j
17 Switchbox terminals option sanitary warm water
tank
j
18 Wallbracket
• AlthermaTM • Indoor units
Dimensions wallbracket Scale 1/5
3TW57754-2A
75
• Indoor units • EKHBH-X016AB
5
Piping diagram
EKHBH(X)016AB
Water Site
Expansion
Vessel
Pressure
Gauge
2
5
Drain
Safety
Valve
Flowswitch
Evaporator
Condensor
Air
Purge
Blow Off
Field Installation
R2T
Refriferant
Side
R1T
Pump
Refr. Out
Water Outlet
Refr. In
Electric
Heater Body
Shut Off Valve
With Drain/Fill Valve
Plate
Heat
Exchanger
R3T
Field Installation
R4T
Filter
Refr. In
Water Inlet
Refr. Out
Shut Off Valve
With Drain/Fill Valve
Check Valve
Cooling (EKHBX)
Heating (EKHBX + EKHBH)
Flare Conn.
Screw Conn.
Flange Conn.
Pinched Pipe
Spinned Pipe
R4T
R3T
R2T
R1T
Thermistor
Inlet water Thermistor
Refrigerant Liquid Side Thermistor
Outlet Water Backup heater Thermistor
Outlet Water Heat-exchanger Thermistor
Description
3TW57755-1
76
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X016AB
6
Wiring diagram
6-1
Wiring diagram
EKHBH(X)016AB3V3
Only for EKSOLHWAV1
Option
Outdoor unit
Power supply
230V 1N∼50Hz
Domestic hot water
tank
Solar pump connection
>> See note 2 <<
Only
for *EKHWE* Option
See note 9
Only
for *EKHW(S/E) Option
See note 7
For EKHWSU*V3
Option
2
User interface
6
Only
for EKRTW Option
Solar input
Alarm output
Cooling/heating
on/off output
Only for EKHW Option
heating
cooling
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
230V AC
supply from PCB
Domestic hot water
Only for EKRTROption
3 wire type (SPST)
tank
Only forEKHW*V3
Option
Only for EKHW Option
NO valve
Only for EKSOLHWAV1
Option
Only
for EKHW(S/E) Option
See note 7
For EKHWSU*V3 Option
Electric heater fuse
20A
F1B
Only for EKRTWOption
Example
field supply
thermostat
NC valve
F2B
EKHW kit fuse
20A
X1M-X9M
V1S, V2S
FU1
FU2
FuS, FuR
Q1DI
Q2L
Q1L
S1S
SS1
TR1
R5T
R4T
R3T
R2T
R2T (EKRTETS)
R1T
R1H (EKRTR)
R1T (EKRTW/R)
S1L
E4H
E1H
M3S
M2S
M1P
PHC1
K5M
: Terminal strips
: Spark suppression 1,2
: Fuse 3.15A T 250V
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Earth leakage protector
: Thermal protector booster heater
: Thermal protector backup heater
: Solar pumpstation relay
: DIP switch
: Transformer 24V for PCB
: Domestic hot water thermistor
: Inlet water thermistor
: Refrigerant liquid side thermistor
: Outlet water backup heater thermistor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Humidity sensor
: Ambient sensor
: Flowswitch
: Booster heater (3kW)
: Backup heater element 1
: 3way valve: floorheating/domestic hot water
: 2 way valve for cooling mode
: Pump
: Optocoupler input circuit
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
K4M
: Pump Relay
K3M
: Contactor booster heater
K1M
: Contactor backup heater step 1
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse Back up heater
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
Notes:
1
2
3
4
5
6
7
8
9
Domestic hot water
tank
Only forEKHW*V3
Option
Wiring dependent
on model
Option
Field wiring
PCB
Wire colour
Field wiring
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow / BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For EKHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (L,N)
For EKSOLHWAV1, refer to option manual
3TW57816-2B
EKHBH(X)016AB6V3
Outdoor unit
Power supply
230V 1N∼50Hz
>> See note 2 <<
Only
for EKSOLHWAV1
Option
Solar pump connection
Domestic hot water
tank
Only
See note 9
for EKHW*V3 Option
User
interface
Only for EKHW
Option
Only forEKRTW
Option
Solar input
Cooling/heating
on/off output
Alarm output
See note 7
For EKHWSU*V3
Option
Only for EKRP1HB &
EKSOLWAV1
Option
230V AC
supply from PCB
See note 8
Only forEKRTR
Option
Domestic hot water
tank
Only for EKHW*V3
Option
3 wire type
(SPST)
Only for EKHW*
Option
NO valve
Only for EKSOLWAV*
Option
Only for EKHW Option
See note 7
For EKHWSU*V3 Option
Wiring
dependent on
model
Field wiring
F1B
Only forEKRTETS
Option
Example field
supply
thermostat
Option
Field wiring
Wire
colour
NC valve
F2B
Electric heater fuse
32A
EKHW kit fuse
20A
X1M-X9M
: Terminal strips
V2S
: Spark suppression 2
V1S
: Spark suppression 1
FU1
: Fuse 3.15A T 250V
FU2
: Fuse 5A T 250V
FuS, FuR
: Fuse 5A 250V for solar/remote alarm PCB
Q1DI
: Earth leakage protector
Q2L
: Thermal protector 1/2 Booster heater
Q1L
: Thermal protector backup heater
S1S
: Solar pumpstation relay
SS1
: DIP switch
R5T
: Domestic hot water thermistor
R4T
: Inlet water thermistor
R3T
: Refrigerant liquid side thermistor
R2T (EKRTETS) : External sensor (floor or ambient)
R2T
: Outlet water backup heater thermistor
R1H (EKRTW/R) : Ambient sensor
R1T
: Outlet water heat-exchanger thermistor
R1H (EKRTR) : Humidity sensor
S1L
: Flowswitch
E4H
: Booster heater (3kW)
E1H-E2H
: Backup heater element 1-2
M3S
: 3way valve: floorheating/domestic hot water
M2S
: 2 way valve for cooling mode
M1P
: Pump
PHC1
: Optocoupler input circuit
K5M
: Contactor for backup heater all-pole disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M/K2M
: Contactor backup heater step 1/2
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse Back up heater
E4H
: Booster heater
E1H-E3H
: Backup heater element 1-2
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
Domestic hot
water tank
Only for EKHW*V3
Option
Notes:
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit.
9 For EKSOLHWAV1, refer to option manual
• AlthermaTM • Indoor units
3TW57816-3B
77
• Indoor units • EKHBH-X016AB
6
Wiring diagram
6-1
Wiring diagram
EKHBH(X)016AB6T1/9T1
Power supply
Only for EKSOLHWAV1
Option
Outdoor unit
Domestic hot water
Solar pump connection
tank
>> See note 2 <<
See note 9
Only for EKHW*V3 Option
See note 7
For EKHWSU*V3
Option
2
User interface
Only for EKHW
Option
Only forEKRTW
Option
Solar input
Cooling/heating
on/off output
Alarm output
6
Only for EKRP1HB &
EKSOLWAV1
Option
230V AC
supply from PCB
See note 8
Only for EKRTR
Option
Domestic hot water
tank
3 wire type
(SPST)
Only for EKHW*V3
Option
Only for EKHW*
Option
NO valve
Only for EKSOLWAV*
Option
Only for EKHW Option
See note 7
For EKHWSU*V3 Option
Option
Field wiring
Field wiring
Example field
supply thermostat
NC valve
Wire
colour
Electric heater fuse
6T1
20A
Model
F1B
Only for EKRTETS
Option
Wiring
dependent on
model
F2B
9T1
32A
EKHW kit fuse
20A
X1M-X9M
: Terminal strips
V2S
: Spark suppression 2
V1S
: Spark suppression 1
FU1
: Fuse 3.15A T 250V
FU2
: Fuse 5A T 250V
FuS, FuR
: Fuse 5A 250V for solar/remote alarm PCB
Q1DI
: Earth leakage protector
Q2L/Q3L
: Thermal protector 1/2 Booster heater
Q1L
: Thermal protector backup heater
S1S
: Solar pumpstation relay
SS1
: DIP switch
R5T
: Domestic hot water thermistor
R4T
: Inlet water thermistor
R3T
: Refrigerant liquid side thermistor
R2T (EKRTETS) : External sensor (floor or ambient)
R2T
: Outlet water backup heater thermistor
R1H (EKRTW/R) : Ambient sensor
R1T
: Outlet water heat-exchanger thermistor
R1H (EKRTR) : Humidity sensor
S1L
: Flowswitch
E4H
: Booster heater (3kW)
E1H-E3H
: Backup heater element 1-3
M3S
: 3way valve: floorheating/domestic hot water
M2S
: 2 way valve for cooling mode
M1P
: Pump
PHC1
: Optocoupler input circuit
K5M
: Contactor for backup heater all-pole disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M/K2M
: Contactor backup heater step 1/2
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse Back up heater
E4H
: Booster heater
E1H-E3H
: Backup heater element 1-3
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
Domestic hot
water tank
Only for EKHW*V3
Option
Notes:
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit.
9 For EKSOLHWAV1, refer to option manual
EKHBH(X)016AB6WN/9WN
Power supply
230V 1N∼50Hz
>> See note 2 <<
Outdoor unit
Only
for EKSOLHWAV1
Option
3TW57816-6B
Domestic hot water
Solar pump connection
Domestic hot water
tank
tank
Only
See note 9
for EKHW*V3 Option
Cooling/heating
on/off output
Only
for EKHW*V3 Option
User
interface
Only for EKHW
Option
Only forEKRTW
Option
Solar input
Alarm output
See note 7
For EKHWSU*V3
Option
230V AC
Only for EKRP1HB &
EKSOLWAV1
Option
supply from PCB
See note 8
Domestic hot water
tank
Only for EKHW*V3 Option
Only forEKRTR
Option
Domestic hot water
tank
3 wire type
(SPST)
Only for
EKHW*Option
NO valve
Only for EKHW Option
Only forEKHW*Z2 Option
See note 7
For EKHWSU*V3 Option
Wiring
dependent on
model
Field wiring
Domestic hot
water tank
Only for EKHW*V3 Option
Model
F1B
Only for EKRTETS
Option
Example field
supply
thermostat
Option
Field wiring
Wire
colour
NC valve
F2B
Only for EKSOLWAV*
Option
Electric heater fuse
6WN
16A
EKHW kit fuse
20A
9WN
20A
X1M-X9M
: Terminal strips
V2S
: Spark suppression 2
V1S
: Spark suppression 1
FU1
: Fuse 3.15A T 250V
FU2
: Fuse 5A T 250V
FuS, FuR
: Fuse 5A 250V for solar/remote alarm PCB
Q1DI
: Earth leakage protector
Q2L/Q3L
: Thermal protector 1/2 Booster heater
Q1L
: Thermal protector backup heater
S1S
: Solar pumpstation relay
SS1
: DIP switch
R5T
: Domestic hot water thermistor
R4T
: Inlet water thermistor
R3T
: Refrigerant liquid side thermistor
R2T (EKRTETS) : External sensor (floor or ambient)
R2T
: Outlet water backup heater thermistor
R1H (EKRTW/R) : Ambient sensor
R1T
: Outlet water heat-exchanger thermistor
R1H (EKRTR) : Humidity sensor
S1L
: Flowswitch
E4H
: Booster heater (3kW)
E1H-E3H
: Backup heater element 1-3
M3S
: 3way valve: floorheating/domestic hot water
M2S
: 2 way valve for cooling mode
M1P
: Pump
PHC1
: Optocoupler input circuit
K5M
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
K3M
: Contactor booster heater
K1M/K2M
: Contactor backup heater step 1/2
F2B
: Fuse booster heater
F1B
: Fuse backup heater
F1T
: Thermal fuse Back up heater
E4H
: Booster heater
E1H-E3H
: Backup heater element 1-3
A4P (EKRTR) : Receiver PCB
A4P (EKRP1HB) : Solar/remote alarm PCB
A3P
: Thermostat (PC=power circuit)
A2P
: User interface PCB
A1P
: Main PCB
Domestic hot
water tank
Only for EKHW*Z2 Option
Notes:
1
2
3
4
5
6
This wiring diagram only applies to the indoor unit.
Use one and same dedicated power supply for indoor ubit, outdoor unit and EKHW option.
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-sircuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
7 For EKHWSU*V3, refer to option manual
8 Option PCB works with an external 230V AC power supply unit.
9 For EKSOLHWAV1, refer to option manual
78
• AlthermaTM • Indoor units
3TW57816-4B
• Indoor units • EKHBH-X016AB
6
Wiring diagram
6-2
External connection diagram
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
unit power supply: 400V or 230V + earth
5 or 3 core
2
X1M:L1-L2-L3-N-Earth
Optional power supply
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Power supply (alarm indication, cooling/heating
on/off indication, solar interlock)
Bottom plate heater option
Optional power supply
X1M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
4 core
<10m: 4Gx1.5
>10m: 4Gx2.5
2 core
3 core
3 or4 core
Optional parts
6
Field supply
Only for EKBPHT
Indoor unit
Only for EKRP1HB & EKSOLHWAV1
X1M:1-2-3-Earth
1 core
Domestic hot water tank
X1M:L1-L2-L3-N-Earth
1 core
X3M:L-N-Earth
Alarm indication
Alarm output
A4P: Y2
Cooling/Heating
on/off output
2 way valve
2 core
Q3L
Clixon
A4P: Y3
Solar input
1 core
solar interlock
Only for EKHWSU*V3
Power supply booster heater
5 core
X4M:1-2-Earth
NO valve: X2M: 6-7
2 core
NC valve: X2M: 5-7
Q2L - Clixon booster heater
R5T - Thermistor water
temperature
Cooling/Heating
on/off indication
1 core
2 way valve
M2S (EKHBX Units)
for cooling mode
Room thermostat
Only for field supplied room thermostat
Possibility 1
Note: min. distance to power cable * 5cm
2 core
4 core
Signal
2 core
Possibility 2
3 core for C/H application
2 core for H only application
Only for EKRTW (wired room thermostat)
Possibility 3
5 core for C/H application
4 core for H only application
Only for EKTR (wireless room
thermostat)
Q3L
Clixon
Solar pump
Only for EKSOLHWAV1
Only for EKRTETS
2 core (3m
R2T External sensor
included)
floor or ambient
3 way valve
M3S (when EKHWE is intalled) selection domestic hot
water-floorheating
3 core
User interface
Signal
3TW57786-7A
• AlthermaTM • Indoor units
79
• Indoor units • EKHBH-X016AB
7
Installation
7-1
Drainage instructions
EKHBDP
2
Leaving water temperature limit to prevent condesation
7
Relative humidity 40%
Relative humidity 60%
Relative humidity 80%
Leaving water temperature [°C]
Leaving water temperature [°C]
Maximum leaving water
temperature cooling mode
= 22°C
Example:
With ambient temperature of 25°C and
relative humidity of 40%.
If leaving water temperature is below
12°C, condensation on water piping
will happen.
Dry bulb temperature [°C]
1. Refer to psychometric chart for more information.
2. If condensation is expected, installation of EKHBDP - drainpan kit must be considered.
4TW57759-3
80
• AlthermaTM • Indoor units
• Indoor units • EKHBH-X016AB
8
Operation range
EKHBH(X)016AB
Outdoor temp. (°CDB)
2
Cooling mode
8
Leaving evaporator
Water temperature (°C)
Outdoor temp. (°CDB)
Heating mode
No heat pump operation, back up
heater only
* ERHQ_V18 units include special equipment (insulation heater sheet, ...) to
ensure good operation in areas where low ambient temperature can
occur together with high humidity conditions. In such conditions the
ERHQ_V3 models may experience problems with severe ice build up on
the aircooled coil. In case such conditions are expected, the ERHQ-V38
must be installed instead. These models contain countermeasures
(insulation, heater sheet, ...) to prevent freeze up.
leaving condensor
Water temperature (°C)
Domestic hot water mode
Outdoor temp. (°CDB)
Booster heater operation only
Water temperature domestic hot
water tank (C°)
4TW57753-1B
• AlthermaTM • Indoor units
81
• Indoor units • EKHBH-X016AB
9
Hydraulic performance
9-1
Static pressure drop unit
EKHBH(X)016
2
ESP [kPa]
9
Flow [l/min]
l high speed
ll medium speed
ESP: external static pressure
Flow: waterflow through the unit
Warning:
1. Selecting a flow outside the curves can cause damage to or
malfunction of the unit. See also minimum and maximum allowed
water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
4TW57759-1
82
• AlthermaTM • Indoor units
EEDEN09-720
technical data
AlthermaTM
Part 3/4:
EDHQ011-016AA6V3
EDHQ011-016AA6W1
EDLQ011-016AA6V3
EDLQ011-016AA6W1
EBHQ011-016AA6V3
EBHQ011-016AA6W1
EBLQ011-016AA6V3
EBLQ011-016AA6W1
• Monobloc • EDHQ011-016AA6V3
TABLE OF CONTENTS
EDHQ011-016AA6V3
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87
87
88
89
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
91
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
93
Heating capacity tables
5
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 94
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
97
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
96
98
99
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
85
• Monobloc • EDHQ011-016AA6V3
1
A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnH Dlo E•MA
Features
Heating only monobloc
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
86
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EDHQ011AA6V3
EDHQ014AA6V3
EDHQ016AA6V3
16.00
Heating capacity
Nominal
kW
11.20
14.00
Heating PI
Nominal
kW
2.47
3.20
3.79
COP
Nominal
4.54
4.37
4.22
15.06
Heating capacity
Nominal
kW
10.87
13.10
Heating PI
Nominal
kW
3.22
3.91
4.62
COP
Nominal
3.37
3.35
3.26
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EDHQ011AA6V3
Colour
Unit
Packing
Weight
Packing
2
EDHQ016AA6V3
Ivory white
Material
Dimensions
EDHQ014AA6V3
3
Painted galvanised steel
Height
mm
Width
mm
Depth
mm
Height
mm
1,418
1,435
382
382
382
1,557
Width
mm
Depth
mm
430
1,500
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Material
430
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
Min
Max
Sound Level
(nominal)
Sound Level (Night
quiet)
Refrigerant
kg
20
20
20
°CDB
-15
-15
-15
°CDB
35
35
35
Heating - Waterside Min
°C
15
15
15
Max
°C
55
55
55
Domestic hot water
-Ambient
Min
°CDB
-15
-15
-15
Max
°CDB
43
43
43
Domestic hot water
- Waterside
Min
°C
25
25
25
Max
°C
80
80
80
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
51
51
52
Sound
Pressure
dBA
42
42
43
Heating
Type
Charge
R-410A
kg
2.95
Control
Nr of Circuits
Refrigerant Oil
1
Type
Charged Volume
2.95
2.95
Electronic expansion valve
1
1
Daphne FVC68D
l
1.0
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
• AlthermaTM • Monobloc
87
• Monobloc • EDHQ011-016AA6V3
2
2-3
Specifications
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EDHQ011AA6V3
EDHQ014AA6V3
EDHQ016AA6V3
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
3
60
Tube type
Hi-XSS
Fin
2
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
Air Flow Rate
(nominal at 230V)
Heating
High
Fan
Discharge direction
Motor
m³/min
2
2
2
90
90
90
Horizontal
Quantity
2
Model
Motor
Fan
Speed (nominal)
Steps
Motor
8
8
8
rpm
760
760
760
Output
W
70
70
70
Direct drive
Quantity
1
Motor
JT100G-VD
Type
Hermetically sealed scroll compressor
Crankcase Heater
Type
Output
W
Inverter driven
33
Nominal ESP unit
Heating
Power input
Water filter
2
2
2
52.5
43.5
35.0
W
210
210
210
Type
Brazed plate
Quantity
1
1
1
1.01
1.01
1.01
Water volume
l
Water flow rate Min.
l/min
16
16
16
Water flow rate Nom. Heating
l/min
32.1
40.1
45.9
Water flow rate Max.
l/min
58
58
58
Foamed synthetic elastomer
Volume
l
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
Water circuit
10
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
Manometer
3
3
Yes
Drain valve / Fill valve
yes
Shut off valve
yes
Air purge valve
yes
Total water volume (6)
88
33
kPa
Insulation material
Expansion vessel
33
Water cooled
Nr. of speed
Water side Heat
exchanger
1
2,200
Starting Method
Pump
1
Model
Motor Output W
Motor
2
Heating
Drive
Compressor
2
Brushless DC
l
• AlthermaTM • Monobloc
5.5
5.5
5.5
• Monobloc • EDHQ011-016AA6V3
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
compressor
component
Main Power
EDHQ011AA6V3
Name
Current
Power supply
Current back-up
hydraulic component heater
Current back-up
heater
Power Supply
1
1
1
50
50
230
230
Frequency
Hz
50
Voltage
V
230
Minimum
V
Maximum
V
-10%
+10%
Minimum Ssc kVa
value
Recomended A
fuses
Wiring connections
EDHQ016AA6V3
V3
Phase
Voltage range
EDHQ014AA6V3
3
Equipment complying with EN/IEC 61000-3-12(*)
32
For power supply
compressor component
32
32
See installation manual
Type
6V3
Phase
1~
Frequency
Hz
50
50
50
Voltage
V
230
230
230
Running Current
Back-up
heater
A
26
26
26
Running Current
Back-up heater +
booster heater
+EK*V3
A
Current back-up
heater
Z-max
Back-up
heater
A
0.29
0.29
0.29
Back-up
heater +
booster
heater
A
0.17
0.17
0.17
+EK*V3
kVa
Minimum Ssc value
2
• AlthermaTM • Monobloc
39(26+13)
Equipment complying with EN/IEC 61000-3-12(**)
89
• Monobloc • EDHQ011-016AA6V3
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
Voltage range
Wiring connections
EDHQ011AA6V3
Minimum
V
Maximum
V
+10%
Connection type
for power supply hydraulic compartment
2G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EDHQ016AA6V3
-10%
Quantity of wires
3
EDHQ014AA6V3
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network operator
to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal to Zmax.
