Download Econar GeoSource 2000 Operating instructions
Transcript
Figure 2 – Open Loop Water Plumbing The heat pump should never be operated with flow rates less than specified. Low flow rates or no flow may result in freezing water in the water to refrigerant heat exchanger. This will cause the unit to shut down on lowpressure lockout. If the unit locks out, verify that the unit has the required flow and reset the unit by shutting off power to the unit for one minute. I DO NOT continually reset the unit, if the unit locks out more than once call your service professional. ( Continued reset of the unit can freeze water inside the water coil to the point of rupturing the water coil. 1. Open Loop Freeze Protection Switch Heat pump installations on open loop systems, using a non-antifreeze protected water source during the heating mode, require the use of a freeze protection switch. If the water supply to the heat pump is interrupted for any reason, continued operation of the compressor would cause the water remaining in the water-to-refrigerant heat exchanger to freeze and rupture the copper inner tube. The freeze protection switch (ECONAR Part # 75-1028) will shut the unit down before freezing can occur and protect the heat pump against loss of flow. A freeze protection switch must be field installed on open loop GeoSource 2000 heat pumps before the warranty can be registered on the heat pump. The switch mounts on the compressor’s suction line and is wired to terminals on the controller (from X to FP). After the freeze protection switch is installed, the J4 jumper must be removed from the controller to activate the switch. The low pressure switch now locks the unit off at 35 psi pressure in the heating mode. 6 2. Water Coil Maintenance Water quality is a major concern for open systems. Problems can occur from scaling, particle buildup, suspended solids, corrosion, pH levels outside the 7-9 range, or biological growth. If poor water quality is known to exist in your area, a cupro-nickel water coil may be required when ordering the system, or installing a closed loop system may be the best alternative. Water coil cleaning on open loop systems may be necessary on a regular basis. Depending on the specific water quality issue, the water coil can be cleaned by the following methods: a. Freeze Cleaning (Scale deposits, particle buildup) I. Before using the freeze cleaning procedure, verify that it needs to be done. Answer the following questions to determine if servicing is required. 1. Determine and verify that the required water flow rate in GPM is both present and correct. 2. Determine the temperature differential of the water. Under normal conditions, there should be a temperature difference of about 10-15 degrees between the supply side and discharge side. If the temperature difference is 8 degrees or less, consideration should then be given to cleaning the water coil heat exchanger. II. If cleaning of the water coil is indicated, please carefully follow the steps listed below to utilize the freeze cleaning method.