The numerical formats All temperature values are represented in a uniform numerical format. In the default setting (type K) one Bit corresponds to 0.1°C. The output value corresponds to the temperature range of each sensor as defined according to standards. By using a configuration tool, the output formats can be chosen. The linearization can be switched off and the building of the reference temperature can be switched off also. The following table identifies the numerical format on the default range (type K). Temp. °C 850 Voltage (uV) 35314 100 Binary Value 0010 0001 0011 0100 Hex. 2134 Dec. 8500 4095 0000 0011 1110 1000 03E8 1000 25,5 1021 0000 0000 1111 1111 00FF 255 0,1 4 0000 0000 0000 0001 0001 1 0 0 0000 0000 0000 0000 0000 0 -0,1 -4 1111 1111 1111 1111 FFFF -1 -25,5 -986 1111 1111 0000 0001 FF01 -255 -100 -3553 1111 1100 0001 1000 FC18 -1000 Table 2: Numerical formats Input for thermocouple modules 750-462,469 4 :$*2Ç,2Ç6<67(0