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
90
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
3
Options
EDHQ011-016AAV3
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
1-Phase
Reference
Description
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
91
• Monobloc • EDHQ011-016AA6V3
3
Options
EDHQ011-016AA6V3
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
92
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
4
Capacity tables
4-1
Heating capacity tables
EDHQ011-016AA6V3
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
93
• Monobloc • EDHQ011-016AA6V3
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EDHQ011-016AA6V3
3
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
94
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
6
Piping diagram
6-1
Piping diagram
EDHQ011-016AA6V3
Expansion
vessel
Filter
Pressure
gauge
Filter
Evaporator
Condenser
Safety valve
Heat exchanger
Distributor
3
Air purge
6
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Stop valve
(with service port 5/16’ flare)
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58015-1A
• AlthermaTM • Monobloc
95
• Monobloc • EDHQ011-016AA6V3
7
Wiring diagram
7-1
Wiring diagram
EDHQ011-016AA6V3
Power supply
A1P
A2P
A3P
A4P
BS1∼BS4
C1∼C4
DS1
E1H
E1HC
F1U, F3U, F4U
F6U
F7U, F8U
H1P∼7P (A2P)
Compressor module switchbox
N-50Hz
230V
Only for E(D/B)LO*
To hydromodule switchbox (8.5 Page 2
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Printed circuit board
Push button switch
Capacitor
DIP switch
Bottomplate heater
Crankcase heater
Fuse (T 6.3A/250V)
Fuse (T 5.0A/250V)
Fuse (F 1,0A/250V)
Light Emit. Diode (Serv. Monitor-Orange)
Prepare, Test --------- Flickering
Malfunction Detection -- Light up
Light emitting diode (service monitor green)
Magnetic relay (Y1S)
Magnetic relay (E1HC)
Magnetic relay
Magnetic relay
Reactor
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Field earth leakage breaker (300mA)
Resistor
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Signal receiver circuit
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Signal transmission circuit
Power module
Diode module
IGBT
Terminal strip (Power supply)
Electronic expansion valve
Solenoid valve (4 way valve)
Noise filter (ferrity core)
Noise filter
HAP (A1P)
K1R
K4R
K10R
K11R
L1R
M1C
M1F
M2F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
RC
R10T
S1NPH
S1PH
TC
V1R
V2R, V3R
V1T
X1M
Y1E
Y1S
Z1C∼Z3C
Z1F∼Z4F
Optional connector
X1Y
3
7
Connector
Position of
compressor
terminal
Wire entrance
Option
Wiring dependent on
model
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.
El. comp. Assy
(Position of elements)
2TW58016-1
EDHQ011-016AA6V3
Outdoor unit
Only for EC/BLQOption
Only
for EKSOLHWAV1Option
Domestic hot water
tank
Solar pump connection
Power supply
230V 1N∼50Hz
Only
for *KHWE*Option
See note 9
>> See note 2 <<
Only
for *KHW(S/E)*Option
See note 7
For *KHWSU*V3 Option
User
interface
F1B
heating
cooling
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
Domestic hot water
tank
Only for *KHW Option
Only
for *KRTW* Option
Solar input
Alarm output
Standard 6kw
(_)
See note 10
Cooling/heating
on/off output
From compressor
module switchbox
(B.7 PageA)
supply from
PCB
Only
for *KRTR* Option
3 wire type (SPST)
NO valve
Only forEKHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only
for *KHW(S/E)* Option
Only for EKHW
Option
Wiring dependent on
model
Only
for EKRTETS* Option
Field wiring
Example field
supply
thermostat
Reduced 3kw
See note 10
Electric heater fuse
32A
230V AC
Only for EKSOLHWAV1
Option
Option
Field wiring
F2B
PCB
*KHW kit fuse
20A
A11P
A12P
A3P (*KRTW)
A4P (EKRTR)
A4P (*KRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
K7M
M1P
M2S
M3S
PHC1
Q1DI
Q1L
Q2L
R1H (*KRTR)
R1T (*KRTW/R)
R2T (EKRTETS)
R11T
R12T
R13T
R14T
R5T (*KHW*)
S1L
S1S
S2S
SS1
S1T
S2T
TR1
V1S, V2S
X1M-X10M
X2Y
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole disconnection
: Relay for solar pump
: Pump
: 2 way valve for cooling mode
: 3 way valve: floorheating/domestic hot water
: Optocoupler input circuit
: Earth leakage protector
: Thermal protector backup heater
: Thermal protector 1/2Booster heater
: Humidity sensor
: Ambient sensor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Outlet water backup heater thermistor
: Refrigerant liquid side thermistor
: Inlet water thermistor
: Domestic hot water thermistor
: Flowswitch
: Solar pumpstation relay
: benefit kWh rate power supply contact
: DIP switch
: thermostat switchbox heater
: thermostat expansion vessel heater
: Transformer 24V for PCB
: Spark suppression 1, 2
: Terminal strips
: Connector
Wire colour
NC valve
Notes:
Domestic hot water
tank
Only for *KHWE*V3
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58016-1
96
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
7
Wiring diagram
7-2
External connection diagram
EDHQ011-016AA6V3
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
230V
3 core
3 or4 core
Optional parts
Only for EKRP1HB & EKSOLHWAV1
230V
X1M:1-2-3-Earth
A4P: Y1
Alarm output
A4P: Y2
Cooling/Heating
on/off output
2 way valve
Power supply
booster heater
A4P: Y3
Solar input
2 core
2x0.75
X7M
X5M
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X4M:1-2-Earth
Alarm indication
230V
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
X3M: L1-L2-Earth
or L-N-Earth
Q*L
Clixon
7
1 core
A4P: YC
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
3
2 core
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
X2M: 16-160
User interface
communication
3TW58016-2A
• AlthermaTM • Monobloc
97
• Monobloc • EDHQ011-016AA6V3
8
Sound data
8-1
Sound pressure spectrum
EDHQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
98
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
8
Sound data
8-2
Sound pressure night quiet mode
EDHQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
• AlthermaTM • Monobloc
99
• Monobloc • EDHQ011-016AA6V3
9
Installation
9-1
Service space
EDHQ011-016AA6V3
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
3
Left side obstacle
9
Right side obstacle
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
100
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3
10
Operation range
EDHQ011-016AA6V3
3
Outdoor temp. (°CDB)
Cooling mode
only EB(H/L)*
10
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58013-1A
• AlthermaTM • Monobloc
101
• Monobloc • EDHQ011-016AA6V3
11
Hydraulic performance
11 - 1 Static pressure drop unit
EDHQ011-016AA6V3
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
102
• AlthermaTM • Monobloc
4TW58019-2
• Monobloc • EDHQ011-016AA6W1
TABLE OF CONTENTS
EDHQ011-016AA6W1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
105
105
106
107
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Heating capacity tables
5
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 112
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
115
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
114
116
117
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
103
• Monobloc • EDHQ011-016AA6W1
1
A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnH Dlo E•MA
Features
Heating only monobloc
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
104
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EDHQ011AA6W1
EDHQ014AA6W1
EDHQ016AA6W1
16.00
Heating capacity
Nominal
kW
11.20
14.00
Heating PI
Nominal
kW
2.51
3.22
3.72
COP
Nominal
4.46
4.35
4.30
15.06
Heating capacity
Nominal
kW
10.87
13.10
Heating PI
Nominal
kW
3.12
3.98
4.58
COP
Nominal
3.48
3.29
3.29
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EDHQ011AA6W1
Colour
Unit
Packing
Weight
Packing
2
EDHQ016AA6W1
Ivory white
Material
Dimensions
EDHQ014AA6W1
3
Painted galvanised steel
Height
mm
1,418
Width
mm
1,435
Depth
mm
Height
mm
382
382
382
1,557
Width
mm
Depth
mm
430
1,500
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Material
430
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
Min
Max
kg
20
20
20
°CDB
-15
-15
-15
°CDB
35
35
35
Heating - Waterside Min
°C
15
15
15
Max
°C
55
55
55
°CDB
-15
-15
-15
Domestic hot water Min
-Ambient
Max
°CDB
43
43
43
Domestic hot water Min
- Waterside
Max
°C
25
25
25
°C
80
80
80
Sound Level
(nominal)
Heating
Sound
Pressure
dBA
49
51
53
Sound Level (Night
quiet)
Heating
Sound
Pressure
dBA
42
42
43
Refrigerant
Type
Charge
R-410A
kg
2.95
Control
Nr of Circuits
Refrigerant Oil
1
Type
Charged Volume
2.95
2.95
Electronic expansion valve
1
1
Daphne FVC68D
l
1.0
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
• AlthermaTM • Monobloc
105
• Monobloc • EDHQ011-016AA6W1
2
2-3
Specifications
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EDHQ011AA6W1
EDHQ014AA6W1
EDHQ016AA6W1
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
3
60
Tube type
Hi-XSS
Fin
2
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
Discharge direction
Motor
Quantity
2
Model
Motor
Fan
Speed (nominal)
Steps
Motor
Crankcase Heater
Pump
Type
8
8
8
760
760
760
Output
W
70
70
70
Direct drive
1
JT1G-VDYR@S
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
W
33
Heating
2
2
2
52.5
43.5
35.0
W
210
210
210
Brazed plate
Quantity
l
Water flow rate Min.
Water flow rate
Nom.
Heating
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
l/min
32.1
40.1
45.9
l/min
58
58
58
Insulation material
Foamed synthetic elastomer
Volume
l
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
10
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
Manometer
3
3
Yes
Drain valve / Fill valve
yes
Shut off valve
yes
Air purge valve
yes
Total water volume (6)
106
33
kPa
Type
Water volume
Water circuit
33
1
Water cooled
Power input
Water filter
1
Model
Output
Nominal ESP unit
Expansion vessel
2
rpm
Nr. of speed
Water side Heat
exchanger
2
Heating
Quantity
Motor
Motor
2
Brushless DC
Drive
Compressor
2
Horizontal
l
• AlthermaTM • Monobloc
5.5
5.5
5.5
• Monobloc • EDHQ011-016AA6W1
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
compressor
component
Main Power
Voltage range
EDHQ011AA6W1
EDHQ014AA6W1
Name
W1
Phase
3N~
EDHQ016AA6W1
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Minimum
V
-10%
Maximum
V
+10%
Nominal running
current (RLA)
Heating (A)
A
5.8
5.8
5.8
Maximum running
current
Heating
A
14
14
14
Power supply
compressor
component
Current
Recomended A
fuses
20
20
20
Wiring connections
For power supply
compressor component
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
Phase
Current
Running Current
Current back-up
heater
3
2
See installation manual
6W1
3~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Running Current
Back-up
heater
A
8.7
8.7
8.7
Back-up heater +
booster heater
+EK*V3
A
21.7(8.7+13)
+EK*Z2
A
16.2(8.7+7.5)
Minimum Ssc value +EK*V3
kVa
Equipment complying with EN/IEC 61000-3-12(**)
+EK*Z2
kVa
Equipment complying with EN/IEC 61000-3-12(**)
• AlthermaTM • Monobloc
107
• Monobloc • EDHQ011-016AA6W1
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
Voltage range
Wiring connections
EDHQ011AA6W1
Minimum
V
Maximum
V
+10%
Connection type
for power supply hydraulic compartment
4G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EDHQ016AA6W1
-10%
Quantity of wires
3
EDHQ014AA6W1
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
108
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
3
Options
EDHQ011-016AA6W1
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
1-Phase
Reference
Description
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
109
• Monobloc • EDHQ011-016AA6W1
3
Options
EDHQ011-016AA6W1
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
110
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
4
Capacity tables
4-1
Heating capacity tables
EDHQ011-016AA6W1
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
111
• Monobloc • EDHQ011-016AA6W1
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EDHQ011-016AA6W1
3
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
112
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
6
Piping diagram
6-1
Piping diagram
EDLH011-016AA6W1
Expansion
vessel
Filter
Pressure
gauge
Filter
Evaporator
Condenser
Safety valve
Heat exchanger
Distributor
3
Air purge
6
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Capillary tube
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Stop valve
(with service port 5/16’ flare)
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58135-1A
• AlthermaTM • Monobloc
113
• Monobloc • EDHQ011-016AA6W1
7
Wiring diagram
7-1
Wiring diagram
EDHQ011-016AA6W1
Power supply
Compressor module switchbox
To hydromodule switchbox (8.5 Page 2
Only for E(D/B)LO*
3
7
Reactor terminal
position
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all
switches: ’’OFF’’.
Position of
compressor
terminal
Option
A1P
A2P
A3P
BS1∼BS4
C1∼C4
DS1
E1HC
E1H
F1U
F2U
F3U
F4U
F5U
F6U
F7U
F8U, F9U
H1P∼7P (A1P)
HAP (A1P)
HAP (A2P)
K1M∼K2M
K1R (A1P)
K1R (A2P)
K2R (A1P)
K3R (A1P)
L1R∼L3R
L4R
M1C
M1F
M2F
PS
Q1DI
R1∼R4
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1PH
V1R, V2R
V3R
X1M
Y1E
Y1S
Y3S
Z1C∼Z9C
Z1F∼Z4F
Optional connector
X6A
X77A
X1Y
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Push button switch
Capacitor
DIP switch
Crankcase heater
Bottomplate heater
Fuse (T 31,5A/250V)
Fuse (T 31,5A/250V)
Fuse (T 6.3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 5,0A/250V)
Fuse (T 1,0A/250V)
Pilotlamp (service monitor - orange)
Pilotlamp (service monitor - green)
Pilotlamp (service monitor - green)
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay
Magnetic relay (Y2S)
Magnetic relay (E1HC)
Reactor
Reactor (For outdoor fan motor)
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Earth leakage protector
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Power module
Diode module
Terminal strip
Electronic expansion valve
Solenoid valve (4 way valve)
Solenoid valve
Noise filter
Noise filter
Connector
Connector
Connector
Wiring dependent on
model
Reactor box
El. comp. Assy
(Position of elements)
Arrow A
Arrow B
2TW58136-1
EDHQ011-016AA6W1
Only
for E(D/B)LO*
Option
Only
for EKSOLHWAV1
Option
Power supply E11H-E12H-E13H / E4H
Domestic hot
water tank
Domestic hot
water tank
Solar pump connection
>> See note 2 <<
See note 9
Only for
*KHWE*V3
Option
Only for
*KHW(S/E)* Option
Only for *KHWS*Z2
Option
See note 7
For *KHWSU*V3 Option
User interface
From compressor
module switchbox
(B.7 PageA)
Cooling/heating
on/off output
See note 8
Standard 6kw (_)
See note 10
230V AC
heating
cooling
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only for *KHWS*Z2
Option
Only for *KHW*
Option
Only for *KRTW
Option
Solar input
Only for EKRP1HB
& ESOLHWAV1
Option
Alarm output
Outdoor unit
supply from PCB
Only for *KRTR
Option
3 wire type
(SPST)
Only for *KHW*
Option
NO valve
Only for EKSOLHWAV1
Option
Only for EKHW(S/E)*
Option
Only for EKRTETS
Option
Example field
supply
thermostat
Reduced 3.5kw ( )
See note 10
Wiring dependent
on model
Option
PCB
Field wiring
Field wiring
Wire colour
Electric heater fuse
Model
6WN
F1B
16A
KHW kit fuse
F2B
20A
A11P
A12P
A3P (*KRTW)
A4P (*KRTR)
A4P (EKRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
M1P
: Pump
M2S
: 2 way valve for cooling mode
M3S
: 3 way valve: floorheating/domestic hot water
PHC1
: Optocoupler input circuit
Q1DI
: Earth leakage protector
Q1L
: Thermal protector backup heater
Q2L/Q3L
: Thermal protector 1/2Booster heater
R1H (*KRTR)) : Humidity sensor
R1T (*KRTW/R) : Ambient sensor
R2T (EKRTETS) : External sensor (floor or ambient)
R11T
: Outlet water heat-exchanger thermistor
R12T
: Outlet water backup heater thermistor
R13T
: Refrigerant liquid side thermistor
R14T
: Inlet water thermistor
R5T (*KHW*) : Domestic hot water thermistor
S1L
: Flowswitch
S1S
: Solar pumpstation relay
S2S
: benefit kWh rate power supply contact
SS1
: DIP switch
S1T
: thermostat switchbox heater
S2T
: thermostat expansion vessel heater
TR1
: Transformer 24V for PCB
V1S, V2S
: Spark suppression 1, 2
X1M-X10M : Terminal strips
X2Y
: Connector
NC valve
Notes:
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWE*V3
Option
Only for *KHWE*Z2
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58136-1
114
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
7
Wiring diagram
7-2
External connection diagram
EDHQ011-016AA6W1
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
230V
3 core
3 or4 core
Optional parts
Only for EKRP1HB & EKSOLHWAV1
230V
X1M:1-2-3-Earth
A4P: Y1
Alarm output
A4P: Y2
Cooling/Heating
on/off output
2 way valve
Power supply
booster heater
A4P: Y3
Solar input
2 core
2x0.75
X7M
X5M
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X4M:1-2-Earth
Alarm indication
230V
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
X3M: L1-L2-Earth
or L-N-Earth
Q*L
Clixon
7
1 core
A4P: YC
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
3
2 core
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
X2M: 16-160
User interface
communication
3TW58016-2A
• AlthermaTM • Monobloc
115
• Monobloc • EDHQ011-016AA6W1
8
Sound data
8-1
Sound pressure spectrum
EDHQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
116
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
8
Sound data
8-2
Sound pressure night quiet mode
EDHQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
• AlthermaTM • Monobloc
117
• Monobloc • EDHQ011-016AA6W1
9
Installation
9-1
Service space
EDHQ011-016AA6W1
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
3
Left side obstacle
9
Right side obstacle
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
118
• AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1
10
Operation range
Outdoor temp. (°CDB)
Cooling mode
EDHQ011-016AA6W1
3
only EB(H/L)*
10
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
operation possible, but no guarantee of capacity
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58133-1A
• AlthermaTM • Monobloc
119
• Monobloc • EDHQ011-016AA6W1
11
Hydraulic performance
11 - 1 Static pressure drop unit
EDHQ011-016AA6W1
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
120
• AlthermaTM • Monobloc
4TW58019-2
• Monobloc • EDLQ011-016AA6V3
TABLE OF CONTENTS
EDLQ011-016AA6V3
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
123
123
124
125
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Heating capacity tables
5
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 130
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
133
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
132
134
135
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
121
• Monobloc • EDLQ011-016AA6V3
1
A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnL Dlo E•MA
Features
Heating only monobloc with bottom plate heater
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
122
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EDLQ011AA6V3
EDLQ014AA6V3
EDLQ016AA6V3
16.00
Heating capacity
Nominal
kW
11.20
14.00
Heating PI
Nominal
kW
2.47
3.20
3.79
COP
Nominal
4.54
4.37
4.22
15.06
Heating capacity
Nominal
kW
10.87
13.10
Heating PI
Nominal
kW
3.22
3.91
4.62
COP
Nominal
3.37
3.35
3.26
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EDLQ011AA6V3
Colour
Unit
Packing
Weight
Packing
2
EDLQ016AA6V3
Ivory white
Material
Dimensions
EDLQ014AA6V3
3
Painted galvanised steel
Height
mm
1,418
Width
mm
1,435
Depth
mm
Height
mm
382
382
382
1,557
Width
mm
Depth
mm
430
1,500
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Material
430
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
Min
Max
Sound Level (Night
quiet)
Refrigerant
20
20
20
°CDB
-15
-15
-15
°CDB
35
35
35
Heating - Waterside Min
°C
15
15
15
Max
°C
55
55
55
°CDB
-15
-15
-15
Domestic hot water Min
-Ambient
Max
Sound Level
(nominal)
kg
°CDB
43
43
43
Domestic hot water Min
- Waterside
Max
°C
25
25
25
°C
80
80
80
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
51
51
52
Sound
Pressure
dBA
42
42
43
Heating
Type
Charge
R-410A
kg
2.95
Control
Nr of Circuits
Refrigerant Oil
1
Type
Charged Volume
2.95
2.95
Electronic expansion valve
1
1
Daphne FVC68D
l
1.0
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
• AlthermaTM • Monobloc
123
• Monobloc • EDLQ011-016AA6V3
2
2-3
Specifications
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EDLQ011AA6V3
EDLQ014AA6V3
EDLQ016AA6V3
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
3
60
Tube type
Hi-XSS
Fin
2
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
Air Flow Rate
(nominal at 230V)
Heating
Fan
Discharge direction
High
m³/min
2
2
2
90
90
90
Horizontal
Motor
Quantity
2
Model
Motor
Fan
Speed (nominal)
Steps
Motor
8
8
8
rpm
760
760
760
Output
W
70
70
70
Direct drive
Quantity
1
Motor
Motor
Crankcase Heater
Pump
Type
JT100G-VD
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
Output
W
33
Heating
Power input
2
2
2
52.5
43.5
35.0
W
210
210
210
Brazed plate
Quantity
l
Water flow rate Min.
