4. Hardware Installation
Master Control Network
Tally Processors
The tally processor is slightly different because it is a third-party device.
First, connect the tally processor to the master control Ethernet switch. Use the front panel “menu”
of the tally processor to define its IP address (which must be unique on the master control network).
Following that step, you can access the tally processor’s internal configuration software through a
browser on your PC (such as Internet Explorer). To launch the software, type in the box’s IP
address as the URL. Perform configuration as required and as directed in the Tally Processor User’s
Guide.
You will have to fabricate cables to the tally processor’s GPIs (up to 32 inputs) and GPOs (up to 32
outputs) connecting them to the appropriate switches and circuits at your facility. See Tally Processor Connectors on page 126.
S
You can connect the GPIs of control panels, MCPMs, and MCEs to the tally processor GPIOs.
The tally processor receives event notification (e.g., preset keyer selected, transition occurred) from
master control. The tally processor sends event commands (e.g., take, keyer on/off, transition) to
master control based on its internal event-monitoring list (which you must configure).
Device Controllers
The DC21 device controller, like the tally processor, is a third-party device. It is a 1RU processor
that functions as an intermediary between your MCEs and devices that require machine control.
Your master control network can have more than one DC21. The configuration of every MCE that
performs machine control identifies the DC21 with which it will communicate. A single DC21
could receive commands from more than one MCE.
Ethernet Connection
First, connect the device controller to the master control Ethernet switch. Use the front panel
“menu” of the device controller to define its IP address (which must be unique on the master control network).
In MasterConfig’s general settings, for each MCE that is to communicate with the DC21, specify
that IP address for the device controller’s address.
You can access the device controller’s internal configuration software through a browser on your
PC (such as Internet Explorer). To launch the software, type in the box’s IP address as the URL.
Perform configuration as required and as directed in the Device Controller User’s Guide.
The device controller receives commands, through the master control network, from the MCE(s)
that have been configured to communicate with it.
Ports Connections
The DC21 can control up to 4 devices on its 4 serial ports using one of 3 protocols: Sony, Odetics,
or VDCP. It can control up to 16 other devices with 100 ms start and stop pulses on its GPO lines.
The devices you connect on the serial ports must, of course, recognize one of the available protocols. The device controller’s DE9 pinout is shown in Device Controller Connectors on page 127.
Under master control, the DC21’s 32 GPO ports are paired (1,2), (3,4) and so on up to (31,32). This
gives you control over 16 devices. The odd port in the pair carries a start pulse and the even port in
74