Download DriSteem XT Specifications
Transcript
Installation Piping: XT steam blowers Figure 17-1: Piping from XT humidifier steam cylinders to XTSBs with Y connectors * Water seal is required, whether condensate is piped to open drain or returned to humidifier fill cup. XTSB-50 Plastic tie Pitch 2”/ft (15%) minimum 1½” (DN40) steam hose (provided) Hose clamp (provided) Y connector (provided) Hose clamp Hose clamp (provided) Condensate hose (provided) 7” (178 mm) water seal Plastic tie OM-7604 To open drain or humidifier fill cup* XT-75 To open drain or humidifier fill cup* Maximum recommended distance between humidifier and XTSB is 10” (3 m). XTSB-50 Plastic tie Pitch 2”/ft (15%) minimum 1½” DN40 steam hose (provided) Hose clamp (provided) Y connector (provided) Hose clamp Hose clamp (provided) Condensate hose (provided) 7” (178 mm) water seal Plastic tie To open drain or humidifier fill cup* mc_091010_0940 XT-150 To open drain or humidifier fill cup* OM-7605 DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 17