Components – Vitotronic 100
Flue gas temperature sensor (for VD2/VD2A/CT3 only)
The sensor measures the flue gas
temperature and monitors the selected
limit value.
Electrical connection
The sensor is inserted in socket ”15”
on the boiler control.
Check flue gas temperature sensor
1. Disconnect plug aG in the terminal
compartment of the boiler control.
2. Measure resistance of sensor at
terminals ”1” and ”2” of the plug.
1020
980
Flue gas
temperature
in °C / °F
Resistance
in Ω
180 / 176
160 / 320
200 / 392
650
800
880
3. Compare the value measured with
the actual temperature. If the value
differs significantly, check
installation and, if necessary, replace
sensor.
940
900
860
Technical data
Degree of protection:
IP 60
Ambient temperature:
During operation:
–20 to + 600°C
32 to + 1112°F
During storage and transport:
–20 to + 670°C
–4 to + 158°F
820
780
740
700
660
620
Resistance in Ω
5351 340 v1.4
580
540
500
0
32
40
80 120 160 200 240
104 176 248 360 392 464
280
536
Flue gas temperature in °C / °F
139