Download Worcester DANESMOOR Technical data
Transcript
3. Technical Data Table 1 SPECIFICATIONS MODEL 12/19 POWER SUPPLY 230V 50Hz HEATING FLOW 22mm HEATING RETURN 22mm HEIGHT 600mm WIDTH 420mm DEPTH 315mm standard (285mm optional) 1/4 inch BSP FUEL LINE FLUE REQUIREMENT RS Telescopic (Supplied with appliance) MAXIMUM STATIC HEAD 30m (98 ft.) PRIMARY WATER CAPACITY 6.5 litres (1.4 gal) WEIGHT (DRY) 76Kg (167lbs) WEIGHT (WET) 82.5Kg (182lbs) BURNER Electro Oil Inter B9C WATER SIDE RESISTANCE 10°C Difference 40 mbar WATER SIDE RESISTANCE 20°C Difference 10 mbar EXIT FLUE GAS MASS FLOW 33kg/h CONTROL THERMOSTAT RANGE 55°C minimum cut in to 82°C maximum cut out CONTROL THERMOSTAT DIFFERENTIAL 5°C HIGH LIMIT THERMOSTAT BREAK POINT 100 +0/-6°C MANUAL RESET THERMOSTAT BREAK POINT 110 +0/-6°C DUCT MANUAL RESET THERMOSTAT BREAK POINT 100 +0/-6°C FROST THERMOSTAT RANGE 5°C cut in to 10°C cut out Fig. 1. Pipework dimensions inside the property (all dimensions are millimeters) 236 (315mm Standard) 206 (285mm Optional) To the inside of the pipe end stop 288 26 26 100 SIDE VIEW WALL RETURN FLOW FRONT VIEW 12/19 Table 2. Electro Oil Inter B9C Burner (See Fig. 28) NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE Fuel** 28 Sec. Kerosene 28 Sec. Kerosene 28 Sec. Kerosene 28 Sec. Kerosene Nozzle Pump Pressure (p.s.i.) 0.4 60°ES 0.5 60°ES 0.5 60°ES 0.6 60°ES 115 105 140 125 Fuel Flow Rate Kg/h l/h 1.11 1.41 1.38 1.75 1.57 1.99 1.76 2.23 Flue Gas Temp. (°C)* 180 200 210 230 %CO2 9.5 10.5 11 11.5 Approx. Air Setting 7.25 8.5 8.75 9 kW 13.3 16.6 18.9 21.1 Appliance Input Output Btu/hr kW Btu/hr 46,000 12 41,000 56,000 15 51,000 65,000 17 58,000 72,000 19 65,000 * NOTE: The flue gas temperature is measured in the flue. The probe should be inserted to a depth of 150mm in the center of the flue. The temperature measured is not an absolute flue gas temperature and is for general guidance purposes only! **NOTE: Class C2 28sec kerosene. NOTE: The pump pressure given is for general guidance only as variations in nozzle output can be up to ± 15%. It is, therefore, essential that the air is adjusted to give the correct CO 2 value. NOTE: The nozzle type used on 28 Sec. Kerosene outputs are nozzles calibrated specifically for use with 28 Sec. Kerosene which gives less variation in nozzle output than the standard 35 Sec. Gas Oil nozzles. However, if a 28 Sec. Kerosene nozzle is not available at servicing or commissioning it is appropriate to install a 35 Sec. Gas Oil nozzle providing the output, spray angle and pattern of the nozzle is the same as the 28 Sec. Kerosene nozzle (e.g. 0.560°ES may be replaced with a 0.560°S). 3