Water flow rate
Nom.
Heating
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
l/min
32.1
40.1
45.9
l/min
58
58
58
Insulation material
Foamed synthetic elastomer
Volume
l
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
Water circuit
10
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
3
Manometer
Yes
Drain valve / Fill valve
yes
Shut off valve
yes
Air purge valve
3
yes
Total water volume (6)
124
33
kPa
Type
Water volume
Water filter
33
1
Water cooled
Nominal ESP unit
Expansion vessel
1
Model
Nr. of speed
Water side Heat
exchanger
2
Heating
Drive
Compressor
2
Brushless DC
l
• AlthermaTM • Monobloc
5.5
5.5
5.5
• Monobloc • EDLQ011-016AA6V3
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
compressor
component
Main Power
EDLQ011AA6V3
Name
EDLQ014AA6V3
EDLQ016AA6V3
V3
Phase
1
1
1
50
50
230
230
Frequency
Hz
50
230
Voltage
V
Voltage range
Minimum
V
Maximum
V
Current
Minimum
Ssc value
kVa
Recomende
d fuses
A
Wiring connections
For power supply
compressor component
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
-10%
+10%
3
Equipment complying with EN/IEC 61000-3-12(*)
32
32
32
See installation manual
6V3
Phase
1~
Frequency
Hz
50
50
50
Voltage
V
230
230
230
Running Current
Back-up
heater
A
26
26
26
Running Current
Back-up heater +
booster heater
+EK*V3
A
Current back-up
heater
Z-max
Back-up
heater
A
0.29
0.29
0.29
Back-up
heater +
booster
heater
A
0.17
0.17
0.17
Minimum Ssc value +EK*V3
2
kVa
• AlthermaTM • Monobloc
39(26+13)
Equipment complying with EN/IEC 61000-3-12(**)
125
• Monobloc • EDLQ011-016AA6V3
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
Voltage range
Wiring connections
EDLQ011AA6V3
Minimum
V
Maximum
V
+10%
Connection type
for power supply hydraulic compartment
2G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EDLQ016AA6V3
-10%
Quantity of wires
3
EDLQ014AA6V3
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
126
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
3
Options
EDLQ011-016AAV3
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
1-Phase
Reference
Description
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
127
• Monobloc • EDLQ011-016AA6V3
3
Options
EDLQ011-016AA6V3
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
128
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
4
Capacity tables
4-1
Heating capacity tables
EDLQ011-016AA6V3
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
129
• Monobloc • EDLQ011-016AA6V3
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EDLQ011-016AA6V3
3
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
130
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
6
Piping diagram
6-1
Piping diagram
EDLQ011-016AA6V3
Expansion
vessel
Filter
Pressure
gauge
Filter
Evaporator
Condenser
Safety valve
Heat exchanger
Distributor
3
Air purge
6
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Stop valve
(with service port 5/16’ flare)
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58015-1A
• AlthermaTM • Monobloc
131
• Monobloc • EDLQ011-016AA6V3
7
Wiring diagram
7-1
Wiring diagram
EDLQ011-016AA6V3
Power supply
A1P
A2P
A3P
A4P
BS1∼BS4
C1∼C4
DS1
E1H
E1HC
F1U, F3U, F4U
F6U
F7U, F8U
H1P∼7P (A2P)
Compressor module switchbox
N-50Hz
230V
Only for E(D/B)LO*
To hydromodule switchbox (8.5 Page 2
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Printed circuit board
Push button switch
Capacitor
DIP switch
Bottomplate heater
Crankcase heater
Fuse (T 6.3A/250V)
Fuse (T 5.0A/250V)
Fuse (F 1,0A/250V)
Light Emit. Diode (Serv. Monitor-Orange)
Prepare, Test --------- Flickering
Malfunction Detection -- Light up
Light emitting diode (service monitor green)
Magnetic relay (Y1S)
Magnetic relay (E1HC)
Magnetic relay
Magnetic relay
Reactor
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Field earth leakage breaker (300mA)
Resistor
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Signal receiver circuit
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Signal transmission circuit
Power module
Diode module
IGBT
Terminal strip (Power supply)
Electronic expansion valve
Solenoid valve (4 way valve)
Noise filter (ferrity core)
Noise filter
HAP (A1P)
K1R
K4R
K10R
K11R
L1R
M1C
M1F
M2F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
RC
R10T
S1NPH
S1PH
TC
V1R
V2R, V3R
V1T
X1M
Y1E
Y1S
Z1C∼Z3C
Z1F∼Z4F
Optional connector
X1Y
3
7
Connector
Position of
compressor
terminal
Wire entrance
Option
Wiring dependent on
model
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.
El. comp. Assy
(Position of elements)
2TW58016-1
EDLQ011-016AA6V3
Outdoor unit
Only for EC/BLQOption
Only
for EKSOLHWAV1Option
Domestic hot water
tank
Solar pump connection
Power supply
230V 1N∼50Hz
Only
for *KHWE*Option
See note 9
>> See note 2 <<
Only
for *KHW(S/E)*Option
See note 7
For *KHWSU*V3 Option
User
interface
F1B
heating
cooling
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
Domestic hot water
tank
Only for *KHW Option
Only
for *KRTW* Option
Solar input
Alarm output
Standard 6kw
(_)
See note 10
Cooling/heating
on/off output
From compressor
module switchbox
(B.7 PageA)
supply from
PCB
Only
for *KRTR* Option
3 wire type (SPST)
NO valve
Only forEKHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only
for *KHW(S/E)* Option
Only for EKHW
Option
Wiring dependent on
model
Only
for EKRTETS* Option
Field wiring
Example field
supply
thermostat
Reduced 3kw
See note 10
Electric heater fuse
32A
230V AC
Only for EKSOLHWAV1
Option
Option
Field wiring
F2B
PCB
*KHW kit fuse
20A
A11P
A12P
A3P (*KRTW)
A4P (EKRTR)
A4P (*KRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
K7M
M1P
M2S
M3S
PHC1
Q1DI
Q1L
Q2L
R1H (*KRTR)
R1T (*KRTW/R)
R2T (EKRTETS)
R11T
R12T
R13T
R14T
R5T (*KHW*)
S1L
S1S
S2S
SS1
S1T
S2T
TR1
V1S, V2S
X1M-X10M
X2Y
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole disconnection
: Relay for solar pump
: Pump
: 2 way valve for cooling mode
: 3 way valve: floorheating/domestic hot water
: Optocoupler input circuit
: Earth leakage protector
: Thermal protector backup heater
: Thermal protector 1/2Booster heater
: Humidity sensor
: Ambient sensor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Outlet water backup heater thermistor
: Refrigerant liquid side thermistor
: Inlet water thermistor
: Domestic hot water thermistor
: Flowswitch
: Solar pumpstation relay
: benefit kWh rate power supply contact
: DIP switch
: thermostat switchbox heater
: thermostat expansion vessel heater
: Transformer 24V for PCB
: Spark suppression 1, 2
: Terminal strips
: Connector
Wire colour
NC valve
Notes:
Domestic hot water
tank
Only for *KHWE*V3
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58016-1
132
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
7
Wiring diagram
7-2
External connection diagram
EDLQ011-016AA6V3
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
230V
3 core
3 or4 core
Optional parts
Only for EKRP1HB & EKSOLHWAV1
230V
X1M:1-2-3-Earth
A4P: Y1
Alarm output
A4P: Y2
Cooling/Heating
on/off output
2 way valve
Power supply
booster heater
A4P: Y3
Solar input
2 core
2x0.75
X7M
X5M
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X4M:1-2-Earth
Alarm indication
230V
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
X3M: L1-L2-Earth
or L-N-Earth
Q*L
Clixon
7
1 core
A4P: YC
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
3
2 core
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
X2M: 16-160
User interface
communication
3TW58016-2A
• AlthermaTM • Monobloc
133
• Monobloc • EDLQ011-016AA6V3
8
Sound data
8-1
Sound pressure spectrum
EDLQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
134
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
8
Sound data
8-2
Sound pressure night quiet mode
EDLQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
• AlthermaTM • Monobloc
135
• Monobloc • EDLQ011-016AA6V3
9
Installation
9-1
Service space
EDLQ011-016AA6V3
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
3
Left side obstacle
9
Right side obstacle
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
136
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3
10
Operation range
EDLQ011-016AA6V3
3
Outdoor temp. (°CDB)
Cooling mode
only EB(H/L)*
10
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58013-1A
• AlthermaTM • Monobloc
137
• Monobloc • EDLQ011-016AA6V3
11
Hydraulic performance
11 - 1 Static pressure drop unit
EDLQ011-016AA6V3
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
138
• AlthermaTM • Monobloc
4TW58019-2
• Monobloc • EDLQ011-016AA6W1
TABLE OF CONTENTS
EDLQ011-016AA6W1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
141
141
142
143
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Heating capacity tables
5
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 148
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
151
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
150
152
153
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
139
• Monobloc • EDLQ011-016AA6W1
1
A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnL Dlo E•MA
Features
Heating only monobloc with bottom plate heater
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
140
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EDLQ011AA6W1
EDLQ014AA6W1
EDLQ016AA6W1
Heating capacity
Nominal
kW
11.20
14.00
16.00
Heating PI
Nominal
kW
2.51
3.22
3.72
COP
Nominal
4.46
4.35
4.30
Heating capacity
Nominal
kW
10.87
13.10
15.06
Heating PI
Nominal
kW
3.12
3.98
4.58
COP
Nominal
3.48
3.29
3.29
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EDLQ011AA6W1
Colour
Unit
Weight
Packing
EDLQ016AA6W1
Painted galvanised steel
Height
mm
1,418
Width
mm
1,435
Depth
mm
Height
mm
Width
mm
Depth
mm
430
430
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Packing
2
Ivory white
Material
Dimensions
EDLQ014AA6W1
3
382
382
382
1,557
1,500
Material
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
kg
20
20
20
Min
°CDB
-15
-15
-15
Max
35
°CDB
35
35
Heating - Waterside Min
°C
15
15
15
Max
°C
55
55
55
Domestic hot water
-Ambient
Min
°CDB
-15
-15
-15
Max
°CDB
43
43
43
Domestic hot water
- Waterside
Min
°C
25
25
25
Max
°C
80
80
80
Sound Level
(nominal)
Heating
Sound
Pressure
dBA
49
51
53
Sound Level (Night
quiet)
Heating
Sound
Pressure
dBA
42
42
43
Refrigerant
Type
Charge
R-410A
kg
2.95
Control
Nr of Circuits
Refrigerant Oil
1
Type
Charged Volume
2.95
2.95
Electronic expansion valve
1
1
Daphne FVC68D
l
1.0
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
• AlthermaTM • Monobloc
141
• Monobloc • EDLQ011-016AA6W1
2
2-3
Specifications
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EDLQ011AA6W1
EDLQ014AA6W1
EDLQ016AA6W1
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
3
60
Tube type
Hi-XSS
Fin
2
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
Discharge direction
Motor
Quantity
2
Model
Motor
Fan
Speed (nominal)
Steps
Motor
Crankcase Heater
Pump
Type
8
8
8
760
760
760
Output
W
70
70
70
Direct drive
1
JT1G-VDYR@S
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
W
33
Heating
2
2
2
52.5
43.5
35
W
210
210
210
Brazed plate
Quantity
l
Water flow rate Min.
Water flow rate
Nom.
Heating
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
l/min
32.1
40.1
45.9
l/min
58
58
58
Insulation material
Foamed synthetic elastomer
Volume
l
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
10
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
3
Manometer
Yes
Drain valve / Fill valve
yes
Shut off valve
yes
Air purge valve
yes
Total water volume (6)
142
33
kPa
Type
Water volume
Water circuit
33
1
Water cooled
Power input
Water filter
1
Model
Output
Nominal ESP unit
Expansion vessel
2
rpm
Nr. of speed
Water side Heat
exchanger
2
Heating
Quantity
Motor
Motor
2
Brushless DC
Drive
Compressor
2
Horizontal
l
• AlthermaTM • Monobloc
5.5
5.5
3
5.5
• Monobloc • EDLQ011-016AA6W1
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
compressor
component
Main Power
Voltage range
EDLQ011AA6W1
EDLQ014AA6W1
Name
W1
Phase
3N~
EDLQ016AA6W1
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Minimum
V
-10%
Maximum
V
+10%
Nominal running
current (RLA)
Heating (A)
A
5.8
5.8
5.8
Maximum running
current
Heating
A
14
14
14
Power supply
compressor
component
Current
Recomended A
fuses
20
20
20
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
Current
Running Current
Current back-up
heater
3
2
6W1
Phase
3~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Running Current
Back-up
heater
A
8.7
8.7
8.7
Back-up heater +
booster heater
+EK*V3
A
21.7(8.7+13)
+EK*Z2
A
16.2(8.7+7.5)
Minimum Ssc value +EK*V3
kVa
Equipment complying with EN/IEC 61000-3-12(**)
+EK*Z2
kVa
Equipment complying with EN/IEC 61000-3-12(**)
• AlthermaTM • Monobloc
143
• Monobloc • EDLQ011-016AA6W1
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
Voltage range
Wiring connections
EDLQ011AA6W1
Minimum
V
Maximum
V
+10%
Connection type
for power supply hydraulic compartment
4G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EDLQ016AA6W1
-10%
Quantity of wires
3
EDLQ014AA6W1
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
144
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
3
Options
EDLQ011-016AA6W1
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
1-Phase
Reference
Description
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
145
• Monobloc • EDLQ011-016AA6W1
3
Options
EDLQ011-016AA6W1
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1 A
K2 A
Boiler thermostat
A uxiliary contact (normal closed)
Heating only room thermostat
A uxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
A uxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q * unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5
146
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
4
Capacity tables
4-1
Heating capacity tables
EDLQ011-016AA6W1
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
147
• Monobloc • EDLQ011-016AA6W1
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EDLQ011-016AA6W1
3
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
148
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
6
Piping diagram
6-1
Piping diagram
EDLQ011-016AA6W1
Expansion
vessel
Filter
Pressure
gauge
Filter
Evaporator
Condenser
Safety valve
Heat exchanger
Distributor
3
Air purge
6
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Capillary tube
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Stop valve
(with service port 5/16’ flare)
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58135-1A
• AlthermaTM • Monobloc
149
• Monobloc • EDLQ011-016AA6W1
7
Wiring diagram
7-1
Wiring diagram
EDLQ011-016AA6W1
Power supply
Compressor module switchbox
To hydromodule switchbox (8.5 Page 2
Only for E(D/B)LO*
3
7
Reactor terminal
position
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all
switches: ’’OFF’’.
