Communication 6.5 Communication via PROFINET CAUTION Shutdown on faults can only take place if both monitoring functions are activated! When the PROFINET interface is in operation, parameter P8840 should also be set to a value of > 0. The process data monitoring function is thus activated/deactivated solely using the PROFIBUS process data monitoring function. The monitoring time then corresponds to the process data monitoring time setting plus the time set in P8840. Note Process data whose complete control word (PZD1) is set to zero are not transferred from the PROFINET interface to the inverter. Result: Alarm A0703 and possibly fault F0070. P0927 Modification source for parameters This parameter defines the interface through which parameters can be modified. Bit Description Index 0 PROFINET 0: No 1: Yes 1 BOP 0: No 1: Yes 2 PC Connection Kit (STARTER) 0: No 1: Yes The default setting for all bits is 1, i.e. parameters can be modified from all sources. 176 Control Units CU240S Operating Instructions, 06/2007 - SW 3.0, A5E00766042B AB