Modbus for Field Technicians 11. MULTIPLE CLIENTS OF A MODBUS SLAVE We are frequently asked how you deal with a situation where you have more than one client for a slave(s). The Modbus spec does not support this but we have a solution. The essence of the solution is to use a multi-port FieldServer. Connect each client to its own port and the slave(s) to their own ports. Each client will see a single virtual slave(s) on its network. This not only solves the problem but is extremely efficient. Of course the FieldServer needs to be correctly configured. In a situation like this we exploit the FieldServer technology known as ‘Port Expansion’. Figure 1: Normally it is not possible to connect two clients to the same slave. There are two primary reasons: 1) If you are using RS232 then there can only be two devices on the cable segment. 2) If you are using RS485 then the 2nd client will not know to process the poll from the 1st client. It will cause errors. Page 21