Download Samson S2000 Operating instructions
Transcript
Start-up – Settings Limiting the signal pressure: Reading direction for left attachment of pneumatic connections Pressure limit Default: No If the displayed data appear upside down, proceed as follows: Turn → Code 16 Turn → Code 2 Press → Code 16 blinks. Press → Code 2 blinks. Turn → Required direction Turn until the required pressure limit (1.4/2.4/3.7 bar) appears. Press 7.4 to confirm reading direction. Limiting the signal pressure If the maximum actuator force may cause damage to the valve, the signal pressure must be limited. Enable configuration at the positioner before activating the pressure limit function: Note: If no settings are entered within 120 seconds, the enabled configuration function becomes invalid. Press ting. 7.5 to confirm the pressure limit set- Checking the operating range of the positioner To check the mechanical attachment and the proper functioning, the valve should be moved through the operating range of the positioner in the manual operating mode with the manual set point. Selecting manual operating mode: Operating mode Default MAN Configuration enabled Default: No Turn → Code 0 Turn → Code 3, display: No Press → Code 0 blinks. Press → Code 3 blinks. Turn → MAN Turn → YES Press → display Press . The positioner changes to the manual operating mode. 58 EB 8384-4 EN