Download Westinghouse W-007 Specifications
Transcript
EV Inverter Operating Manual Table 13.2 Automatically and Manually Recoverable Errors Display OCS OCD Error Overcurrent at start OVC OHC 1. Motor winding and frame short circuit 2. Motor and ground short circuit 3. Power module is damaged Remedy 1. Check the motor 2. Check the wiring 3. Replace the power module Overcurrent at deceleration The preset deceleration time is set Set a longer deceleration time (Parameter F02) too short Overcurrent at acceleration 1. Acceleration time is set too short 2. The capacity of the motor exceeds the capacity of the inverter 3. Short circuit between the motor winding and frame. 4. Short circuit between motor wiring and earth 5. IGBT module is damaged OCA OCC Cause Overcurrent during run Overvoltage during operation/ deceleration 1. Transient load change 2. Transient power change 1. Set a longer acceleration time (Parameter F01) 2. Replace the inverter with the same or greater capacity as that of the motor 3. Check the motor 4. Check the wiring 5. Replace the IGBT module Increase inverter capacity 1. Set a longer deceleration time (Parameter F02) 1. Deceleration time is set too low 2. Add a braking resistor or braking or excessive load inertia unit 3. Add a reactor to the input line 2. Input voltage varies widely side 4. Increase inverter capacity 1. Check if there are any problems with the motor load 1. Excessive motor load 2. Increase inverter capacity Excessive heat sink temperature during 2. Ambient temperature too high or 3. Improve ventilation conditions operation poor ventilation 4. Check the setting value of parameter C13 ___________________________________________________________________________ TECO – Westinghouse Motor Company 56