Download Viessmann VD2-860 Technical data
Transcript
Function description – Vitocontrol-S, VD2/CT3/CM2 Cascade control (continued) Net calorific strategy 1 Conventional boilers are preferably operated at their upper output range, to reliably prevent the formation of condensate due to low return temperatures. With net calorific strategy 1, an additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down, when the remaining boiler(s) can achieve the required output on its/their own. Benefit: As few boilers as possible are active. Start-up criteria The boiler is started via a start-up integral. The start-up criteria is met when the start-up integral exceeds a limit set via coding address 45, and the next boiler in the sequence will be started (see page 129). Shutdown criteria The boiler is shut down via an output statement (coding 3d: 1). A boiler is shut down when the currently required output can be achieved without the boiler which was started last. 5351 340 v1.4 Net calorific strategy 2 With the net calorific strategy 2, an additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down if the burner was returned to its minimum output because of a large negative control deviation, and the output is then still too high. Benefit: Long burner operating times Start-up criteria The boiler is started via a start-up integral. The start-up criteria is met when the start-up integral exceeds a limit set via coding address 45, and the next boiler in the sequence will be started (see page 129). Shutdown criteria The boiler is shut down via a shutdown integral. The shutdown criteria is met when the shutdown integral exceeds a limit set via coding 3d: 1, and the boiler started last will be shut down. 127