VLT ® 2800 Series
Is active if the frequency is lower than 0.1 Hz.
342
Terminal 46, max. pulse scaling
(DO 46 MAX. PULS)
Value:
150 - 10000 Hz
5000 Hz
Function:
This parameter is used for setting the pulse output signal's maximum frequency.
Description of choice:
Set the required frequency.
343
The counter function is activated (starts timing) at the
flank of the start signal (when it changes from stop to
start).
Speed compensated stop. To stop at precisely the
same point, regardless of the present speed, a stop
signal received is delayed internally when the present
speed is lower than the maximum speed (set in parameter 202).
Reset. Counter stop and Speed-compensated stop can
be combined with or without reset.
Counter stop with reset [1]. After each precise stop the
number of pulses counted during ramp down 0 Hz is
reset.
Counter stop without reset [2]. The number of pulses
counted during ramp down to 0 Hz is deducted from
the counter value in parameter 344.
Precise stop function
(Precise stop)
344
Value:
Precise ramp stop (normal)
Counter stop with reset
(Count stop reset)
Counter stop without reset
(Count stop no reset)
[2]
Speed-compensated stop (Spd cmp stop)
[3]
Speed-compensated counter stop with reset
(Spd cmp cstop w. res)
[4]
Speed-compensated counter stop without reset
(Spd cmp cstop no res)
(Pulse count pre.)
[0]
[1]
[5]
Function:
In this parameter you select which stop function is performed in response to a stop command. All six data
selections contain a precise stop routine, thus ensuring a high level of repeat accuracy.
The selections are a combination of the functions described below.
NB!
Pulse start [8] may not be used together
with the precise stop function.
Description of choice:
Precise ramp stop [0] is selected to achieve high repetitive precision at the stopping point.
Counter stop. Once it has received a pulse start signal
the frequency converter runs until the number of pulses programmed by the user have been received at
input terminal 33. In this way an internal stop signal will
activate the normal ramp down time (parameter 208).
Counter value
Value:
0 - 999999
100000 pulses
Function:
In this parameter you can select the counter value to
be used in the integrated precise stop function (parameter 343).
Description of choice:
The factory setting is 100000 pulses. The highest frequency (max. resolution) that can be registered at
terminal 33 is 67.6 kHz.
349
Speed comp delay
(SPEED COMP DELAY)
Value:
0 ms - 100 ms
10 ms
Function:
In this parameter the user can set the SYSTEM's delay
time (Sensor, PLC, etc.). If you are running speedcompensated stop, the delay time at different frequencies has a major influence on the way in which you
stop.
Description of choice:
The factory setting is 10 ms. This means that it is assumed that the total delay from the Sensor, PLC and
other hardware corresponds to this setting.
= factory setting, () = display text, [] = value for use in communication via serial communication port