Download Acson A5ACV 55 CR Specifications

Transcript
MODEL
LEAVING WATER TEMP (°C)
MODEL : A5ACV 210CR - COOLING
MODEL
LEAVING WATER TEMP (°C)
4
5
6
A5ACV 210CR 7
8
9
10
MODEL
LEAVING WATER TEMP (°C
4
5
6
A5ACV 210CR 7
8
9
10
4
5
6
A5ACV 210CR 7
8
9
10
AMBIENT TEMPERATURE ON CONDENSOR (°C)
19
20
25
28
WATER
AVAIL.
PUMP
PUMP
COOL
POWER
RUNNING
COOL
POWER
RUNNING
COOL
POWER
RUNNING
COOL
POWER
RUNNING
FLOW
HEAD
INPUT
INPUT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
RATE
PRESS.
POWER
AMP
3
kW
kW
A
kW
kW
A
kW
kW
A
kW
kW
A
m /hr
kPa
W
A
63.80
66.15
68.03
70.10
70.40
70.89
70.92
17.42
17.43
17.44
17.46
17.49
17.52
17.56
34.9
34.9
34.9
35.0
35.0
35.1
35.2
62.40
65.03
67.15
68.77
69.87
70.46
70.55
17.76
17.78
17.81
17.84
17.88
17.92
17.97
35.5
35.6
35.7
35.7
35.8
35.9
36.0
59.43
62.45
64.91
66.29
68.18
68.98
69.23
18.72
18.74
18.78
18.85
18.95
19.07
19.21
37.5
37.5
37.6
37.7
37.9
38.2
38.5
57.03
60.19
62.80
64.51
66.38
67.33
67.75
19.53
19.66
19.79
19.90
20.00
20.09
20.17
39.1
39.4
39.6
39.8
40.0
40.2
40.4
8.31
8.80
9.22
9.58
9.86
10.08
10.23
245
234
225
216
209
203
199
1232
1259
1282
1301
1317
1328
1336
2.2
2.3
2.3
2.3
2.4
2.4
2.4
AMBIENT TEMPERATURE ON CONDENSOR (°C)
30
32
35
40
WATER
AVAIL.
PUMP
PUMP
COOL
POWER
RUNNING
COOL
POWER
RUNNING
COOL
POWER
RUNNING
COOL
POWER
RUNNING
FLOW
HEAD
INPUT
INPUT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
RATE
PRESS.
POWER
AMP
kPa
W
A
245
234
225
216
209
203
199
1232
1259
1282
1301
1317
1328
1336
2.2
2.3
2.3
2.3
2.4
2.4
2.4
kW
kW
A
kW
kW
A
kW
kW
A
kW
kW
A
m3/hr
55.35
58.53
61.19
62.72
64.92
65.98
66.52
20.11
20.34
20.52
20.67
20.76
20.82
20.83
40.3
40.7
41.1
41.4
41.6
41.7
41.7
53.61
56.76
59.42
61.12
63.25
64.42
65.10
20.72
20.94
21.13
21.28
21.39
21.46
21.50
41.5
41.9
42.3
42.6
42.8
43.0
43.0
50.87
53.87
56.45
58.62
60.37
61.70
62.62
21.70
21.94
22.14
22.30
22.42
22.49
22.52
43.4
43.9
44.3
44.6
44.9
45.0
45.1
46.01
48.46
50.70
52.41
54.54
56.14
57.54
23.51
23.73
23.91
24.06
24.17
24.25
24.29
47.1
47.5
47.9
48.2
48.4
48.5
48.6
8.31
8.80
9.22
9.58
9.86
10.08
10.23
AMBIENT TEMPERATURE ON CONDENSOR (°C)
42
46
WATER
AVAIL.
PUMP
PUMP
COOL
POWER
RUNNING
COOL
POWER
RUNNING
FLOW
HEAD
INPUT
INPUT
CAP.
INPUT
CURRENT
CAP.
INPUT
CURRENT
RATE
PRESS.
POWER
AMP
kW
kW
A
kW
kW
A
m3/hr
kPa
W
A
43.95
46.08
48.11
49.83
51.85
53.56
55.17
24.29
24.48
24.64
24.77
24.88
24.96
25.02
48.6
49.0
49.3
49.6
49.8
50.0
50.1
39.65
40.97
42.44
44.07
45.85
47.78
49.87
25.96
26.05
26.14
26.23
26.33
26.42
26.51
52.0
52.1
52.3
52.5
52.7
52.9
53.1
8.31
8.80
9.22
9.58
9.86
10.08
10.23
245
234
225
216
209
203
199
1232
1259
1282
1301
1317
1328
1336
2.2
2.3
2.3
2.3
2.4
2.4
2.4
65