Position of
compressor
terminal
Option
A1P
A2P
A3P
BS1∼BS4
C1∼C4
DS1
E1HC
E1H
F1U
F2U
F3U
F4U
F5U
F6U
F7U
F8U, F9U
H1P∼7P (A1P)
HAP (A1P)
HAP (A2P)
K1M∼K2M
K1R (A1P)
K1R (A2P)
K2R (A1P)
K3R (A1P)
L1R∼L3R
L4R
M1C
M1F
M2F
PS
Q1DI
R1∼R4
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1PH
V1R, V2R
V3R
X1M
Y1E
Y1S
Y3S
Z1C∼Z9C
Z1F∼Z4F
Optional connector
X6A
X77A
X1Y
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Push button switch
Capacitor
DIP switch
Crankcase heater
Bottomplate heater
Fuse (T 31,5A/250V)
Fuse (T 31,5A/250V)
Fuse (T 6.3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 5,0A/250V)
Fuse (T 1,0A/250V)
Pilotlamp (service monitor - orange)
Pilotlamp (service monitor - green)
Pilotlamp (service monitor - green)
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay
Magnetic relay (Y2S)
Magnetic relay (E1HC)
Reactor
Reactor (For outdoor fan motor)
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Earth leakage protector
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Power module
Diode module
Terminal strip
Electronic expansion valve
Solenoid valve (4 way valve)
Solenoid valve
Noise filter
Noise filter
Connector
Connector
Connector
Wiring dependent on
model
Reactor box
Arrow A
El. comp. Assy
(Position of elements)
Arrow B
2TW58136-1
EDLQ011-016AA6W1
Only
for E(D/B)LO*
Option
Only
for EKSOLHWAV1
Option
Power supply E11H-E12H-E13H / E4H
Domestic hot
water tank
Domestic hot
water tank
Solar pump connection
>> See note 2 <<
See note 9
Only for
*KHWE*V3
Option
Only for
*KHW(S/E)* Option
Only for *KHWS*Z2
Option
See note 7
For *KHWSU*V3 Option
User interface
From compressor
module switchbox
(B.7 PageA)
Cooling/heating
on/off output
See note 8
Standard 6kw (_)
See note 10
230V AC
heating
cooling
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only for *KHWS*Z2
Option
Only for *KHW*
Option
Only for *KRTW
Option
Solar input
Only for EKRP1HB
& ESOLHWAV1
Option
Alarm output
Outdoor unit
supply from PCB
Only for *KRTR
Option
3 wire type
(SPST)
Only for *KHW*
Option
NO valve
Only for EKSOLHWAV1
Option
Only for EKHW(S/E)*
Option
Only for EKRTETS
Option
Example field
supply
thermostat
Reduced 3.5kw ( )
See note 10
Wiring dependent
on model
Option
PCB
Field wiring
Field wiring
Wire colour
Electric heater fuse
Model
6WN
F1B
16A
KHW kit fuse
F2B
20A
A11P
A12P
A3P (*KRTW)
A4P (*KRTR)
A4P (EKRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
M1P
: Pump
M2S
: 2 way valve for cooling mode
M3S
: 3 way valve: floorheating/domestic hot water
PHC1
: Optocoupler input circuit
Q1DI
: Earth leakage protector
Q1L
: Thermal protector backup heater
Q2L/Q3L
: Thermal protector 1/2Booster heater
R1H (*KRTR)) : Humidity sensor
R1T (*KRTW/R) : Ambient sensor
R2T (EKRTETS) : External sensor (floor or ambient)
R11T
: Outlet water heat-exchanger thermistor
R12T
: Outlet water backup heater thermistor
R13T
: Refrigerant liquid side thermistor
R14T
: Inlet water thermistor
R5T (*KHW*) : Domestic hot water thermistor
S1L
: Flowswitch
S1S
: Solar pumpstation relay
S2S
: benefit kWh rate power supply contact
SS1
: DIP switch
S1T
: thermostat switchbox heater
S2T
: thermostat expansion vessel heater
TR1
: Transformer 24V for PCB
V1S, V2S
: Spark suppression 1, 2
X1M-X10M : Terminal strips
X2Y
: Connector
NC valve
Notes:
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWE*V3
Option
Only for *KHWE*Z2
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58136-1
150
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
7
Wiring diagram
7-2
External connection diagram
EDLQ011-016AA6W1
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
230V
3 core
3 or4 core
Optional parts
Only for EKRP1HB & EKSOLHWAV1
230V
X1M:1-2-3-Earth
A4P: Y1
Alarm output
A4P: Y2
Cooling/Heating
on/off output
2 way valve
Power supply
booster heater
A4P: Y3
Solar input
2 core
2x0.75
X7M
X5M
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X4M:1-2-Earth
Alarm indication
230V
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
X3M: L1-L2-Earth
or L-N-Earth
Q*L
Clixon
7
1 core
A4P: YC
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
3
2 core
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
X2M: 16-160
User interface
communication
3TW58016-2A
• AlthermaTM • Monobloc
151
• Monobloc • EDLQ011-016AA6W1
8
Sound data
8-1
Sound pressure spectrum
EDLQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
152
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
8
Sound data
8-2
Sound pressure night quiet mode
EDLQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
• AlthermaTM • Monobloc
153
• Monobloc • EDLQ011-016AA6W1
9
Installation
9-1
Service space
EDLQ011-016AA6W1
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
3
Left side obstacle
9
Right side obstacle
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
154
• AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1
10
Operation range
Outdoor temp. (°CDB)
Cooling mode
EDLQ011-016AA6W1
3
only EB(H/L)*
10
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
operation possible, but no guarantee of capacity
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58133-1A
• AlthermaTM • Monobloc
155
• Monobloc • EDLQ011-016AA6W1
11
Hydraulic performance
11 - 1 Static pressure drop unit
EDLQ011-016AA6W1
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
156
• AlthermaTM • Monobloc
4TW58019-2
• Monobloc • EBHQ011-016AA6V3
TABLE OF CONTENTS
EBHQ011-016AA6V3
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
159
159
160
161
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Heating capacity tables
Cooling capacity tables
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 167
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
169
170
171
172
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
157
• Monobloc • EBHQ011-016AA6V3
1
A A 6 1 0 ac- mo1 r l1 eb0 hoQ tHn Blo E•MA
Features
Reversible monobloc
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
158
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EBHQ011AA6V3
EBHQ014AA6V3
EBHQ016AA6V3
Heating capacity
Nominal
kW
11.20
14.00
16.00
Cooling capacity
Nominal
kW
12.85
15.99
16.73
Heating PI
Nominal
kW
2.47
3.20
3.79
Cooling PI
Nominal
kW
3.78
5.65
6.28
COP
Nominal
4.54
4.37
4.22
EER
Nominal
3.39
2.83
2.66
Heating capacity
Nominal
kW
10.87
13.10
15.06
Cooling capacity
Nominal
kW
10.00
12.50
13.10
Heating PI
Nominal
kW
3.22
3.91
4.62
Cooling PI
Nominal
kW
COP
Nominal
EER
Nominal
3.60
5.30
5.85
3.37
3.35
3.26
2.78
2.36
2.24
3
2
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EBHQ011AA6V3
Colour
Unit
Packing
Painted galvanised steel
Height
mm
1,418
Width
mm
1,435
Depth
mm
Height
mm
Width
mm
Depth
mm
430
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Packing
Weight
EBHQ016AA6V3
Ivory white
Material
Dimensions
EBHQ014AA6V3
382
382
382
1,557
1,500
Material
430
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
Min
Max
20
-15
-15
-15
°CDB
35
35
35
15
15
15
Max
°C
55
55
55
Min
°CDB
10
10
10
46
°CDB
46
46
Cooling - Waterside Min
°C
5
5
5
Max
°C
22
22
22
Domestic hot water
-Ambient
Min
°CDB
-15
-15
-15
Max
°CDB
43
43
43
Domestic hot water
- Waterside
Min
°C
25
25
25
Max
°C
80
80
80
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
51
51
52
Sound
Power
dBA
65
66
69
Sound
Pressure
dBA
50
52
54
Heating
Sound
Pressure
dBA
42
42
43
Cooling
Sound
Pressure
dBA
45
45
46
Cooling
Refrigerant
20
°CDB
°C
Max
Sound Level (Night
quiet)
20
Heating - Waterside Min
Cooling - Ambient
Sound Level
(nominal)
kg
Type
Charge
R-410A
kg
2.95
Control
2.95
2.95
Electronic expansion valve
Nr of Circuits
1
• AlthermaTM • Monobloc
1
1
159
• Monobloc • EBHQ011-016AA6V3
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Refrigerant Oil
EBHQ011AA6V3
Type
Charged Volume
l
1.0
2
EBHQ016AA6V3
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
3
EBHQ014AA6V3
Daphne FVC68D
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
2-3
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EBHQ011AA6V3
EBHQ014AA6V3
EBHQ016AA6V3
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
60
Tube type
Hi-XSS
Fin
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
2
2
90
90
100
97
Air Flow Rate
(nominal at 230V)
Heating
High
m³/min
90
Cooling
High
m³/min
96
Fan
Discharge direction
Horizontal
Motor
Quantity
2
Model
Motor
Speed (nominal)
Steps
Motor
8
8
8
760
760
760
Cooling
rpm
780
780
780
Output
W
70
70
70
Drive
Compressor
Direct drive
Quantity
1
Motor
Motor
Crankcase Heater
Pump
Type
JT100G-VD
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
Output
W
33
33
1
33
Water cooled
Nominal ESP unit
Heating
Cooling
Power input
2
2
2
kPa
52.5
43.5
35.0
kPa
55.9
49.1
46.8
W
210
210
210
Type
Brazed plate
Quantity
Water volume
l
Water flow rate Min.
Water flow rate
Nom.
Heating
Cooling
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
l/min
32.1
40.1
45.9
l/min
36.8
45.9
48.0
l/min
58
58
58
Insulation material
160
1
Model
Nr. of speed
Water side Heat
exchanger
2
rpm
Heating
Fan
2
Brushless DC
Foamed synthetic elastomer
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
2
2-3
Specifications
MAIN COMPONENTS
Expansion vessel
Water filter
EBHQ011AA6V3
EBHQ014AA6V3
EBHQ016AA6V3
Volume
l
10
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
Water circuit
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
Manometer
Drain valve / Fill valve
yes
Shut off valve
yes
l
ELECTRICAL SPECIFICATIONS
Main Power
3
2
yes
Total water volume (6)
Power supply
compressor
component
3
Yes
Air purge valve
2-4
3
5.5
5.5
5.5
EBHQ011AA6V3
EBHQ014AA6V3
EBHQ016AA6V3
Name
V3
Phase
1
1
1
Frequency
Hz
50
50
50
230
230
230
Voltage
V
Voltage range
Minimum
V
Maximum
V
Current
Minimum
Ssc value
kVa
Current
Maximum running
current
Cooling
A
Power supply
compressor
component
Current
Recomended A
fuses
Wiring connections
For power supply
compressor component
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
-10%
+10%
Equipment complying with EN/IEC 61000-3-12(×)
22.8
27.4
31.9
32
32
32
See installiation manual
6V3
Phase
1~
Frequency
Hz
50
50
50
Voltage
V
230
230
230
Running Current
Back-up
heater
A
26
26
26
Running Current
Back-up heater +
booster heater
+EK*V3
A
Current back-up
heater
Z-max
Back-up
heater
A
0.29
0.29
0.29
Back-up
heater +
booster
heater
A
0.17
0.17
0.17
Minimum Ssc value +EK*V3
kVa
• AlthermaTM • Monobloc
39(26+13)
Equipment complying with EN/IEC 61000-3-12(**)
161
• Monobloc • EBHQ011-016AA6V3
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
Voltage range
Wiring connections
EBHQ011AA6V3
Minimum
V
Maximum
V
+10%
Connection type
for power supply hydraulic compartment
3G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EBHQ016AA6V3
-10%
Quantity of wires
3
EBHQ014AA6V3
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
162
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
3
Options
EBHQ011-016AAV3
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
1-Phase
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
Reference
Description
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
163
• Monobloc • EBHQ011-016AA6V3
3
Options
EBHQ011-016AA6V3
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
164
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
4
Capacity tables
4-1
Heating capacity tables
EBHQ011-016AA6V3
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
165
• Monobloc • EBHQ011-016AA6V3
4
Capacity tables
4-2
Cooling capacity tables
EBHQ011-016AA6V3
Maximum Cooling Capacity
Model
Tamb
LWE [°C]
20
CC [kW]
25
PI [kW]
CC [kW]
30
PI [kW]
CC [kW]
35
PI [kW]
CC [kW]
40
PI [kW]
CC [kW]
45
PI [kW]
CC [kW]
PI [kW]
3
4
3TW58012-1A
SYMBOLS
CC
PI
LWE
LWC
Tamb
(a)
: only E(D/B)L*
HC
166
NOTES
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to
be added = 95W
• Monobloc • EBHQ011-016AA6V3
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EBHQ011-016AA6V3
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
3
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
• AlthermaTM • Monobloc
167
• Monobloc • EBHQ011-016AA6V3
6
Piping diagram
6-1
Piping diagram
EBHQ011-016AA6V3
Expansion
vessel
Filter
Pressure
gauge
Evaporator
Condenser
Safety valve
3
6
Filter
Heat exchanger
Distributor
Air purge
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Stop valve
(with service port 5/16’ flare)
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58015-1A
168
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
7
Wiring diagram
7-1
Wiring diagram
EBHQ011-016AA6V3
Power supply
A1P
A2P
A3P
A4P
BS1∼BS4
C1∼C4
DS1
E1H
E1HC
F1U, F3U, F4U
F6U
F7U, F8U
H1P∼7P (A2P)
Compressor module switchbox
N-50Hz
230V
Only for E(D/B)LO*
To hydromodule switchbox (8.5 Page 2
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Printed circuit board
Push button switch
Capacitor
DIP switch
Bottomplate heater
Crankcase heater
Fuse (T 6.3A/250V)
Fuse (T 5.0A/250V)
Fuse (F 1,0A/250V)
Light Emit. Diode (Serv. Monitor-Orange)
Prepare, Test --------- Flickering
Malfunction Detection -- Light up
Light emitting diode (service monitor green)
Magnetic relay (Y1S)
Magnetic relay (E1HC)
Magnetic relay
Magnetic relay
Reactor
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Field earth leakage breaker (300mA)
Resistor
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Signal receiver circuit
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Signal transmission circuit
Power module
Diode module
IGBT
Terminal strip (Power supply)
Electronic expansion valve
Solenoid valve (4 way valve)
Noise filter (ferrity core)
Noise filter
HAP (A1P)
K1R
K4R
K10R
K11R
L1R
M1C
M1F
M2F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
RC
R10T
S1NPH
S1PH
TC
V1R
V2R, V3R
V1T
X1M
Y1E
Y1S
Z1C∼Z3C
Z1F∼Z4F
Optional connector
X1Y
3
7
Connector
Position of
compressor
terminal
Wire entrance
Option
Wiring dependent on
model
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.
El. comp. Assy
(Position of elements)
2TW58016-1
EBHQ011-016AA6V3
Outdoor unit
Only for EC/BLQOption
Only
for EKSOLHWAV1Option
Domestic hot water
tank
Solar pump connection
Power supply
230V 1N∼50Hz
Only
for *KHWE*Option
See note 9
>> See note 2 <<
Only
for *KHW(S/E)*Option
See note 7
For *KHWSU*V3 Option
User
interface
F1B
heating
cooling
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
Domestic hot water
tank
Only for *KHW Option
Only
for *KRTW* Option
Solar input
Alarm output
Standard 6kw
(_)
See note 10
Cooling/heating
on/off output
From compressor
module switchbox
(B.7 PageA)
supply from
PCB
Only
for *KRTR* Option
3 wire type (SPST)
NO valve
Only forEKHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only
for *KHW(S/E)* Option
Only for EKHW
Option
Wiring dependent on
model
Only
for EKRTETS* Option
Field wiring
Example field
supply
thermostat
Reduced 3kw
See note 10
Electric heater fuse
32A
230V AC
Only for EKSOLHWAV1
Option
Option
Field wiring
F2B
PCB
*KHW kit fuse
20A
A11P
A12P
A3P (*KRTW)
A4P (EKRTR)
A4P (*KRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
K7M
M1P
M2S
M3S
PHC1
Q1DI
Q1L
Q2L
R1H (*KRTR)
R1T (*KRTW/R)
R2T (EKRTETS)
R11T
R12T
R13T
R14T
R5T (*KHW*)
S1L
S1S
S2S
SS1
S1T
S2T
TR1
V1S, V2S
X1M-X10M
X2Y
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole disconnection
: Relay for solar pump
: Pump
: 2 way valve for cooling mode
: 3 way valve: floorheating/domestic hot water
: Optocoupler input circuit
: Earth leakage protector
: Thermal protector backup heater
: Thermal protector 1/2Booster heater
: Humidity sensor
: Ambient sensor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Outlet water backup heater thermistor
: Refrigerant liquid side thermistor
: Inlet water thermistor
: Domestic hot water thermistor
: Flowswitch
: Solar pumpstation relay
: benefit kWh rate power supply contact
: DIP switch
: thermostat switchbox heater
: thermostat expansion vessel heater
: Transformer 24V for PCB
: Spark suppression 1, 2
: Terminal strips
: Connector
Wire colour
NC valve
Notes:
Domestic hot water
tank
Only for *KHWE*V3
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58016-1
• AlthermaTM • Monobloc
169
• Monobloc • EBHQ011-016AA6V3
7
Wiring diagram
7-2
External connection diagram
EBHQ011-016AA6V3
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
230V
Optional parts
3 or4 core
3 core
7
Only for EKRP1HB & EKSOLHWAV1
1 core
A4P: YC
X3M: L1-L2-Earth
or L-N-Earth
2 way valve
Q*L
Clixon
Power supply
booster heater
A4P: Y1
Alarm output
X7M
A4P: Y2
Cooling/Heating
on/off output
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
X4M:1-2-Earth
Alarm indication
230V
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
A4P: Y3
Solar input
2 core
2x0.75
X5M
230V
X1M:1-2-3-Earth
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
2 core
3
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
X2M: 16-160
User interface
communication
3TW58016-2A
170
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
8
Sound data
8-1
Sound pressure spectrum
EBHQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
EBHQ011-016AA6V3
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-1
• AlthermaTM • Monobloc
171
• Monobloc • EBHQ011-016AA6V3
8
Sound data
8-2
Sound pressure night quiet mode
EBHQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
EBHQ011-016AA6V3
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-3
172
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
9
Installation
9-1
Service space
EBHQ011-016AA6V3
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
Left side obstacle
3
Right side obstacle
9
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
• AlthermaTM • Monobloc
173
• Monobloc • EBHQ011-016AA6V3
10
Operation range
EBHQ011-016AA6V3
Outdoor temp. (°CDB)
10
Cooling mode
3
only EB(H/L)*
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58013-1A
174
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3
11
Hydraulic performance
11 - 1 Static pressure drop unit
EBHQ011-016AA6V3
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
• AlthermaTM • Monobloc
4TW58019-2
175
• Monobloc • EBHQ011-016AA6W1
TABLE OF CONTENTS
EBHQ011-016AA6W1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
179
179
180
181
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Heating capacity tables
Cooling capacity tables
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 187
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
189
190
191
192
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
177
• Monobloc • EBHQ011-016AA6W1
1
A A 6 1 0 ac- mo1 r l1 eb0 hoQ tHn Blo E•MA
Features
Reversible monobloc
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
178
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EBHQ011AA6W1
EBHQ014AA6W1
EBHQ016AA6W1
Heating capacity
Nominal
kW
11.20
14.00
16.00
Cooling capacity
Nominal
kW
12.85
15.99
16.73
Heating PI
Nominal
kW
2.51
3.22
3.72
Cooling PI
Nominal
kW
3.78
5.32
6.06
COP
Nominal
4.46
4.35
4.30
EER
Nominal
3.39
3.01
2.76
Heating capacity
Nominal
kW
10.87
13.10
15.06
Cooling capacity
Nominal
kW
10.00
12.50
13.10
Heating PI
Nominal
kW
3.12
3.98
4.58
Cooling PI
Nominal
kW
3.60
4.98
5.65
COP
Nominal
3.48
3.29
3.29
EER
Nominal
2.78
2.51
2.32
3
2
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EBHQ011AA6W1
Colour
Unit
Packing
Weight
Packing
EBHQ016AA6W1
Ivory white
Material
Dimensions
EBHQ014AA6W1
Painted galvanised steel
Height
mm
Width
mm
Depth
mm
Height
mm
1,418
1,435
382
382
382
1,557
Width
mm
Depth
mm
430
1,500
430
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Material
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
Refrigerant
20
20
-15
-15
-15
Max
35
°CDB
35
35
°C
15
15
15
Max
°C
55
55
55
Min
°CDB
10
10
10
Max
°CDB
46
46
46
Cooling - Waterside Min
°C
5
5
5
Max
°C
22
22
22
Domestic hot water
-Ambient
Min
°CDB
-15
-15
-15
Max
°CDB
43
43
43
Domestic hot water
- Waterside
Min
°C
25
25
25
Max
°C
80
80
80
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
49
51
53
Sound
Power
dBA
65
66
69
Sound
Pressure
dBA
50
52
54
Heating
Sound
Pressure
dBA
42
42
43
Cooling
Sound
Pressure
dBA
45
45
46
Cooling
Sound Level (Night
quiet)
20
°CDB
Heating - Waterside Min
Cooling - Ambient
Sound Level
(nominal)
kg
Min
Type
Charge
R-410A
kg
2.95
Control
2.95
2.95
Electronic expansion valve
Nr of Circuits
1
• AlthermaTM • Monobloc
1
1
179
• Monobloc • EBHQ011-016AA6W1
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Refrigerant Oil
EBHQ011AA6W1
Type
Charged Volume
l
1.0
2
EBHQ016AA6W1
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
3
EBHQ014AA6W1
Daphne FVC68D
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
2-3
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EBHQ011AA6W1
EBHQ014AA6W1
EBHQ016AA6W1
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
60
Tube type
Hi-XSS
Fin
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
Discharge direction
Motor
Quantity
2
Model
Motor
Speed (nominal)
Motor
Motor
Crankcase Heater
Pump
Type
8
8
8
760
760
Cooling
rpm
780
780
780
Output
W
70
70
70
Direct drive
1
JT1G-VDYR@S
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
Output
W
33
33
1
33
Water cooled
Nominal ESP unit
2
2
2
Heating
kPa
52.5
43.5
35.0
Cooling
kPa
55.9
49.1
46.8
W
210
210
210
Power input
Type
Brazed plate
Quantity
Water volume
l
Water flow rate Min.
Water flow rate
Nom.
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
Heating
l/min
32.1
40.1
45.9
Cooling
l/min
36.8
45.9
48.0
l/min
58
58
58
Insulation material
180
1
Model
Nr. of speed
Water side Heat
exchanger
2
760
Quantity
Motor
2
rpm
Drive
Compressor
2
Brushless DC
Steps
Heating
Fan
2
Horizontal
Foamed synthetic elastomer
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
2
2-3
Specifications
MAIN COMPONENTS
Expansion vessel
Water filter
EBHQ011AA6W1
EBHQ014AA6W1
EBHQ016AA6W1
Volume
l
10
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
Water circuit
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
Manometer
Drain valve / Fill valve
yes
Shut off valve
yes
l
5.5
ELECTRICAL SPECIFICATIONS
Main Power
EBHQ011AA6W1
Name
5.5
EBHQ014AA6W1
5.5
EBHQ016AA6W1
3N~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Minimum
V
-10%
Maximum
V
+10%
Nominal running
current (RLA)
Heating (A)
A
Maximum running
current
Heating
A
14
14
14
Cooling
A
13.5
13.5
13.5
Power supply
compressor
component
Current
Recomended A
fuses
20
20
20
Wiring connections
For power supply
compressor component
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
Current
Running Current
Current back-up
heater
5.8
5.8
5.8
See installation manual
6W1
Phase
3~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Running Current
Back-up
heater
A
8.7
8.7
8.7
Back-up heater +
booster heater
+EK*V3
A
21.7(8.7+13)
+EK*Z2
A
16.2(8.7+7.5)
+EK*V3
kVa
Equipment complying with EN/IEC 61000-3-12(**)
+EK*Z2
kVa
Equipment complying with EN/IEC 61000-3-12(**)
Minimum Ssc value
2
W1
Phase
Voltage range
3
yes
Total water volume (6)
Power supply
compressor
component
3
Yes
Air purge valve
2-4
3
• AlthermaTM • Monobloc
181
• Monobloc • EBHQ011-016AA6W1
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
EBHQ011AA6W1
Voltage range
Minimum
V
Maximum
V
Wiring connections
Connection type
+10%
for power supply hydraulic compartment
4G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EBHQ016AA6W1
-10%
Quantity of wires
3
EBHQ014AA6W1
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
182
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
3
Options
EBHQ011-016AA6W1
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
1-Phase
Reference
Description
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
183
• Monobloc • EBHQ011-016AA6W1
3
Options
EBHQ011-016AA6W1
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
184
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
4
Capacity tables
4-1
Heating capacity tables
EBHQ011-016AA6W1
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
185
• Monobloc • EBHQ011-016AA6W1
4
Capacity tables
4-2
Cooling capacity tables
EBHQ011-016AA6W1
Maximum Cooling Capacity
Model
Tamb
LWE [°C]
20
CC [kW]
25
PI [kW]
CC [kW]
30
PI [kW]
CC [kW]
35
PI [kW]
CC [kW]
40
PI [kW]
CC [kW]
45
PI [kW]
CC [kW]
PI [kW]
3
4
3TW58012-1A
SYMBOLS
CC
PI
LWE
LWC
Tamb
(a)
: only E(D/B)L*
HC
186
NOTES
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to
be added = 95W
• Monobloc • EBHQ011-016AA6W1
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EBHQ011-016AA6W1
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
3
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
• AlthermaTM • Monobloc
187
• Monobloc • EBHQ011-016AA6W1
6
Piping diagram
6-1
Piping diagram
EBHQ011-016AA6W1
Expansion
vessel
Filter
Pressure
gauge
Evaporator
Condenser
Safety valve
3
6
Filter
Heat exchanger
Distributor
Air purge
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Capillary tube
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Stop valve
(with service port 5/16’ flare)
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58135-1A
188
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
7
Wiring diagram
7-1
Wiring diagram
EBHQ011-016AA6W1
Power supply
Compressor module switchbox
To hydromodule switchbox (8.5 Page 2
Only for E(D/B)LO*
Reactor terminal
position
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all
switches: ’’OFF’’.
