Download Raypak Temp-Tracker Specifications

Transcript
28
Raypak, Inc.
HYBRID Operating Menu
OD=
55oFSYS=143oF
<<A>>
67%
B
22%
STAGE ◄ ►
MENU
-------
SETBACK ------10 oF
[
]
BACK ▲ ▼ SAVE
---
PURGE
DELAY
1.0
---
min
[
]
BACK ▲ ▼ SAVE
--
SYSTEM
10
RUN-ON
--
min
[
]
BACK ▲ ▼ SAVE
-------- SETTINGS ---Season
Winter
o
System Target140 F
<System Settings>
<Maintenance>
<System Startup>
BACK ▲ ▼
SELECT
----- SETTINGS 1 ---Setback
10oF
Purge Delay 1.0min
System Run-On10min
Lead Rotation Time
<More Settings>
BACK ▲ ▼ SELECT
Note
To be able to change the
TempTracker mod+ Hybrid settings
the Program/Run Switch must
be set to Program. The switch is
located under the Enclosure Wiring
Cover for security. The Enclosure
Wiring Cover can be secured using
a lock.
-- LEAD ROTATION -
Manual
Time
Last-On
BACK ▲ ▼ SAVE
--
STANDBY
10
TIME
LAST
STAGE
HOLD
HTC# 059105-00D
[ ]
BACK ▲ ▼ SAVE
--- LEAD STAGES --Cond Lead
A
Non-Cond Lead
C
BACK ▲ ▼ SAVE
BACK ▲ ▼ SAVE
-- SYSTEM
TARGET -1.00ooOD = 4.00ooSys
1.00oOD = 3.00oSys
1.00oOD = 2.00oSys
1.00 OD = 1.50 Sys
1.00ooOD = 1.25ooSys
1.00 OD = 1.00 Sys
o
o
1.25oOD = 1.00oSys
1.50oOD = 1.00oSys
2.00oOD = 1.00oSys
3.00oOD = 1.00oSys
4.00 OD = 1.00 Sys
BACK ▲ ▼ SAVE
-------
OFFSET -----+0 oF
[ ]
BACK ▲ ▼ SAVE
-
OUTDOOR
CUTOFF 65 F
]
BACK ▲ ▼ SAVE
o
[
WATER TEMP
70 oF
[ ]
BACK ▲ ▼ SAVE
--
5 oF
-----
MINIMUM
MAXIMUM
min
[
]
BACK ▲ ▼ SAVE
----- SEASON
Winter
Summer
----- SETTINGS 2 ---Standby Time 10min
o
Last Stg Hold 5 F
<Lead Stages>
<Staging Settings>
<Mdlating Settings>
<Day/Night Schdule>
BACK ▲ ▼ SELECT
WATER
TEMP
200 oF
[
]
BACK ▲ ▼ SAVE
- STAGE SETTINGS Reaction Time 2min
Minimum Runtime
2min
BACK ▲ ▼ SAVE
DAY/NIGHT SCHEDULE
Set Time
**:**
Day Schedule 6:00a
Night Schedule
8:00p
BACK ▲ ▼ SAVE
MODULATION SETTINGS
Gain
+0
Lag Delay
0min
Soft-Off Delay45sec
BACK ▲ ▼ SAVE