Download RedMax REVOLUTION - 15-BF Technical data

Transcript
RedMax-...-BF
Special options
... -CTS
... -VAS
E X P L O S I O N P R O O F
Technical data
RedMax- 5.10 - BF
Torque motor (min.)
Torque spring (F)
Dimension of external torque
Supply voltage / frequency
Power consumption
Protection class
Angle of rotation and indication
Working direction
Motor running times
Motor
Spring return (F)
3 sec. mode – spring return
Safety operation at 10 sec. (F)
at 3 sec. (F)
Response time spring return
Control mode
Intrinsically safe circuit
IS connection
Integrated aux. switches
Axle of the actuator
Electrical connection
5 / 10 Nm selectable on site
15 Nm
min. 10 Nm
min. 15 Nm
Above mentioned torques are min. torques in blocked position, external torque should be max. 80 % of max. actuator torque but min. 3 Nm
24...240 VAC/DC, ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
max. starting currents see Extra information (in acc. with voltage, I start >> I rated ), approx. 5 W holding power, approx. 16 W for heater
Class I (grounded)
95° incl. ~ 5° pretension, mechanical value indication
Selectable by left/right mounting to the damper/valve shaft
3 / 15 / 30 / 60 / 120 s /90° selectable on site
Brushless DC motor
~ 3 or 10 s/90°, selectable on site, function in the event of loss of power
In acc. with external torque ~ 3 to 4 s/90° angle of rotation
min. 10,000 in acc. with construction of damper and ambient
min. 1,000 in acc. with construction of damper and ambient
up to 1 sec. after power failure
On-off and 3-pos. in acc. with wiring, selectable on site
Additional Ex-i circuit to connect a passive potential free thermostat (e.g. ExPro-TT-...) as a safety sensor for fire dampers
Directly to the actuator with quick connection M12
2 aux. switches, switching at 5° and 85° angle of rotation
Double square 12 × 12 mm, direct coupling, 100 % overload protected and self locking up to 15 Nm
Cable ~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm².
Connections in hazardous areas require a terminal box !
~ Ø 9.6 mm
~ Ø 9.6 mm
M16 × 1.5 mm standard cable and wire entries
Use delivered socket wrench, max. 4 Nm
Integral, controlled heater for ambient temperature down to −40 °C
Aluminium die cast housing, painted. Optional with seawater resistant C5-M finish (...-CTS) or housing in stainless steel DIN EN 1.4581 /
V4A / UNS- J92900 / similar AISI 316 Cb (...-VAS)
L × W × H = 210 × 95 × 80 mm, for diagrams see Extra information
~ 3,5 kg aluminium housing, stainless steel ~ 7 kg
Storage temperature −40…+70 °C, working temperature −40…+40 °C at T6 and −40…+50 °C at T5
0...90 % rH, non condensing
In 3 s mode the motor will work only after 1 minute of voltage supply. While open/close operation (open voltage supply and shut it down)
motor works only with speed of 15 s /90°
at 15 / 30 / 60 / 120 s 100 % of ED is permitted (ED = duty cycle)
Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
SB 7.0 / 7.1
SB 7.0 / 7.1
Actuator with 1 m cable, 4 screws M4 × 100 mm, 4 nuts M4, Allen key for simple manual override
5 Nm, 30 s/ 90°
15 Nm, 30 s/90°
Diameter of cable
Cable gland
Manual override
Integral heater
Housing material
Dimensions
Weight
Ambients
Humidity
Operating 3 sec. motor run time
≥ 15 sec. motor run time
Maintenance
Wiring diagrams
Scope of delivery
Parameter at delivery
RedMax- 15 - BF
Approbations
ATEX tested
IECEx tested
In acc. with ATEX
Approval for gas
Approval for dust
Identification
EMC
Low voltage
IP-Protection
Ex-i circuit data
Special solutions and accessories
PTB 04 ATEX 2106
IECEx PTB 08.0059
94/9 /EC
II 3 (1) G Ex nC [ia] IIC T6/T5
II 3 G
Ex nC II T6/T5
II 3 D
Ex tD A22 IP66 T80 °C
CE No. 0158
2004 /108 /EC
2006 /95 /EC
IP66 in acc. with EN 60529
see table (T 1.0)
zone 2
zone 22
...-CTS
...-VAS
RedBox-...
MKK-S
ExPro-TT-...
RedSwitch
HV-S...
KB-S
AR-12-xx
BSH-S
Kit-S8
Adaptions
RedMax-... S3
RedMax-... S7
Types in aluminium housing with C5-M finish, parts nickel-plated
Types in stainless steel housing, parts nickel-plated
Terminal boxes for zone 2, 22
Mounting bracket for boxes type ...Box-... directly on actuator
Safety temperature trigger in acc. with ATEX
2 external aux. switches, adjustable for zone 2, 22
Comfortable manual override for...Max actuators size S
Clamp for damper shafts Ø 10...20 mm and □ 10...16 mm
Reduction part for 12 mm square connection to 11, 10, 9 or 8 mm shafts
Mounting holder for actuators in fire danger areas
Cable glands nickel-plated
for dampers and valves on request
Ambient temperature up to +60 °C (T4), 110...240 VAC/DC, 25 % ED
Shock tested up to 500 g
RedMax-S-BF_en
V01 –
4-Feb-2015
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
www.schischek.com
2/4