Position of
compressor
terminal
Option
A1P
A2P
A3P
BS1∼BS4
C1∼C4
DS1
E1HC
E1H
F1U
F2U
F3U
F4U
F5U
F6U
F7U
F8U, F9U
H1P∼7P (A1P)
HAP (A1P)
HAP (A2P)
K1M∼K2M
K1R (A1P)
K1R (A2P)
K2R (A1P)
K3R (A1P)
L1R∼L3R
L4R
M1C
M1F
M2F
PS
Q1DI
R1∼R4
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1PH
V1R, V2R
V3R
X1M
Y1E
Y1S
Y3S
Z1C∼Z9C
Z1F∼Z4F
Optional connector
X6A
X77A
X1Y
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Push button switch
Capacitor
DIP switch
Crankcase heater
Bottomplate heater
Fuse (T 31,5A/250V)
Fuse (T 31,5A/250V)
Fuse (T 6.3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 5,0A/250V)
Fuse (T 1,0A/250V)
Pilotlamp (service monitor - orange)
Pilotlamp (service monitor - green)
Pilotlamp (service monitor - green)
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay
Magnetic relay (Y2S)
Magnetic relay (E1HC)
Reactor
Reactor (For outdoor fan motor)
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Earth leakage protector
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Power module
Diode module
Terminal strip
Electronic expansion valve
Solenoid valve (4 way valve)
Solenoid valve
Noise filter
Noise filter
3
7
Connector
Connector
Connector
Wiring dependent on
model
Reactor box
Arrow A
El. comp. Assy
(Position of elements)
Arrow B
2TW58136-1
EBHQ011-016AA6W1
Only
for E(D/B)LO*
Option
Only
for EKSOLHWAV1
Option
Power supply E11H-E12H-E13H / E4H
Domestic hot
water tank
Domestic hot
water tank
Solar pump connection
>> See note 2 <<
See note 9
Only for
*KHWE*V3
Option
Only for
*KHW(S/E)* Option
Only for *KHWS*Z2
Option
See note 7
For *KHWSU*V3 Option
User interface
From compressor
module switchbox
(B.7 PageA)
Cooling/heating
on/off output
See note 8
Standard 6kw (_)
See note 10
230V AC
heating
cooling
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only for *KHWS*Z2
Option
Only for *KHW*
Option
Only for *KRTW
Option
Solar input
Only for EKRP1HB
& ESOLHWAV1
Option
Alarm output
Outdoor unit
supply from PCB
Only for *KRTR
Option
3 wire type
(SPST)
Only for *KHW*
Option
NO valve
Only for EKSOLHWAV1
Option
Only for EKHW(S/E)*
Option
Only for EKRTETS
Option
Example field
supply
thermostat
Reduced 3.5kw ( )
See note 10
Wiring dependent
on model
Option
PCB
Field wiring
Field wiring
Wire colour
Electric heater fuse
Model
6WN
F1B
16A
KHW kit fuse
F2B
20A
A11P
A12P
A3P (*KRTW)
A4P (*KRTR)
A4P (EKRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
M1P
: Pump
M2S
: 2 way valve for cooling mode
M3S
: 3 way valve: floorheating/domestic hot water
PHC1
: Optocoupler input circuit
Q1DI
: Earth leakage protector
Q1L
: Thermal protector backup heater
Q2L/Q3L
: Thermal protector 1/2Booster heater
R1H (*KRTR)) : Humidity sensor
R1T (*KRTW/R) : Ambient sensor
R2T (EKRTETS) : External sensor (floor or ambient)
R11T
: Outlet water heat-exchanger thermistor
R12T
: Outlet water backup heater thermistor
R13T
: Refrigerant liquid side thermistor
R14T
: Inlet water thermistor
R5T (*KHW*) : Domestic hot water thermistor
S1L
: Flowswitch
S1S
: Solar pumpstation relay
S2S
: benefit kWh rate power supply contact
SS1
: DIP switch
S1T
: thermostat switchbox heater
S2T
: thermostat expansion vessel heater
TR1
: Transformer 24V for PCB
V1S, V2S
: Spark suppression 1, 2
X1M-X10M : Terminal strips
X2Y
: Connector
NC valve
Notes:
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWE*V3
Option
Only for *KHWE*Z2
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58136-1
• AlthermaTM • Monobloc
189
• Monobloc • EBHQ011-016AA6W1
7
Wiring diagram
7-2
External connection diagram
EBHQ011-016AA6W1
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
230V
3 core
Optional parts
3 or4 core
7
Only for EKRP1HB & EKSOLHWAV1
1 core
A4P: YC
X3M: L1-L2-Earth
or L-N-Earth
2 way valve
X5M
Power supply
booster heater
X6M
A4P: Y1
Alarm output
X7M
A4P: Y2
Cooling/Heating
on/off output
F28
230V
Only for EKHWSU*V3
5 core
G5 x 2.5
X4M:1-2-Earth
Alarm indication
230V
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
Solar pump
230V
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
A4P: Y3
Solar input
2 core
2x0.75
Q*L
Clixon
230V
X1M:1-2-3-Earth
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
2 core
3
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
X2M: 16-160
User interface
communication
3TW58016-2A
190
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
8
Sound data
8-1
Sound pressure spectrum
EBHQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
EBHQ011-016AA6W1
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-1
• AlthermaTM • Monobloc
191
• Monobloc • EBHQ011-016AA6W1
8
Sound data
8-2
Sound pressure night quiet mode
EBHQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
EBHQ011-016AA6W1
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-3
192
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
9
Installation
9-1
Service space
EBHQ011-016AA6W1
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
Left side obstacle
3
Right side obstacle
9
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
• AlthermaTM • Monobloc
193
• Monobloc • EBHQ011-016AA6W1
10
Operation range
10
Outdoor temp. (°CDB)
3
Cooling mode
EBHQ011-016AA6W1
only EB(H/L)*
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
operation possible, but no guarantee of capacity
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58133-1A
194
• AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1
11
Hydraulic performance
11 - 1 Static pressure drop unit
EBHQ011-016AA6W1
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
• AlthermaTM • Monobloc
4TW58019-2
195
• Monobloc • EBLQ011-016AA6V3
TABLE OF CONTENTS
EBLQ011-016AA6V3
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
199
199
200
201
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Heating capacity tables
Cooling capacity tables
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 207
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
209
210
211
212
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
197
• Monobloc • EBLQ011-016AA6V3
1
A A 6 1 0 ac- mo1 r l1 eb0 hQo tLn Blo E•MA
Features
Reversible monobloc with bottom plate heater
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
198
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EBLQ011AA6V3
EBLQ014AA6V3
EBLQ016AA6V3
Heating capacity
Nominal
kW
11.20
14.00
16.00
Cooling capacity
Nominal
kW
12.85
15.99
16.73
Heating PI
Nominal
kW
2.47
3.20
3.79
Cooling PI
Nominal
kW
3.78
5.65
6.28
COP
Nominal
4.54
4.37
4.22
EER
Nominal
3.39
2.83
2.66
Heating capacity
Nominal
kW
10.87
13.10
15.06
Cooling capacity
Nominal
kW
10.00
12.50
13.10
Heating PI
Nominal
kW
3.22
3.91
4.62
Cooling PI
Nominal
kW
COP
Nominal
EER
Nominal
3.60
5.30
5.85
3.37
3.35
3.26
2.78
2.36
2.24
3
2
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
EBLQ011AA6V3
Colour
Unit
Packing
Painted galvanised steel
Height
mm
1,418
Width
mm
1,435
Depth
mm
Height
mm
Width
mm
Depth
mm
430
430
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Packing
Weight
EBLQ016AA6V3
Ivory white
Material
Dimensions
EBLQ014AA6V3
382
382
382
1,557
1,500
Material
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
Refrigerant
20
20
-15
-15
-15
Max
35
°CDB
35
35
°C
15
15
15
Max
°C
55
55
55
Min
°CDB
10
10
10
Max
°CDB
46
46
46
Cooling - Waterside Min
°C
5
5
5
Max
°C
22
22
22
-15
Domestic hot water
-Ambient
Min
°CDB
-15
-15
Max
°CDB
43
43
43
Domestic hot water
- Waterside
Min
°C
25
25
25
Max
°C
80
80
80
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
51
51
52
Sound
Power
dBA
65
66
69
Sound
Pressure
dBA
50
52
54
Heating
Sound
Pressure
dBA
42
42
43
Cooling
Sound
Pressure
dBA
45
45
46
Cooling
Sound Level (Night
quiet)
20
°CDB
Heating - Waterside Min
Cooling - Ambient
Sound Level
(nominal)
kg
Min
Type
Charge
R-410A
kg
2.95
Control
2.95
2.95
Electronic expansion valve
Nr of Circuits
1
• AlthermaTM • Monobloc
1
1
199
• Monobloc • EBLQ011-016AA6V3
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Refrigerant Oil
EBLQ011AA6V3
Type
Charged Volume
l
1.0
2
EBLQ016AA6V3
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
3
EBLQ014AA6V3
Daphne FVC68D
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
2-3
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EBLQ011AA6V3
EBLQ014AA6V3
EBLQ016AA6V3
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
60
Tube type
Hi-XSS
Fin
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
2
2
90
90
100
97
Air Flow Rate
(nominal at 230V)
Heating
High
m³/min
90
Cooling
High
m³/min
96
Fan
Discharge direction
Horizontal
Motor
Quantity
2
Model
Motor
Speed (nominal)
Steps
Motor
8
8
8
760
760
760
Cooling
rpm
780
780
780
Output
W
70
70
70
Drive
Compressor
Direct drive
Quantity
1
Motor
Motor
Crankcase Heater
Pump
Type
JT100G-VD
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
Output
W
33
33
1
33
Water cooled
Nominal ESP unit
Heating
Cooling
Power input
2
2
2
kPa
52.5
43.5
35.0
kPa
55.9
49.1
46.8
W
210
210
210
Type
Brazed plate
Quantity
Water volume
l
Water flow rate Min.
Water flow rate
Nom.
Heating
Cooling
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
l/min
32.1
40.1
45.9
l/min
36.8
45.9
48.0
l/min
58
58
58
Insulation material
200
1
Model
Nr. of speed
Water side Heat
exchanger
2
rpm
Heating
Fan
2
Brushless DC
Foamed synthetic elastomer
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
2
2-3
Specifications
MAIN COMPONENTS
Expansion vessel
Water filter
EBLQ011AA6V3
EBLQ014AA6V3
EBLQ016AA6V3
Volume
l
10
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
Water circuit
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
Manometer
Drain valve / Fill valve
yes
Shut off valve
yes
l
ELECTRICAL SPECIFICATIONS
Main Power
3
2
yes
Total water volume (6)
Power supply
compressor
component
3
Yes
Air purge valve
2-4
3
5.5
5.5
5.5
EBLQ011AA6V3
EBLQ014AA6V3
EBLQ016AA6V3
Name
V3
Phase
1
1
1
Frequency
Hz
50
50
50
230
230
230
Voltage
V
Voltage range
Minimum
V
Maximum
V
Current
Minimum Ssc kVa
value
Current
Maximum running
current
Cooling
A
22.8
27.4
31.9
Power supply
compressor
component
Current
Recomende
d fuses
A
32
32
32
Wiring connections
For power supply
compressor component
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
-10%
+10%
Equipment complying with EN/IEC 61000-3-12(×)
See installation manual
6V3
Phase
1~
Frequency
Hz
50
50
50
Voltage
V
230
230
230
Running Current
Back-up
heater
A
26
26
26
Running Current
Back-up heater +
booster heater
+EK*V3
A
Current back-up
heater
Z-max
Back-up
heater
A
0.29
0.29
0.29
Back-up
heater +
booster
heater
A
0.17
0.17
0.17
Minimum Ssc value +EK*V3
kVa
• AlthermaTM • Monobloc
39(26+13)
Equipment complying with EN/IEC 61000-3-12(**)
201
• Monobloc • EBLQ011-016AA6V3
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
Voltage range
Wiring connections
EBLQ011AA6V3
Minimum
V
Maximum
V
+10%
Connection type
for power supply hydraulic compartment
3G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EBLQ016AA6V3
-10%
Quantity of wires
3
EBLQ014AA6V3
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
202
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
3
Options
EBLQ011-016AAV3
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
1-Phase
Reference
Description
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
203
• Monobloc • EBLQ011-016AA6V3
3
Options
EBLQ011-016AA6V3
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
204
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
4
Capacity tables
4-1
Heating capacity tables
EBLQ011-016AA6V3
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
205
• Monobloc • EBLQ011-016AA6V3
4
Capacity tables
4-2
Cooling capacity tables
EBLQ011-016AA6V3
Maximum Cooling Capacity
Model
Tamb
LWE [°C]
20
CC [kW]
25
PI [kW]
CC [kW]
30
PI [kW]
CC [kW]
35
PI [kW]
CC [kW]
40
PI [kW]
CC [kW]
45
PI [kW]
CC [kW]
PI [kW]
3
4
3TW58012-1A
SYMBOLS
CC
PI
LWE
LWC
Tamb
(a)
: only E(D/B)L*
HC
206
NOTES
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to
be added = 95W
• Monobloc • EBLQ011-016AA6V3
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EBLQ011-016AA6V3
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
3
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
• AlthermaTM • Monobloc
207
• Monobloc • EBLQ011-016AA6V3
6
Piping diagram
6-1
Piping diagram
EBLQ011-016AA6V3
Expansion
vessel
Filter
Pressure
gauge
Evaporator
Condenser
Safety valve
3
6
Filter
Heat exchanger
Distributor
Air purge
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Stop valve
(with service port 5/16’ flare)
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58015-1A
208
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
7
Wiring diagram
7-1
Wiring diagram
EBLQ011-016AA6V3
Power supply
A1P
A2P
A3P
A4P
BS1∼BS4
C1∼C4
DS1
E1H
E1HC
F1U, F3U, F4U
F6U
F7U, F8U
H1P∼7P (A2P)
Compressor module switchbox
N-50Hz
230V
Only for E(D/B)LO*
To hydromodule switchbox (8.5 Page 2
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Printed circuit board
Push button switch
Capacitor
DIP switch
Bottomplate heater
Crankcase heater
Fuse (T 6.3A/250V)
Fuse (T 5.0A/250V)
Fuse (F 1,0A/250V)
Light Emit. Diode (Serv. Monitor-Orange)
Prepare, Test --------- Flickering
Malfunction Detection -- Light up
Light emitting diode (service monitor green)
Magnetic relay (Y1S)
Magnetic relay (E1HC)
Magnetic relay
Magnetic relay
Reactor
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Field earth leakage breaker (300mA)
Resistor
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Signal receiver circuit
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Signal transmission circuit
Power module
Diode module
IGBT
Terminal strip (Power supply)
Electronic expansion valve
Solenoid valve (4 way valve)
Noise filter (ferrity core)
Noise filter
HAP (A1P)
K1R
K4R
K10R
K11R
L1R
M1C
M1F
M2F
PS
Q1DI
R1
R2
R1T
R2T
R3T
R4T
R5T
R6T
RC
R10T
S1NPH
S1PH
TC
V1R
V2R, V3R
V1T
X1M
Y1E
Y1S
Z1C∼Z3C
Z1F∼Z4F
Optional connector
X1Y
3
7
Connector
Position of
compressor
terminal
Wire entrance
Option
Wiring dependent on
model
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: ’’OFF’’.
