Download Mitsubishi Q62DAN Specifications
Transcript
4.7.2 CJ SCJ (Conditional jump: instantaneous execution condition jump) (S conditional jump: execution condition jump after one scan) 1 X0 CJ 0 P10 2 X1 SCJ 3 X0 P10 X1 6 Y70 FEND 9 Pointer P10 X3 10 Y71 1 • The CJ instruction instantaneously executes a program jumping it to the specified address (pointer number) when the execution command is on. When the command is off, the program is not jumped. 2 • The SCJ instruction executes a program without jumping it for the scan when the execution command is turned on. From the next scan, the instruction executes the program jumping it to the specified address (pointer number). When the command is off, the program is not jumped. • The SCJ instruction is used when some operations must be executed before jumping the program. For example, when the output needs to be on or reset in advance. [Timing chart] Input condition (X0, X1) CJ Executes every scan Executes every scan SCJ One scan Executes every scan Executes every scan One scan 4 - 27