Shelf Management Alarm Module The deltaT set point is calculated as follows: Set Point S1 S2 T2 T1 Inlet Air Temperature For ambient air temperatures at or below 25°C (default T1), the deltaT set point is set to 20°C (default S1). For ambient air temperatures at or above 55°C (default T2), the deltaT set point is set to 10°C (default S2). For ambient air temperatures between T1 and T2, the deltaT set point is calculated using the following algorithm: S1 + AXP 1410 Installation and Use (6806800H70D) S2 - S1 (T inlet - T1) T2 - T1 181