El. comp. Assy
(Position of elements)
2TW58016-1
EBLQ011-016AA6V3
Outdoor unit
Only for EC/BLQOption
Only
for EKSOLHWAV1Option
Domestic hot water
tank
Solar pump connection
Power supply
230V 1N∼50Hz
Only
for *KHWE*Option
See note 9
>> See note 2 <<
Only
for *KHW(S/E)*Option
See note 7
For *KHWSU*V3 Option
User
interface
F1B
heating
cooling
Only for EKRP1HB &
EKSOLHWAV1
Option
See note 8
Domestic hot water
tank
Only for *KHW Option
Only
for *KRTW* Option
Solar input
Alarm output
Standard 6kw
(_)
See note 10
Cooling/heating
on/off output
From compressor
module switchbox
(B.7 PageA)
supply from
PCB
Only
for *KRTR* Option
3 wire type (SPST)
NO valve
Only forEKHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only
for *KHW(S/E)* Option
Only for EKHW
Option
Wiring dependent on
model
Only
for EKRTETS* Option
Field wiring
Example field
supply
thermostat
Reduced 3kw
See note 10
Electric heater fuse
32A
230V AC
Only for EKSOLHWAV1
Option
Option
Field wiring
F2B
PCB
*KHW kit fuse
20A
A11P
A12P
A3P (*KRTW)
A4P (EKRTR)
A4P (*KRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
K7M
M1P
M2S
M3S
PHC1
Q1DI
Q1L
Q2L
R1H (*KRTR)
R1T (*KRTW/R)
R2T (EKRTETS)
R11T
R12T
R13T
R14T
R5T (*KHW*)
S1L
S1S
S2S
SS1
S1T
S2T
TR1
V1S, V2S
X1M-X10M
X2Y
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole disconnection
: Relay for solar pump
: Pump
: 2 way valve for cooling mode
: 3 way valve: floorheating/domestic hot water
: Optocoupler input circuit
: Earth leakage protector
: Thermal protector backup heater
: Thermal protector 1/2Booster heater
: Humidity sensor
: Ambient sensor
: External sensor (floor or ambient)
: Outlet water heat-exchanger thermistor
: Outlet water backup heater thermistor
: Refrigerant liquid side thermistor
: Inlet water thermistor
: Domestic hot water thermistor
: Flowswitch
: Solar pumpstation relay
: benefit kWh rate power supply contact
: DIP switch
: thermostat switchbox heater
: thermostat expansion vessel heater
: Transformer 24V for PCB
: Spark suppression 1, 2
: Terminal strips
: Connector
Wire colour
NC valve
Notes:
Domestic hot water
tank
Only for *KHWE*V3
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58016-1
• AlthermaTM • Monobloc
209
• Monobloc • EBLQ011-016AA6V3
7
Wiring diagram
7-2
External connection diagram
EBLQ011-016AA6V3
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
230V
Optional parts
3 or4 core
3 core
7
Only for EKRP1HB & EKSOLHWAV1
1 core
A4P: YC
X3M: L1-L2-Earth
or L-N-Earth
2 way valve
Q*L
Clixon
Power supply
booster heater
A4P: Y1
Alarm output
X7M
A4P: Y2
Cooling/Heating
on/off output
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
X4M:1-2-Earth
Alarm indication
230V
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
A4P: Y3
Solar input
2 core
2x0.75
X5M
230V
X1M:1-2-3-Earth
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
2 core
3
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
X2M: 16-160
User interface
communication
3TW58016-2A
210
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
8
Sound data
8-1
Sound pressure spectrum
EBLQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
EBLQ011-016AA6V3
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-1
• AlthermaTM • Monobloc
211
• Monobloc • EBLQ011-016AA6V3
8
Sound data
8-2
Sound pressure night quiet mode
EBLQ011-016AA6V3
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
EBLQ011-016AA6V3
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-3
212
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
9
Installation
9-1
Service space
EBLQ011-016AA6V3
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
Left side obstacle
3
Right side obstacle
9
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
• AlthermaTM • Monobloc
213
• Monobloc • EBLQ011-016AA6V3
10
Operation range
EBLQ011-016AA6V3
Outdoor temp. (°CDB)
10
Cooling mode
3
only EB(H/L)*
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58013-1A
214
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3
11
Hydraulic performance
11 - 1 Static pressure drop unit
EBLQ011-016AA6V3
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
• AlthermaTM • Monobloc
4TW58019-2
215
• Monobloc • EBLQ011-016AA6W1
TABLE OF CONTENTS
EBLQ011-016AA6W1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
219
219
220
221
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
4
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Heating capacity tables
Cooling capacity tables
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Piping diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 227
Dimensional drawing
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure night quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
229
230
231
232
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
10
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
11
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Static pressure drop unit
• AlthermaTM • Monobloc
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
217
• Monobloc • EBLQ011-016AA6W1
1
A A 6 1 0 ac- mo1 r l1 eb0 hQo tLn Blo E•MA
Features
Reversible monobloc with bottom plate heater
•
Low energy bills and low CO2 emissions
•
H2O piping between outdoor unit and indoor heating appliances
•
Easy to install
•
Freeze protection of hydraulic parts
•
Total solution for year round comfort
•
Cost effective alternative to a fossil fuel boiler
3
1
218
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
2
2-1
Specifications
NOMINAL CAPACITY AND NOMINAL INPUT
Condition 1
Condition 2
EBLQ011AA6W1
EBLQ014AA6W1
EBLQ016AA6W1
Heating capacity
Nominal
kW
11.20
14.00
16.00
Cooling capacity
Nominal
kW
12.85
15.99
16.73
Heating PI
Nominal
kW
2.51
3.22
3.72
Cooling PI
Nominal
kW
3.78
5.32
6.06
COP
Nominal
4.46
4.35
4.30
EER
Nominal
3.39
3.01
2.76
Heating capacity
Nominal
kW
10.87
13.10
15.06
Cooling capacity
Nominal
kW
10.00
12.50
13.10
Heating PI
Nominal
kW
3.12
3.98
4.58
Cooling PI
Nominal
kW
3.60
4.98
5.65
COP
Nominal
3.48
3.29
3.29
EER
Nominal
2.78
2.51
2.32
3
2
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Notes
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2
TECHNICAL SPECIFICATIONS
Casing
Colour
Dimensions
Unit
EBLQ011AA6W1
Painted galvanised steel
Height
mm
1,418
Width
mm
1,435
Depth
mm
Height
mm
Width
mm
Depth
mm
430
430
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Packing
Packing
EBLQ016AA6W1
Ivory white
Material
Weight
EBLQ014AA6W1
382
382
382
1,557
1,500
Material
430
Wood
Carton
Plastic foil
Weight
Operation Range
Heating - Ambient
kg
20
20
20
Min
°CDB
-15
-15
-15
Max
°CDB
35
35
35
Heating - Waterside Min
°C
15
15
15
Max
°C
55
55
55
Min
°CDB
10
10
10
Max
°CDB
46
46
46
Cooling - Waterside Min
°C
5
5
5
Max
°C
22
22
22
-15
Cooling - Ambient
Domestic hot water Min
-Ambient
Max
Sound Level
(nominal)
°CDB
-15
-15
°CDB
43
43
43
Domestic hot water Min
- Waterside
Max
°C
25
25
25
°C
80
80
80
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
49
51
53
Sound
Power
dBA
65
66
69
Sound
Pressure
dBA
50
52
54
Heating
Sound
Pressure
dBA
42
42
43
Cooling
Sound
Pressure
dBA
45
45
46
Cooling
Sound Level (Night
quiet)
Refrigerant
Type
Charge
R-410A
kg
2.95
Control
2.95
2.95
Electronic expansion valve
Nr of Circuits
1
• AlthermaTM • Monobloc
1
1
219
• Monobloc • EBLQ011-016AA6W1
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
Refrigerant Oil
EBLQ011AA6W1
Type
Charged Volume
l
1.0
2
EBLQ016AA6W1
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
3
EBLQ014AA6W1
Daphne FVC68D
1.0
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including piping + PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
2-3
MAIN COMPONENTS
Air heat exchanger
Specifications
Length
EBLQ011AA6W1
EBLQ014AA6W1
EBLQ016AA6W1
857
857
857
2
2
2
mm
1.4
1.4
1.4
5
5
5
m²
1.131
1.131
1.131
60
60
mm
Nr of Rows
Fin pitch
Nr of Passes
Face area
Nr of Stages
60
Tube type
Hi-XSS
Fin
Type
WF fin
Treatment
Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity
2
Discharge direction
Motor
Quantity
2
Model
Motor
Speed (nominal)
Motor
Motor
Crankcase Heater
Pump
Type
8
8
8
760
760
Cooling
rpm
780
780
780
Output
W
70
70
70
Direct drive
1
JT1G-VDYR@S
Type
Hermetically sealed scroll compressor
Motor Output W
2,200
Starting Method
Inverter driven
Output
W
33
33
1
33
Water cooled
Nominal ESP unit
Heating
Cooling
Power input
2
2
2
kPa
52.5
43.5
35.0
kPa
55.9
49.1
46.8
W
210
210
210
Type
Brazed plate
Quantity
Water volume
l
Water flow rate Min.
Water flow rate
Nom.
Heating
Cooling
Water flow rate Max.
1
1
1
1.01
1.01
1.01
l/min
16
16
16
l/min
32.1
40.1
45.9
l/min
36.8
45.9
48.0
l/min
58
58
58
Insulation material
220
1
Model
Nr. of speed
Water side Heat
exchanger
2
760
Quantity
Motor
2
rpm
Drive
Compressor
2
Brushless DC
Steps
Heating
Fan
2
Horizontal
Foamed synthetic elastomer
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
2
2-3
Specifications
MAIN COMPONENTS
Expansion vessel
Water filter
EBLQ011AA6W1
EBLQ014AA6W1
EBLQ016AA6W1
Volume
l
10
10
10
Maximum water pressure
bar
3
3
3
Pre pressure
bar
1.0
1.0
1.0
Diameter perforations
mm
1
1
1
Material
Water circuit
Brass
Piping connections
inch
Piping
inch
Safety valve
bar
G5/4 (FEMALE)
5/4"
3
Manometer
Drain valve / Fill valve
yes
Shut off valve
yes
l
ELECTRICAL SPECIFICATIONS
Main Power
5.5
5.5
5.5
EBLQ011AA6W1
EBLQ014AA6W1
EBLQ016AA6W1
Name
3N~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Minimum
V
-10%
Maximum
V
+10%
Nominal running
current (RLA)
Heating (A)
A
Maximum running
current
Heating
A
14
14
14
Cooling
A
13.5
13.5
13.5
Power supply
compressor
component
Current
Recomended A
fuses
20
20
20
Wiring connections
For power supply
compressor component
Power supply
hydraulic
component
Current back-up
heater
Type
Current back-up
heater
Power Supply
Phase
Current
Running Current
Current back-up
heater
2
W1
Phase
Voltage range
3
yes
Total water volume (6)
Power supply
compressor
component
3
Yes
Air purge valve
2-4
3
5.8
5.8
5.8
See installation manual
6W1
3~
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Running Current
Back-up
heater
A
8.7
8.7
8.7
Back-up heater +
booster heater
+EK*V3
A
21.7(8.7+13)
+EK*Z2
A
16.2(8.7+7.5)
Minimum Ssc value +EK*V3
kVa
Equipment complying with EN/IEC 61000-3-12(**)
+EK*Z2
kVa
Equipment complying with EN/IEC 61000-3-12(**)
• AlthermaTM • Monobloc
221
• Monobloc • EBLQ011-016AA6W1
2
2-4
Specifications
ELECTRICAL SPECIFICATIONS
Power supply
hydraulic
component
EBLQ011AA6W1
Voltage range
Minimum
V
Maximum
V
Wiring connections
Connection type
+10%
for power supply hydraulic compartment
4G
Type of wires
Select diameter and type according to national and local regulations
Connection type
for power supply connection to optional sanitary tank + Q2L
Quantity of wires
2
EBLQ016AA6W1
-10%
Quantity of wires
3
EBLQ014AA6W1
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
For more details on voltage range and current refer to installation manual
Connection type
for connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
for connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Connection type
for connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations
Type of wires
Voltage 230V / Maximum current: 100mA / Minimum 0.75mm²
Notes
Power supply compressor compartment is for compressor, fan, pump and controller
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (3) smaller than or equal
to Zmax.
Installer can reduce capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A.
Instructions see installation manual.
Installer can reduce capacity of the heater from 6 to 3.5kW. The current is then reduced from 8.7 to
5A. Instructions see installation manual.
(1)European/International Technical Standard setting the limits for voltage changes , voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current <= 75A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current > 16A =< 75A per phase.
(3) System impedance
Power supply hydraulic compartment is for the electric heater. The optional domestic warm water tank
has a separate power supply.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
222
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
3
Options
EBLQ011-016AA6W1
Kit availability for E(D/B)(H/L)Q011-016AA*
Altherma Monoblock / Low temperature
Zone 2
EDLQ***AA6V3
EBLQ***AA6V3
011
014
016
1-Phase
Zone 3
EDHQ***AA6V3
EBHQ***AA6V3
011
014
016
3-Phase
Zone 2
Zone 3
EDLQ***AA6W1
EDHQ***AA6W1
EBLQ***AA6W1
EBHQ***AA6W1
011
014
016
011
014
016
Reference
Description
EKRP1HB
Digital I/O PCB
V
V
V
V
V
V
V
V
V
V
V
V
EKBPHT16Y
Bottom plate heater
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKDK04
drain plug kit
-
-
-
V (2)
V (2)
V (2)
-
-
-
V (2)
V (2)
V (2)
EKHWS150B3V3
EKHWS200B3V3
EKHWS300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
Stainless domestic hot water tank 150l 1∼230V
Stainless domestic hot water tank 200l 1∼230V
Stainless domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWS200B3Z2
EKHWS300B3Z2
Stainless domestic hot water tank 200l 2∼400V
Stainless domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
Enamel domestic hot water tank 150l 1∼230V
Enamel domestic hot water tank 200l 1∼230V
Enamel domestic hot water tank 300l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWE200A3Z2
EKHWE300A3Z2
Enamel domestic hot water tank 200l 2∼400V
Enamel domestic hot water tank 300l 2∼400V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
EKHWET150A3V3
Wallmounted enamel domestic hot water tank 150l 1∼230V
V
V
V
V
V
V
V
V
V
V
V
V
EKSOLHWAV1
Solarkit (4)
V
V
V
V
V
V
V
V
V
V
V
V
EKRTW
EKRTR
EKRTETS
Wired room thermostat option kit
Wireless room thermostat option kit (incl. receiver)
External temperature sensor option kit (3)
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3
3
Remark: Other combinations are not guaranteed.
(1)
(2)
(3)
(4)
Input/Output PCB that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included
It is not allowed to combine bottom plate heater and drain plug kit
EKRTETS can only be used in combination with EKRTR
Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
Note:
E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the E(D/B)H* models may experience problems with severe
ice build-up on the aircooled coil. In case such conditions are expected, the E(D/B)L* must be installed instead.
3TW58019-1
• AlthermaTM • Monobloc
223
• Monobloc • EBLQ011-016AA6W1
3
Options
EBLQ011-016AA6W1
Field wiring
Bivalent system
Space heating with an auxiliary boiler (alternating operation)
3
3
Space heating application by either the altherma indoor unit or by an auxiliary boiler
connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q*
hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor
temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
Boiler thermostat
Auto / Boiler
1
2
3
4
Domestic hot water in such an application is always provided by the domestic hot water
tank which is connected to the hydro module, including when the boiler is in operation for
space heating.
The auxiliary boiler can be integrated in the pipework and in the field wiring according to
the illustrations below.
Boiler thermostat
C
th
K1A
K2A
Boiler thermostat
Auxiliary contact (normal closed)
Heating only room thermostat
Auxiliary relay for activation of E(D/B)(H/L)Q * unit
(field supply)
Auxiliary relay for activation of boiler
(field supply)
Operation
When the room thermostat (th) closes, either the E(D/B)(H/L)Q * unit or the boiler starts operating,
depending on the position of the auxiliary contact ( C )
Make sure that auxiliary contact ( C ) has sufficient differential or time delay so
as to avoid frequent changeover between the E(D/B)(H/L)Q * unit and the
boiler. If the auxiliary contact ( C) is an outdoor temperature thermostat, make
sure to install the thermostat in the shade, so that it is not influenced or turned
ON/OFF by the sun.
Frequent switching may cause corrosion of the boiler in an early stage.Contact
the manufacturer of the boiler.
During heating operation of the E(D/B)(H/L)Q * unit, the Altherma unit will
operate so as to achieve the target leaving water temperature as set on the
user interface. When weather dependent operation is active, the water
temperature is determined automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler will operate so as to achieve
the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature setpoint on the boiler controller
above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion
vessel is already premounted in the Altherma unit.
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)(H/L)Q *
switch box correctly. Refer to ’ Room thermostat installation configuration’ in
the installation manual supplied with the unit.
1 Compressor module
2 Hydro module
3 Heat exchanger
4 Pump
5 Shut-off valve
6 Collector (field supply)
7 Motorised 3-way valve (field supply)
8 Booster heater
9 Heat exchanger coil
10 Domestic hot water tank
11 Boiler (field supply)
12 Aquastat valve (field supply)
13 Shut-off valve (field supply)
14 Non-return valve (field supply)
FHL 1...3 Floor heating loop (field supply)
I
User interface
Make sure that return water to the E(D/B)(H/L)Q * heat exchanger never
exceeds 55°C.
For this reason, never put the target leaving water temperature setpoint on the
boiler controller above 55°C and it required, install an aquastat(*) valve in the
return water flow of the E(D/B)(H/L)Q* unit.
Daikin shall not be held liable fo any damage resulting from failure to observe
this rule.
(*)The aquastat valve must be set for 55°C and must operate to close the return water flow to the
E(D/B)(H/L)Q * unit when the measured temperature exceeds 55°C. When temperature drops to a lower
level, the aquastat valve must operate to open the return water flow to the E(D/B)(H/L)Q * unit again.
3TW58019-5A
224
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
4
Capacity tables
4-1
Heating capacity tables
EBLQ011-016AA6W1
Maximum Heating Capacity (Peak values)
Model
LWC [°C]
Tamb
30
HC [kW]
35
PI [kW]
HC [kW]
40
PI [kW]
HC [kW]
45
PI [kW]
HC [kW]
50
PI [kW]
HC [kW]
55
PI [kW]
HC [kW]
PI [kW]
3
4
Maximum Heating Capacity (integrated values)
Model
LWC
Tamb
30
HC
35
PI
HC
40
PI
HC
45
PI
HC
50
PI
HC
55
PI
HC
PI
3TW58012-1A
SYMBOLS
CC
NOTES
PI
LWE
LWC
Tamb
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
(a)
: only E(D/B)L*
HC
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water
range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating
standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to be added = 95W
225
• Monobloc • EBLQ011-016AA6W1
4
Capacity tables
4-2
Cooling capacity tables
EBLQ011-016AA6W1
Maximum Cooling Capacity
Model
Tamb
LWE [°C]
20
CC [kW]
25
PI [kW]
CC [kW]
30
PI [kW]
CC [kW]
35
PI [kW]
CC [kW]
40
PI [kW]
CC [kW]
45
PI [kW]
CC [kW]
PI [kW]
3
4
3TW58012-1A
SYMBOLS
CC
PI
LWE
LWC
Tamb
(a)
: only E(D/B)L*
HC
226
NOTES
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
: Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW)
: Leaving Water Evaporator temperature (°C)
: Leaving Water Condensor temperature (°C)
: Ambient temperature (°C) RH=85%
• AlthermaTM • Monobloc
1
2
3
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Capacity values may not be extrapolated below 7°C leaving water temperature
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 90 W (according EN14511).
For E(D/B)LQ* models only:if Tamb < 4°C: bottom plate heater power input to
be added = 95W
• Monobloc • EBLQ011-016AA6W1
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
EBLQ011-016AA6W1
Hole for anchor bolt
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Center of gravity
Drain outlet
Waterpiping outlet
Waterpiping inlet
Power supply cables intake
Field wiring intake
Service door switchbox
Service door hydraulic module
Service port
Service door compresor module
Pump
REMOCON kit (to be installed indoors)
Shut off valve
Blow off valve
Blow off drain (flexible base)
Pressure gauge
Water filter
loadup ctrl motor + (18a) nipple
Switchbox terminals
Switchbox terminals option sanitary warm water tank
Drain & fill valve
3
Center of gravity
5
Cutaway2
Cutaway1
Cutaway3
3TW58014-1
• AlthermaTM • Monobloc
227
• Monobloc • EBLQ011-016AA6W1
6
Piping diagram
6-1
Piping diagram
EBLQ011-016AA6W1
Expansion
vessel
Filter
Pressure
gauge
Evaporator
Condenser
Safety valve
3
6
Filter
Heat exchanger
Distributor
Air purge
Pump
Outlet
Shut off valve
Service port
5/16″
Electric heater body
Capillary tube
Flowswitch
Filter
Inlet
Shut off valve
Accumulator
Stop valve
(with service port 5/16’ flare)
Drain & fill valve
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
Y1E
E1HC
:
:
:
:
:
:
:
:
:
Thermistor (Air)
Thermistor (discharge)
Thermistor (Suction)
Thermistor (Liquid 1)
Thermistor (middle)
Thermistor (Liquid 2)
Pressure sensor
Electronic expansion valve
Crankcase heater
Y1S
Y3S
S1PH
M*F
M*C
R11T
R12T
R13T
R14T
:
:
:
:
:
:
:
:
:
4-way valve
Injection valve
High pressure switch
Fan motor
Compressor
Outlet water heat-exchanger thermistor
Outlet water backup heater thermistor
Refrigerant liquid side thermistor
Inlet water thermistor
Heating
Cooling
3TW58135-1A
228
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
7
Wiring diagram
7-1
Wiring diagram
EBLQ011-016AA6W1
Power supply
Compressor module switchbox
To hydromodule switchbox (8.5 Page 2
Only for E(D/B)LO*
Reactor terminal
position
Notes:
1 This wiring diagram only applies to the compressor module switchbox
2 L: Live N:Neutral g: Field wiring
3 D : Terminal strip
F : Connector
T : Connection
R : Protective earth (screw)
: Connector
p : Noiseless earth
G : Terminal
4 NOT APPLICABLE
5 6 Do not operate the unit by short-circuiting protection device S1PH
7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green
8 Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all
switches: ’’OFF’’.
