Download Acson A5ACV 55 CR Specifications
Transcript
MODEL LEAVING WATER TEMP (°C) MODEL : A5ACV 210CR - COOLING MODEL LEAVING WATER TEMP (°C) 4 5 6 A5ACV 210CR 7 8 9 10 MODEL LEAVING WATER TEMP (°C 4 5 6 A5ACV 210CR 7 8 9 10 4 5 6 A5ACV 210CR 7 8 9 10 AMBIENT TEMPERATURE ON CONDENSOR (°C) 19 20 25 28 WATER AVAIL. PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP 3 kW kW A kW kW A kW kW A kW kW A m /hr kPa W A 63.80 66.15 68.03 70.10 70.40 70.89 70.92 17.42 17.43 17.44 17.46 17.49 17.52 17.56 34.9 34.9 34.9 35.0 35.0 35.1 35.2 62.40 65.03 67.15 68.77 69.87 70.46 70.55 17.76 17.78 17.81 17.84 17.88 17.92 17.97 35.5 35.6 35.7 35.7 35.8 35.9 36.0 59.43 62.45 64.91 66.29 68.18 68.98 69.23 18.72 18.74 18.78 18.85 18.95 19.07 19.21 37.5 37.5 37.6 37.7 37.9 38.2 38.5 57.03 60.19 62.80 64.51 66.38 67.33 67.75 19.53 19.66 19.79 19.90 20.00 20.09 20.17 39.1 39.4 39.6 39.8 40.0 40.2 40.4 8.31 8.80 9.22 9.58 9.86 10.08 10.23 245 234 225 216 209 203 199 1232 1259 1282 1301 1317 1328 1336 2.2 2.3 2.3 2.3 2.4 2.4 2.4 AMBIENT TEMPERATURE ON CONDENSOR (°C) 30 32 35 40 WATER AVAIL. PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP kPa W A 245 234 225 216 209 203 199 1232 1259 1282 1301 1317 1328 1336 2.2 2.3 2.3 2.3 2.4 2.4 2.4 kW kW A kW kW A kW kW A kW kW A m3/hr 55.35 58.53 61.19 62.72 64.92 65.98 66.52 20.11 20.34 20.52 20.67 20.76 20.82 20.83 40.3 40.7 41.1 41.4 41.6 41.7 41.7 53.61 56.76 59.42 61.12 63.25 64.42 65.10 20.72 20.94 21.13 21.28 21.39 21.46 21.50 41.5 41.9 42.3 42.6 42.8 43.0 43.0 50.87 53.87 56.45 58.62 60.37 61.70 62.62 21.70 21.94 22.14 22.30 22.42 22.49 22.52 43.4 43.9 44.3 44.6 44.9 45.0 45.1 46.01 48.46 50.70 52.41 54.54 56.14 57.54 23.51 23.73 23.91 24.06 24.17 24.25 24.29 47.1 47.5 47.9 48.2 48.4 48.5 48.6 8.31 8.80 9.22 9.58 9.86 10.08 10.23 AMBIENT TEMPERATURE ON CONDENSOR (°C) 42 46 WATER AVAIL. PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP kW kW A kW kW A m3/hr kPa W A 43.95 46.08 48.11 49.83 51.85 53.56 55.17 24.29 24.48 24.64 24.77 24.88 24.96 25.02 48.6 49.0 49.3 49.6 49.8 50.0 50.1 39.65 40.97 42.44 44.07 45.85 47.78 49.87 25.96 26.05 26.14 26.23 26.33 26.42 26.51 52.0 52.1 52.3 52.5 52.7 52.9 53.1 8.31 8.80 9.22 9.58 9.86 10.08 10.23 245 234 225 216 209 203 199 1232 1259 1282 1301 1317 1328 1336 2.2 2.3 2.3 2.3 2.4 2.4 2.4 65