Troubleshooting by Remote Controller Si20-701_B Troubleshooting Caution Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged. CHECK 12 Check for inadequate refrigerant. Is the refrigerant level proper? NO YES Check the transmission wiring and piping between the indoor and outdoor units. Is wiring and piping connection matched? NO Collect refrigerant and recharge a proper amount of refrigerant after vacuum drying. Match wiring and piping connection. YES Check the refrigerant piping system for clogging. CHECK 11 CHECK 11 Refer to P.477. CHECK 12 Refer to P.478. 357