Position of
compressor
terminal
Option
A1P
A2P
A3P
BS1∼BS4
C1∼C4
DS1
E1HC
E1H
F1U
F2U
F3U
F4U
F5U
F6U
F7U
F8U, F9U
H1P∼7P (A1P)
HAP (A1P)
HAP (A2P)
K1M∼K2M
K1R (A1P)
K1R (A2P)
K2R (A1P)
K3R (A1P)
L1R∼L3R
L4R
M1C
M1F
M2F
PS
Q1DI
R1∼R4
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1PH
V1R, V2R
V3R
X1M
Y1E
Y1S
Y3S
Z1C∼Z9C
Z1F∼Z4F
Optional connector
X6A
X77A
X1Y
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Noise filter)
Push button switch
Capacitor
DIP switch
Crankcase heater
Bottomplate heater
Fuse (T 31,5A/250V)
Fuse (T 31,5A/250V)
Fuse (T 6.3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (T 5,0A/250V)
Fuse (T 1,0A/250V)
Pilotlamp (service monitor - orange)
Pilotlamp (service monitor - green)
Pilotlamp (service monitor - green)
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay
Magnetic relay (Y2S)
Magnetic relay (E1HC)
Reactor
Reactor (For outdoor fan motor)
Motor (Compressor)
Motor (Fan) (upper)
Motor (Fan) (lower)
Switching power supply
Earth leakage protector
Resistor
Thermistor (Air)
Thermistor (Discharge)
Thermistor (Suction)
Thermistor (Heat exchanger)
Thermistor (heat exchanger middle)
Thermistor (Liquid)
Thermistor (Fin)
Pressure sensor
Pressure switch (High)
Power module
Diode module
Terminal strip
Electronic expansion valve
Solenoid valve (4 way valve)
Solenoid valve
Noise filter
Noise filter
3
7
Connector
Connector
Connector
Wiring dependent on
model
Reactor box
Arrow A
El. comp. Assy
(Position of elements)
Arrow B
2TW58136-1
EBLQ011-016AA6W1
Only
for E(D/B)LO*
Option
Only
for EKSOLHWAV1
Option
Power supply E11H-E12H-E13H / E4H
Domestic hot
water tank
Domestic hot
water tank
Solar pump connection
>> See note 2 <<
See note 9
Only for
*KHWE*V3
Option
Only for
*KHW(S/E)* Option
Only for *KHWS*Z2
Option
See note 7
For *KHWSU*V3 Option
User interface
From compressor
module switchbox
(B.7 PageA)
Cooling/heating
on/off output
See note 8
Standard 6kw (_)
See note 10
230V AC
heating
cooling
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWS*V3
Option
See note 7
For *KHWSU*V3 Option
Only for *KHWS*Z2
Option
Only for *KHW*
Option
Only for *KRTW
Option
Solar input
Only for EKRP1HB
& ESOLHWAV1
Option
Alarm output
Outdoor unit
supply from PCB
Only for *KRTR
Option
3 wire type
(SPST)
Only for *KHW*
Option
NO valve
Only for EKSOLHWAV1
Option
Only for EKHW(S/E)*
Option
Only for EKRTETS
Option
Example field
supply
thermostat
Reduced 3.5kw ( )
See note 10
Wiring dependent
on model
Option
PCB
Field wiring
Field wiring
Wire colour
Electric heater fuse
Model
6WN
F1B
16A
KHW kit fuse
F2B
20A
A11P
A12P
A3P (*KRTW)
A4P (*KRTR)
A4P (EKRTR)
E11H-E12H-E13H
E4H
E5H
E6H
F1B
F1T
F2B
F8U, F9U
FU1
FU2
FuS, FuR
K1M
K3M
K4M
K5M
: Main PCB
: User interface PCB
: Thermostat (PC=power circuit)
: Solar/remote alarm PCB
: Receiver PCB
: Backup heater element 1-2-3 (6 kW)
: Booster heater (3kW)
: Switchbox heater
: Expansion vessel heater
: Fuse backup heater
: Thermal fuse backup heater
: Fuse booster heater
: Fuse 1,0A F 250V
: Fuse 3,15A T 250V for PCB
: Fuse 5A T 250V
: Fuse 5A 250V for solar/remote alarm PCB
: Contactor backup heater step
: Contactor booster heater
: pump relay
: Contactor for backup heater all-pole
disconnection
K7M
: Relay for solar pump
M1P
: Pump
M2S
: 2 way valve for cooling mode
M3S
: 3 way valve: floorheating/domestic hot water
PHC1
: Optocoupler input circuit
Q1DI
: Earth leakage protector
Q1L
: Thermal protector backup heater
Q2L/Q3L
: Thermal protector 1/2Booster heater
R1H (*KRTR)) : Humidity sensor
R1T (*KRTW/R) : Ambient sensor
R2T (EKRTETS) : External sensor (floor or ambient)
R11T
: Outlet water heat-exchanger thermistor
R12T
: Outlet water backup heater thermistor
R13T
: Refrigerant liquid side thermistor
R14T
: Inlet water thermistor
R5T (*KHW*) : Domestic hot water thermistor
S1L
: Flowswitch
S1S
: Solar pumpstation relay
S2S
: benefit kWh rate power supply contact
SS1
: DIP switch
S1T
: thermostat switchbox heater
S2T
: thermostat expansion vessel heater
TR1
: Transformer 24V for PCB
V1S, V2S
: Spark suppression 1, 2
X1M-X10M : Terminal strips
X2Y
: Connector
NC valve
Notes:
Domestic hot water
tank
Domestic hot water
tank
Only for *KHWE*V3
Option
Only for *KHWE*Z2
Option
1
2
3
4
5
6
7
8
9
10
This wiring diagram only applies to the compressor module
Use one and same dedicated power supply compressor module switchbox, hydromodule switchbox and *KHW* option
:Field wiring No/Nc normal open/normal closed SPST - single pole single throw.
:Terminal strip
:Connector
:Terminal
:Protective earth
Do not operate the unit by short-circuiting any protection device.
BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet
For *KHWSU*V3, refer to option manual
Option PCB works with an external 230V AC power supply unit. (N,L)
For EKSOLHWAV1, refer to option manual
Backupheater kW reduction, refer to installation manual
2TW58136-1
• AlthermaTM • Monobloc
229
• Monobloc • EBLQ011-016AA6W1
7
Wiring diagram
7-2
External connection diagram
EBLQ011-016AA6W1
Electrical connection diagram Altherma
For more details please check unit wiring
diagram
Standard parts
Outdoor unit
Power supply
Optional power supply
5 or 3 core
unit power supply: 400V or 230V + earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Bottom plate heater
option
Optional power supply
X1M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
Field supply
Only for EKBPHT
230V
Optional parts
3 or4 core
3 core
7
Only for EKRP1HB & EKSOLHWAV1
1 core
A4P: YC
X3M: L1-L2-Earth
or L-N-Earth
2 way valve
Q*L
Clixon
Power supply
booster heater
A4P: Y1
Alarm output
X7M
A4P: Y2
Cooling/Heating
on/off output
F28
230V
Only for EKHWSU*V3
X6M
5 core
G5 x 2.5
X4M:1-2-Earth
Alarm indication
230V
NO valve: X2M: 6-7
NC valve: X2M: 5-7
X2M: 17-18
Room thermostat
230V
1 core
solar interlock
2 core
230V
2 core
230V
A3P
230V
Note: min. distance to power cable * 5cm
2 core
X9A: (PCB A1P)
Possibility 2
Signal
3 core for C/H application
2 core for H only application
230V
Solar pump
Possibility 3
230V
5 core for C/H application
4 core for H only application
X2M: 1-2-3-4
230V
Only for EKSOLHWAV1
3 way valve
M3S (when EKHWE is intalled) selection
domestic hot water-floorheating
User interface
230V
Only for EKRTETS
2 core (3m
included)
Only for EKTR (wireless room
thermostat)
A4P: X1M: H-C-COM
X2M: L-N
R2T External sensor
(floor or ambient)
A3P: X1M:1-3
Signal
2 core
2 x 0.75
3 core
SPST:
X2M: 8-9-10
Optional parts
Only for EKRTW (wired room thermostat)
A3P: X1M: C-COM-H
X2M: 1-2-3-4
X2M: 19-20
X8M
M2S (E(B/D)(H/L)* Units)
for cooling mode
benefit kWh rate power supply
contact
Only for field supplied room thermostat
X2M: 1-2-3-4
2 core
Q*L
Clixon
2 way valve
4 core
X2M: 13-14
R5T - Thermistor
water temperature
Cooling/Heating
on/off indication
230V
Possibility 1
230V or 400V
Q2L - Clixon
booster heater
1 core
1 core
A4P: Y3
Solar input
2 core
2x0.75
X5M
230V
X1M:1-2-3-Earth
X1M: L1-L2-L3-N-Earth
or L-N-Earth
Domestic hot water tank
2 core
3
Power supply (alarm indication, cooling/heating on/off
indication, solar interlock)
X1M: L1-L2-L3-N-Earth
or L-N-Earth
X2M: 16-160
User interface
communication
3TW58016-2A
230
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
8
Sound data
8-1
Sound pressure spectrum
EBLQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-2
EBLQ011-016AA6W1
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-1
• AlthermaTM • Monobloc
231
• Monobloc • EBLQ011-016AA6W1
8
Sound data
8-2
Sound pressure night quiet mode
EBLQ011-016AA6W1
E(D/B)(H/L)Q016*
HEATING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
HEATING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
HEATING
3
8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-4
EBLQ011-016AA6W1
Octave band center frequency (Hz)
E(D/B)(H/L)Q016*
COOLING
Sound pressure level (dB)
Sound pressure level (dB)
E(D/B)(H/L)Q014*
COOLING
Sound pressure level (dB)
E(D/B)(H/L)Q011*
COOLING
Octave band center frequency (Hz)
Octave band center frequency (Hz)
Notes:
1
2
3
4
Data is valid at free field condition (measured in a semi-anachoic room)
dBA = A-weighted sound power level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation conditions, the measured
value will be higher due to environmental noise and sound reflections.
Measuring location (discharge side)
3TW58017-3
232
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
9
Installation
9-1
Service space
EBLQ011-016AA6W1
A. Non stacked installation
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
Left side obstacle
3
Right side obstacle
9
Top side obstacle
Obstacle is present
1
2
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side
2. Obstacles exist in front of the air inlet
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
• AlthermaTM • Monobloc
233
• Monobloc • EBLQ011-016AA6W1
10
Operation range
10
Outdoor temp. (°CDB)
3
Cooling mode
EBLQ011-016AA6W1
only EB(H/L)*
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
operation possible, but no guarantee of capacity
Outdoor temp. (°CDB)
Heating mode
(*)
E(D/B)L* units include special equipment (insulation, heater
sheet, . . . ) to ensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**)
only E(D/B)L*
Leaving condenser water temperature
Booster heater operation only
only E(D/B)L*
Outdoor temp. (°CDB)
Sanitary mode
(**)
Water temperature sanitary tank (C°)
4TW58133-1A
234
• AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1
11
Hydraulic performance
11 - 1 Static pressure drop unit
EBLQ011-016AA6W1
3
ESP (kPa)
11
I High speed
II medium speed
ESP: External static pressure
Flow: waterflow through the unit
Flow (l/min)
WARNING
1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and
maximum allowed water flowrange in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
• AlthermaTM • Monobloc
4TW58019-2
235
EEDEN09-720
technical data
AlthermaTM
Part 4/4:
EKHWS-B
EKHWE
EKSOLHWAV1
EKRTW
EKRTR
• Domestic hot water tank • EKHWS-B
TABLE OF CONTENTS
EKHWS-B
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 243
Dimensional drawing
5
241
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Cooling capacity tables
4
241
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
• AlthermaTM • Domestic hot water tank
239
• Domestic hot water tank • EKHWS-B
1
o h
c a i m Bt r - s e S e h W mtH oKl •DEA
Features
Stainless steel domestic hot water tank
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
4
1
240
• AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWS-B
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
Casing
Dimensions
Packing
EKHWS200B
3V3
EKHWS300B
3V3
EKHWS200B
3Z2
EKHWS300B
3Z2
Colour
Neutral white
Material
Epoxy-coated mild steel
Packing
Unit
Weight
EKHWS150B
3V3
EKHWSU150
B3V3
EKHWSU200
B3V3
EKHWSU300
B3V3
1,735
Height
mm
950
1,200
1,650
1,200
1,650
1,040
1,280
Width
mm
600
600
600
600
600
600
600
600
Depth
mm
600
600
600
600
600
600
600
600
Height
mm
900
1,150
1,600
1,150
1,600
1,015
1,265
1,715
Width
mm
580
580
580
580
580
580
580
580
Depth
mm
580
580
580
580
580
580
580
580
Unit
kg
37
45
59
45
59
38
46
60
Packed Unit
kg
42
51
66
51
66
43
52
67
Material
EPS
4
2
Carton
Weight
Main
components
Tank
kg
3
4
5
4
5
3
4
5
l
150
200
300
200
300
150
200
285
Max.
temperat
ure
°C
85
85
85
85
85
85
85
85
Max.
water
pressure
bar
10
10
10
10
10
10
10
10
mm
40
40
40
1
1
1
Water
volume
Material
Tank
Insulation
Material
Min.
thickness
Main
components
Heat
exchanger
Quantity
Booster heater
Quantity
Polyurethane foam
Material
Capacity
3-Way Valve
Stainless steel (DIN 1.4521)
40
40
40
40
40
1
1
1
1
1
1
Duplex steel LDX 2101
kW
Coefficien m
t of flow
(kV)
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12
12
12
12
Inlet
inch
Rp1
Outlet
inch
2xRp1
Temperature
sensor
Cable length
m
Piping
connections
Water inlet H/E Diameter
inch
G 3/4 (female)
Water outlet H/E Diameter
inch
G 3/4 (female)
Cold water in Diameter
inch
G 3/4 (female)
Hot water out Diameter
inch
G 3/4 (female)
Recirculation connection
inch
G 3/4 (female)
2-2
Unit
ELECTRICAL SPECIFICATIONS
Power Supply
12
12
12
12
EKHWS150B
3V3
EKHWS200B
3V3
EKHWS300B
3V3
EKHWS200B
3Z2
EKHWS300B
3Z2
EKHWSU150
B3V3
EKHWSU200
B3V3
EKHWSU300
B3V3
Phase
1~
1~
1~
2~
2~
1~
1~
1~
Frequenc Hz
y
50
50
50
50
50
50
50
50
Voltage
230
V
230
230
230
400
400
230
230
Nominal running current
A
13
13
13
7.5
7.5
13
13
13
Fuse
A
20
20
20
20
20
20
20
20
1~
1~
1~
2~
2~
1~
1~
1~
Size
Phase
• AlthermaTM • Domestic hot water tank
241
• Domestic hot water tank • EKHWS-B
3
Capacity tables
3-1
Cooling capacity tables
The ALTHERMA by Daikin heat pump in combination with the optional domestic hot water tank provide hot water for household usage.
The below mentioned date allow a proper selection of the domestic hot water tank size for maximum comfort and efficiency.
(1) Domestic hot water volume:
The volume of hot water available for domestic usage depends on the physical volume of the tank, on the domestic water setpoint temperature and on the temperature spreading
in the tank.
Therefore we define the equivalent hot water volume (EHWV).
Definition:
EHWV = the volume of hot water available for domestic usage at a temperature of 40°C.
40°C is considered a comfortable domestic hot water temperature.
Setpoint temp.
(°C)
55
65
75
55
65
75
55
65
75
Tank
4
150L
3
200L
300L
Grade
++
+
-
Usage pattern
EHWV (l)
110
150
175
160
200
240
295
385
435
Modest
+
++
+
++
++
++
++
++
Usage pattern
Medium
+
+
++
++
++
++
High
+
++
Excessive availability of domestic hot water.
Sufficient availability of domestic hot water.
Temporary shortage of domestic hot water can occur.
Modest Daily demand up tp 220 l -> typcial 2-persons usage pattern.
Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern.
High
Daily demand up to 550 l -> 4 to 6 persons usage pattern.
(2) Heat-up time:
Definition:
Heat-up time The time required to reheat the domestic hot water tank to 55°C after tapping a certain volume of hot water at 40°C.
note: changing the field settings (see installation manual) can influence the heat-up time.
Tank
150L
200L
300L
Heat-up time for 150 L (bath)
<min>
60
60
50
Setpoint temp.
(°C)
55
55
55
Heat-up time for 50 L (shower)
<min>
45
40
30
Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERHQ008
(3) Efficiency of domestic hot water production:
In the ALTHERMA by Daikin system both the heat pump and the electric booster heater supply the energy to produce domestic hot water.
The higher the portion of energy supplied by the heat pump, the more energy efficient the system is.
Lowering the setpoint temperature increases the portion of energy supplied by the heat pump and thus the efficiency of the system.
Heat pump portion
Definition:
Heat pump portion Percentage of energy supplied by the heat pump in the total energy need for domestic hot water.
Setpoint temp. (°C)
Conditions:
Real life condition
Outdoor temperature
Room temperature
Outdoor unit type
Tank type
Field settings
Simulation of a daily usage based upon ′medium′ usage pattern.
7°CDB / 6°CWB
20°CDB
ERHQ008
200l
Default field settings (see installation manual).
4TW57949-1
242
• AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWS-B
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKHWS-B
j
1 Water mains in G 3/4 (Female)
j
2 Water mains out G 3/4 (Female)
j
3 Thermistor connection
j
4 Flow (from EKHB(H/X)*) G 3/4 (Female)
j
5 Return (to EKHB(H/X)*) G 3/4 (Female)
j
6 Switchbox
j
7 Thermal protector
j
8 Anode
j
9 Cable entry: power, booster heater and thermal protection cable
j
10 Re-circulation connection: G 3/4 (Female)
j
11 Cable entry for EKSOLHWAV1: power supply from EKHB(H/X)
j
12 Cable entry for EKSOLHWAV1: power supply to EKSOLHWAV1
pump
j
13 Thermistor connection (See EKSOLHWAV1)
j
14 3 way valve
Required service space around the
tank
4
4
3 way valve
3TW57944-1
EKHWSU-B
Model
EKHWSU150B3V3
EKHWSU200B3V3
EKHWSU300B3V3
H1
900
1150
1600
H2
1015
1265
1715
H3
255
410
410
H4
130
200
200
Water connections
j
1
j
2
j
3
j
4
j
5
j
6
j
7
j
8
Water IN (cold)
Water OUT (hot)
Flow from EKHB(H/X)*
Return to EKHB(H/X)*
Temperature relief valve
Thermistor connection
Thermistor connection (See EKSOLHWAV1)
Re-circulation hole
22MM
G 3/4 (Female)
G 3/4 (Female)
G 3/4 (Female)
15MM
G 1/2 (Female)
G 3/4 (Combinations
compliant to NF-PAC)
Water connections kit
j
9
j
10
j
11
j
12
j
13
j
14
j
15
j
16
j
17
Pressure reducing valve
Expansion relief valve
T-piece (to tundish)
Tundish
T-piece (to expansion vessel)
Adapter (expansion vessel)
Expansion vessel
Drain valve
Solenoid valve
22MM-22MM
22MM-22MM
15MM-15MM-G 1/2 (Female)
22MM-15MM
22MM-22MM-22MM
22MM-G 3/4 (Female)
G 3/4 (Male)
22MM-G 2/4 (Female)
3/4’’ female BSP-3/4’’ hale BSP
Other
j
18
EKUHW2WB kit: solenoid valve (only with EKSOLHWAV1) Rp 3/4 - Rp 3/4
j
19 Switchbox
j
20
Thermal protector 1+Thermostat
j
21
Cable entry: power supply booster heater and thermal protector cable
j
22
Cable entry for EKUHW2WB: power supply to solenoid valve
j
23
Cable entry: power supply booster heater and thermal protector cable
j
24
Blind stop + 2 plastic screw-on closing caps for pressure reducing valve
j
25
Thermal protector 2+Thermostat
j
26
Cable entry for EKSOLHWAV1: power supply to EKSOLHWAV1 pump
j
27
3 way valve 3x Rp1
Typical installation EKUHWA-kit
Required service space
3TW57944-2A
• AlthermaTM • Domestic hot water tank
243
• Domestic hot water tank • EKHWS-B
5
Piping diagram
EKHWSU-B
Overview
Field installation
(delivered with indoor
unit)
Field installation (Delivered
with EKHWSU*B*)
3-way motorized valve
Shut off valve
Outdoor
Load
Indoor
Shut off valve
Water return
Water flow
Option domestic hot water tank
4
Water flow
Water return
5
Option domestic hot water tank
Water main OUT
Water main IN
Pressure reducing valve
with integrated non
return valve line strainer
Expansion relief valve
T-piece
2-way solenoid valve
(*): Field installation delivered with EKUHWB kit
(**): Field installation delivered with
EKUHW2WB
Tundish
Expansion vessel
RST
Y1S
M3S
T-piece
Drain valve
Domestic hot water thermistor
Solenoid valve
3-way motorized valve
3TW57945-1
Check valve
244
Flare connection
Screw connection
Flange connection
Pinched pipe
Spinned pipe
• AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWE
TABLE OF CONTENTS
EKHWE
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 249
Dimensional drawing
5
247
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Cooling capacity tables
4
247
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Wiring diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
• AlthermaTM • Domestic hot water tank
245
• Domestic hot water tank • EKHWE
1
o h
c a i m t r s e E e h W mtH oKl •DEA
Features
Enameled domestic hot water tank
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
4
1
246
• AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWE
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
Mounting
Casing
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
EKHWE200A3Z2
EKHWE300A3Z2
EKHWET150A3V3
Floor
Floor
Floor
Floor
Floor
Wall
Colour
RAL9010
Material
Dimensions
Packing
Unit
Epoxy coated steel
Height
mm
1,460
1,835
1,830
1,835
1,830
1,460
Width
mm
615
615
720
615
720
615
Depth
mm
625
625
730
625
730
625
Height
mm
1,205
1,580
1,572
1,580
1,572
1,205
545
Diameter
Weight
Packing
mm
545
545
660
545
660
Unit
kg
80
104
140
104
140
82
Packed Unit
kg
92
117
158
117
158
94
Material
Carton
4
2
Wood
EPS
Weight
Main
components
Tank
kg
13
13
18
13
18
12
l
150
200
300
200
300
150
Max.
temperat
ure
°C
75
75
75
75
75
75
Max.
water
pressure
bar
10
10
10
10
10
10
mm
47.5
47.5
1
1
Water
volume
Material
Tank
Insulation
Material
Min.
thickness
Main
components
Heat
exchanger
Material
50
47.5
50
47.5
1
1
1
1
Enamel coated steel acc. DIN4753TL2
m²
Quantity
Capacity
3-Way Valve
HFC-free Polyurethane foam
Quantity
Surface
Booster heater
Enamel coated steel acc. DIN4753TL2
kW
Coefficient m
of flow
(kV)
0.5
0.8
1.06
0.8
1.06
0.5
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
3.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
Inlet
inch
RP 1"
Outlet
inch
2 x RP 1"
Temperature
sensor
Cable length
m
Piping
connections
Water inlet H/E Diameter
inch
Rp 3/4"
Water outlet H/E Diameter
inch
Rp 3/4"
Cold water in Diameter
inch
G 3/4"
Hot water out Diameter
inch
G 3/4"
Recirculation connection
inch
G3/4"
2-2
Unit
ELECTRICAL SPECIFICATIONS
Power Supply
12.0
12.0
12.0
EKHWE150A3V3
EKHWE200A3V3
EKHWE300A3V3
EKHWE200A3Z2
EKHWE300A3Z2
EKHWET150A3V3
1~
Phase
1~
1~
1~
2~
2~
Frequency Hz
50
50
50
50
50
50
Voltage
230
230
230
400
400
230
V
Nominal running current
A
13
13
13
7.5
7.5
13
Fuse
A
20
20
20
20
20
20
2
2
2
2
2
2
Size
Pole
• AlthermaTM • Domestic hot water tank
247
• Domestic hot water tank • EKHWE
3
Capacity tables
3-1
Cooling capacity tables
The ALTHERMA by Daikin heat pump in combination with the optional domestic hot water tank provide hot water for household usage.
