Download dixell IC200CX Series Technical data
Transcript
Ichill 200CX EVO rev 1.1 14/11/2013 • the parameter CO62≠0 the compressor is forced to works at maximum power and then it modulates the power according to the regulation request It is possible to limit the output % of the inverter compressor in Chiller, Heat pump and Sanitary hot water: o maximum % output inverter in Chiller (parameter CO79) o maximum % output inverter in Heat pump (parameter CO80) o maximum % output inverter in Sanitary hot water (parameter CO81) COMPRESSOR INVERTER CONTROLLED OPERATING MODE: CHILLER At the start up the compressor is forced to work at CO61 speed for CO60 seconds. COMPRESSOR INVERTER CONTROLLED OPERATING MODE: HEAT PUMP At the start up the compressor is forced to work at CO61 speed for CO60 seconds. Pag. 45 of 151