The below mentioned date allow a proper selection of the domestic hot water tank size for maximum comfort and efficiency.
(1) Domestic hot water volume:
The volume of hot water available for domestic usage depends on the physical volume of the tank, on the domestic water setpoint temperature and on the temperature spreading
in the tank.
Therefore we define the equivalent hot water volume (EHWV).
Definition:
EHWV = the volume of hot water available for domestic usage at a temperature of 40°C.
40°C is considered a comfortable domestic hot water temperature.
Setpoint temp.
(°C)
55
65
75
55
65
75
55
65
75
Tank
4
150L
3
200L
300L
Grade
++
+
-
Usage pattern
EHWV (l)
125
165
185
200
230
260
320
400
435
Modest
+
++
+
++
++
++
++
++
Usage pattern
Medium
+
+
++
++
++
++
High
+
++
Excessive availability of domestic hot water.
Sufficient availability of domestic hot water.
Temporary shortage of domestic hot water can occur.
Modest Daily demand up tp 220 l -> typcial 2-persons usage pattern.
Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern.
High
Daily demand up to 550 l -> 4 to 6 persons usage pattern.
(2) Heat-up time:
Definition:
Heat-up time The time required to reheat the domestic hot water tank to 55°C after tapping a certain volume of hot water at 40°C.
note: changing the field settings (see installation manual) can influence the heat-up time.
Tank
150L
200L
300L
Heat-up time for 150 L (bath)
<min>
60
60
50
Setpoint temp.
(°C)
55
55
55
Heat-up time for 50 L (shower)
<min>
45
40
30
Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERHQ011
(3) Efficiency of domestic hot water production:
In the ALTHERMA by Daikin system both the heat pump and the electric booster heater supply the energy to produce domestic hot water.
The higher the portion of energy supplied by the heat pump, the more energy efficient the system is.
Lowering the setpoint temperature increases the portion of energy supplied by the heat pump and thus the efficiency of the system.
Heat pump portion
Definition:
Heat pump portion Percentage of energy supplied by the heat pump in the total energy need for domestic hot water.
Setpoint temp. (°C)
Conditions:
Real life condition
Outdoor temperature
Room temperature
Outdoor unit type
Tank type
Field settings
Simulation of a daily usage based upon ′medium′ usage pattern.
7°CDB / 6°CWB
20°CDB
ERHQ011
200l
Default field settings (see installation manual).
(4) Heat losses of domestic hot water tank:
Tank
Heat losses*
EKHWE
[kWh/24h]
150L
1.7
200L
1.9
300L
2,5
* Heat losses at _45°C between hot water in tank and surrounding air.
4TW57859-1
248
• AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWE
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKHWE
Required service space around the tank
Wall mounted
j
1 Cold water inlet: G 3/4 (Male)
j
2 Hot water outlet: G 3/4 (Male)
j
3 Thermistor hole
j
4 Flow (From EKHB(H/X)*): Rp 3/4 (Female)
j
5 Return (To EKHB(H/X)*): Rp 3/4 (Female)
j
6 Switchbox
j
7 Thermal protector
j
8 Anode
j
9 Cable entry
j
10 Re-circulation connection: G 3/4 (Male)
j
11 Thermistor hole (See EKSOLHWAV1)
j
12 Wall plate 150L Wall-mounted tank
j
13 Safety valve connection: G 1/2 (Male)
j
14 3 way valve: 3x Rp 1 (Female)
4
4
Wall plate 150L Wall-mounted tank
Inside of
switchbox
3 way valve
Scale 1:5
3TW57854-1A
• AlthermaTM • Domestic hot water tank
249
• Domestic hot water tank • EKHWE
5
Wiring diagram
5-1
Wiring diagram
EKHWE
*KHBH/X*
Switchbox
*KHBH/X*
Switchbox
*KHWE**0A3V3
Water tank
Switchbox
*KHWE**00A3Z2
Water tank
Switchbox
Setpoint Q2L & Q3L: 89°C
Setpoint Q2L: 89°C
4
5
E4H
F2B
K3M
L
N
Q2L
Q3L
X2M∼X4M
X9M∼X10M
: Booster heater
: Fuse booster heater
: Contactor booster heater
: Line
: Neutral
: Thermal protector
Booster heater
: Thermal protector 2
Hot water tank
: Terminal block
: Terminal block
Solar pump
Solar pump
EKSOLHWAV1 (Option)
EKSOLHWAV1 (Option)
Notes:
1
2
3
: Field wiring
: Field wiring
: Wire colour
: Terminal strip
: Protective earth
BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow
BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet
Please refer to the *KHWE* manual for more installation details
3TW57856-1A
250
• AlthermaTM • Domestic hot water tank
• Solar Kit • EKSOLHWAV1
TABLE OF CONTENTS
EKSOLHWAV1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
253
253
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 254
Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
4
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
5
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Wiring diagram
• AlthermaTM • Solar Kit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
251
• Solar Kit • EKSOLHWAV1
1
t 1 i V aKA m W r H r e L a hO l tS oKl E•SA
Features
Connectable to solar collectors
•
Easy to install
•
Cost effective alternative to a fossil fuel boiler
•
Total solution for year round comfort
•
Low energy bills and low CO2 emissions
4
1
252
• AlthermaTM • Solar Kit
• Solar Kit • EKSOLHWAV1
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
Dimensions
Packing
Unit
Weight
Packing
Height
mm
Width
mm
340
Depth
mm
295
Pump
795
Height
mm
770
Width
mm
305
Depth
mm
270
Unit
kg
8
Packed Unit
kg
9
Material
Carton
Weight
Heat
Exchanger
EKSOLHWAV1
kg
Type
1
4
Brazed plate
2
Pressure drop
Solar side kPa
21.5
Maximum inlet
temperature
Solar side °C
110
Capacity
W/K
Logarithmic mean
temperature difference
(LMTD)
K
Type
1,400
5
water cooled
Number of speeds
3
Power input
W
Sound
Sound Pressure
dBA
27
Water circuit
Piping connections
diameter
inch
3/4" FBSP
Insulation material
Ambient
temperature
2-2
EPP
Maximum
°C
35
Minimum
°C
1
ELECTRICAL SPECIFICATIONS
Unit
Power Supply
Phase
Voltage
EKSOLHWAV1
1~
Frequency Hz
Voltage range
46
V
50
220-240
Minimum
-10%
Maximum
+10%
Power Supply Intake
indoor unit
• AlthermaTM • Solar Kit
253
• Solar Kit • EKSOLHWAV1
3
Dimensional drawing & centre of gravity
3-1
Dimensional drawing
EKSOLHWAV1+EKHWS
EKSOLHWAV1 + EKHWS200-300*
EKSOLHWAV1 + EKHWS150*
4
Detail 1
Detail 1
3
Switchbox domestic hot water tank
j
11 Cable entry (Altherma indoor unit)
j
12 Cable entry (Pump cable)
Components
j
1
j
2
j
3
j
4
Pump + switch for speed setting
Heat exchanger
EPP casing
Non return valves
Accessories (delivered with EKSOLHWAV1)
Connection type
j
13 Thermistor sockel (thermistor solar pump station) (internal diameter
6.1mm)
j
14 Adapter
3/4″M BSP-3/4″M BSP
j
15 Adapter
3/4″F BSP-3/4″M BSP
j
16 Adapter
3/4″M BSP-3/4″M BSP
CONNECTIONS
j
5
Inlet connection from solar pump station
j
6
Return connection to solar pump station
j
7
Inlet connection from Altherma indoor unit
j
8
Return connection to Altherma indoor uint
j
9
EKSOLHWAV1 return connection to the domestic hot water tank heatexchanger
j
j
9a 200-300l Tank
9b 150l Tank
j
10 EKSOLHWAV1 inlet connection from the domestic hot water tank heatexchanger
254
3/4″F BSP
3/4″F BSP
3/4″F BSP
3/4″F BSP
3/4″F BSP
3/4″F BSP
• AlthermaTM • Solar Kit
Minimum space for service & ventilation
Detail 1
Scale: 1/4
Service space
Scale: 1/20
3TW57844-1
• Solar Kit • EKSOLHWAV1
3
Dimensional drawing & centre of gravity
3-1
Dimensional drawing
EKSOLHWAV1+EKHWSU
EKSOLHWAV1 + EKHWS200-300*
EKSOLHWAV1 + EKHWS150*
Detail 2
Scale: 1/4
Detail 2
4
Detail 1
3
Switchbox domestic hot water tank
j
11 Cable entry (Altherma indoor unit)
j
12 Cable entry (Pump cable)
Components
j
1
j
2
j
3
j
4
Pump + switch for speed setting
Heat exchanger
EPP casing
Non return valves
Accessories (delivered with EKSOLHWAV1)
Connection type
j
13 Thermistor sockel (thermistor solar pump station) (internal diameter 6.1mm)
j
14 Adapter
3/4″M BSP-3/4″M BSP
j
15 Adapter (Field supply)
3/4″F BSP-3/4″M BSP
Minimum space for service & ventilation
Model
EKHWSU150*
EKHWSU200*
EKHWSU300*
H1
430
400
400
Service space
CONNECTIONS
j
5
Inlet connection from solar pump station
j
6
Return connection to solar pump station
j
7
Inlet connection from Altherma indoor unit
j
8
Return connection to Altherma indoor uint
j
9
EKSOLHWAV1 return connection to the domestic hot water tank heatexchanger
j
j
9a 200-300l Tank
9b 150l Tank
j
10 EKSOLHWAV1 inlet connection from the domestic hot water tank heatexchanger
3/4″F BSP
3/4″F BSP
3/4″F BSP
3/4″F BSP
3/4″F BSP
EKUHWA Kit
j
16 Solenoid valve 3/4″F BSP-3/4″F BSP
j
17 Adapter 3/4″M BSP-3/4″M BSP
Solenoid valve
3/4″F BSP
• AlthermaTM • Solar Kit
Scale: 1/20
3TW57844-2
255
• Solar Kit • EKSOLHWAV1
4
Piping diagram
EKSOLHWAV1
Overview
Indoor
3-way motorized
valve
Load
Shut off
valve
Shut off
valve
Water from
indoor
Field supply
Solar
collector
Option domestic
hot water tank
Field supply
Solar
pump
station
4
Solenoid valve
3-way motorized valve
Field supply
Field installation
(delivered with
indoor unit)
Outdoor
Y1S
M3S
Water to tank
Medium from solar collector
Option
solar kit
Medium to solar collector
Water from tank
4
* Delivered with EKUHWA kit
Water to indoor
Detail 1
Only for EKHWSU*
Water from indoor
Water to tank
Detail 1
2-way solenoid valve *
Medium from solar collector
For EKHW(S/E)*
Plate heat
exchanger
Medium to solar collector
Non return
valve
Pump
Water to indoor
Water from tank
Non return
valve
Check valve
256
Flare connection
Screw connection
Flange connection
3TW57845-1
Pinched pipe
• AlthermaTM • Solar Kit
Spinned pipe
• Solar Kit • EKSOLHWAV1
5
Wiring diagram
5-1
Wiring diagram
EKSOLHWAV1 with EKHWS*V3
EKHWS*V3
Switchbox
EKHB/X*
Switchbox
Solar pump
4
5
EKHB/X*
Switchbox
E4H
F2B
F2U
K3M
L
N
Q2T
Q2L
Q3L
Q3T
X2M∼X4M
X5M1∼X7M
Y1S
: Booster heater
: Fuse booster heater
: Fuse 5A/250V
: Contactor booster heater
: Line
: Neutral
: Thermostat protector 1 domestic hot water tank
: Thermal protector
: Thermal protector 2
Booster heater
: Thermostat protector 2 domestic hot water tank
: Terminal block
: Terminal block
: Solenoid valve
Notes:
1
2
3
: Field wiring
: Field wiring
: Wire colour
: Terminal strip
: Protective earth
BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow
BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet
For more installation details please refer to the relevant installation manual.
3TW57846-1
EKSOLHWAV1 with EKHWS*Z2
EKHWS*Z2
Switchbox
EKHB/X*
Switchbox
Solar pump
EKHB/X*
Switchbox
E4H
F2B
F2U
K3M
L
N
Q2T
Q2L
Q3L
Q3T
X2M∼X4M
X5M1∼X7M
Y1S
: Booster heater
: Fuse booster heater
: Fuse 5A/250V
: Contactor booster heater
: Line
: Neutral
: Thermostat protector 1 domestic hot water tank
: Thermal protector
: Thermal protector 2
Booster heater
: Thermostat protector 2 domestic hot water tank
: Terminal block
: Terminal block
: Solenoid valve
Notes:
1
2
3
: Field wiring
: Field wiring
: Wire colour
: Terminal strip
: Protective earth
BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow
BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet
For more installation details please refer to the relevant installation manual.
3TW57846-1
• AlthermaTM • Solar Kit
257
• Solar Kit • EKSOLHWAV1
5
Wiring diagram
5-1
Wiring diagram
EKSOLHWAV1 with EKHWSU
EKHWS*V3
Switchbox
EKUHWA
EKHB/X*
Switchbox
4
Notes:
1
5
2
3
: Field wiring
: Field wiring
: Wire colour
: Terminal strip
: Protective earth
BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow
BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet
For more installation details please refer to the relevant installation manual.
EKSOLHWAV1
EKHB/X*
Switchbox
E4H
F2B
F2U
K3M
L
N
Q2T
Q2L
Q3L
Q3T
X2M∼X4M
X5M1∼X7M
Y1S
: Booster heater
: Fuse booster heater
: Fuse 5A/250V
: Contactor booster heater
: Line
: Neutral
: Thermostat protector 1 domestic hot water tank
: Thermal protector
: Thermal protector 2
Booster heater
: Thermostat protector 2 domestic hot water tank
: Terminal block
: Terminal block
: Solenoid valve
3TW57846-1
258
• AlthermaTM • Solar Kit
• Room thermostat • • EKRTW
TABLE OF CONTENTS
EKRTW
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
261
261
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 263
Dimensional drawing
• AlthermaTM • Room thermostat
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
259
• Room thermostat • EKRTW
1
Features
s o m r e a h m t r e W mh T otR oKl EAR
4
1
260
• AlthermaTM • Room thermostat
• Room thermostat • EKRTW
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
Dimensions
Unit
Packing
Weight
Unit
Packing
EKRTW
Height
mm
87
Width
mm
125
34
Depth
mm
Height
mm
65
Width
mm
175
Depth
mm
100
Net
g
215
Gross
g
440
Material
Carton
Weight
g
55
4
Ambient
temperature
Storage
°C
-20~60
Operation
°C
0~50
2
Temperature
setting range
Heating
°C
4-37
Cooling
°C
4-37
Temperature setting resolution
°C
Clock
0.5
Yes
Regulation function
Features
Proportional band
Item
Heating only
Heating and cooling
Comfort function mode (= comfort setpoint)
Reduced function mode (=night setback setpoint)
Scheduled function mode(= schedule timer)
Number of setpoint changes
Note
12/day
Item
Holiday function mode
Off function (with integrated frost protection)
Setpoint limitation
Keylock function
2-2
ELECTRICAL SPECIFICATIONS
Power Supply
Voltage
Connection
Maximum rated switching current (at
230VAC)
EKRTW
battery powered 3* AA-LR6 (alkaline)
Wired
A
• AlthermaTM • Room thermostat
0.1
261
• Room thermostat • EKRTW
3
Options
Additional information:
comfort function mode
reduced function mode
scheduled function mode
holiday function mode
off function
setpoint limitation
floor temperature protection
Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode)
Use this mode for a fixed temperature on reduced level. (reduced setpoint default on 17°C in heating mode, 28°C in cooling mode)
Use this mode to let your installation be controlled by the schedule timer. The actions programmed in the schedule timer will be executed automatically according to the
actual time. This function uses the scheduled temperature setpoint.
Use this mode to set a fixed temperature during a long absence.
Use this mode to switch of your installation. Integrated frost protection remains activated. (frost protection default on 4°C in heating mode)
Use this function to limit the setpoint range for the end customer.
Use this function to set a maximum and a minimum floor temperature.
4TW57991-2
4
3
262
• AlthermaTM • Room thermostat
• Room thermostat • EKRTW
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKRTW
4
4
EKRTR
4TW57994-1
• AlthermaTM • Room thermostat
263
• Room thermostat • EKRTR
TABLE OF CONTENTS
EKRTR
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
267
267
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . 269
Dimensional drawing
• AlthermaTM • Room thermostat
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
265
• Room thermostat • EKRTR
1
Features
s o m r e a h m t r e R mh T otR oKl EAR
4
1
266
• AlthermaTM • Room thermostat
• Room thermostat • EKRTR
2
2-1
Specifications
TECHNICAL SPECIFICATIONS
Dimensions
Unit
Packing
Weight
Unit
Packing
EKRTR thermostat
Height
mm
87
Width
mm
125
34
Depth
mm
Height
mm
70
Width
mm
200
Depth
mm
140
Net
g
210
Gross
g
665
Material
Carton
Weight
g
85
4
Ambient
temperature
Storage
°C
-20~60
Operation
°C
0~50
2
Temperature
setting range
Heating
°C
4-37
Cooling
°C
4-37
Temperature setting resolution
°C
Clock
0.5
Yes
Regulation function
Features
Proportional band
Item
Heating only
Heating and cooling
Comfort function mode (= comfort setpoint)
Reduced function mode (=night setback setpoint)
Scheduled function mode(= schedule timer)
Number of setpoint changes
Note
12/day
Item
Holiday function mode
Off function (with integrated frost protection)
Setpoint limitation
Keylock function
Floor temperature protection
Note
2-2
Only in combination with EKRTETS
ELECTRICAL SPECIFICATIONS
Power Supply
Voltage
Connection
Maximum
distance to
receiver
EKRTR thermostat
battery powered 3* AA-LR6 (alkaline)
Wireless
Indoor
m
approx. 30m
Outdoor
m
approx. 100m
• AlthermaTM • Room thermostat
267
• Room thermostat • EKRTR
3
Options
Additional information:
comfort function mode
reduced function mode
scheduled function mode
holiday function mode
off function
setpoint limitation
floor temperature protection
Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode)
Use this mode for a fixed temperature on reduced level. (reduced setpoint default on 17°C in heating mode, 28°C in cooling mode)
Use this mode to let your installation be controlled by the schedule timer. The actions programmed in the schedule timer will be executed automatically according to the
actual time. This function uses the scheduled temperature setpoint.
Use this mode to set a fixed temperature during a long absence.
Use this mode to switch of your installation. Integrated frost protection remains activated. (frost protection default on 4°C in heating mode)
Use this function to limit the setpoint range for the end customer.
Use this function to set a maximum and a minimum floor temperature.
4TW57991-2
4
3
268
• AlthermaTM • Room thermostat
• Room thermostat • EKRTR
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKRTW
4
4
EKRTR
4TW57994-1
• AlthermaTM • Room thermostat
269