3. Technical Data
Table 1
SPECIFICATIONS
MODEL
12/19
POWER SUPPLY
230V 50Hz
HEATING FLOW
22mm
HEATING RETURN
22mm
HEIGHT
600mm
WIDTH
420mm
DEPTH
315mm standard (285mm optional)
1/4 inch BSP
FUEL LINE
FLUE REQUIREMENT
RS
Telescopic (Supplied with appliance)
MAXIMUM STATIC HEAD
30m (98 ft.)
PRIMARY WATER CAPACITY
6.5 litres (1.4 gal)
WEIGHT (DRY)
76Kg (167lbs)
WEIGHT (WET)
82.5Kg (182lbs)
BURNER
Electro Oil Inter B9C
WATER SIDE RESISTANCE
10°C Difference
40 mbar
WATER SIDE RESISTANCE
20°C Difference
10 mbar
EXIT FLUE GAS MASS FLOW
33kg/h
CONTROL THERMOSTAT RANGE
55°C minimum cut in to 82°C maximum cut out
CONTROL THERMOSTAT DIFFERENTIAL
5°C
HIGH LIMIT THERMOSTAT BREAK POINT
100 +0/-6°C
MANUAL RESET THERMOSTAT BREAK POINT
110 +0/-6°C
DUCT MANUAL RESET THERMOSTAT BREAK POINT
100 +0/-6°C
FROST THERMOSTAT RANGE
5°C cut in to 10°C cut out
Fig. 1. Pipework dimensions inside the property (all dimensions are millimeters)
236 (315mm Standard)
206 (285mm Optional)
To the inside
of the pipe
end stop
288
26
26
100
SIDE VIEW
WALL
RETURN
FLOW
FRONT VIEW
12/19 Table 2. Electro Oil Inter B9C Burner (See Fig. 28)
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Fuel**
28 Sec. Kerosene
28 Sec. Kerosene
28 Sec. Kerosene
28 Sec. Kerosene
Nozzle
Pump
Pressure
(p.s.i.)
0.4 60°ES
0.5 60°ES
0.5 60°ES
0.6 60°ES
115
105
140
125
Fuel Flow
Rate
Kg/h
l/h
1.11
1.41
1.38
1.75
1.57
1.99
1.76
2.23
Flue Gas
Temp.
(°C)*
180
200
210
230
%CO2
9.5
10.5
11
11.5
Approx.
Air
Setting
7.25
8.5
8.75
9
kW
13.3
16.6
18.9
21.1
Appliance
Input
Output
Btu/hr
kW
Btu/hr
46,000
12
41,000
56,000
15
51,000
65,000
17
58,000
72,000
19
65,000
* NOTE: The flue gas temperature is measured in the flue. The probe should be inserted to a depth of 150mm in the center of the flue. The temperature measured is not an absolute flue
gas temperature and is for general guidance purposes only!
**NOTE: Class C2 28sec kerosene.
NOTE: The pump pressure given is for general guidance only as variations in nozzle output can be up to ± 15%. It is, therefore, essential that the air is adjusted to give the correct CO 2 value.
NOTE: The nozzle type used on 28 Sec. Kerosene outputs are nozzles calibrated specifically for use with 28 Sec. Kerosene which gives less variation in nozzle output than the standard
35 Sec. Gas Oil nozzles. However, if a 28 Sec. Kerosene nozzle is not available at servicing or commissioning it is appropriate to install a 35 Sec. Gas Oil nozzle providing the output, spray
angle and pattern of the nozzle is the same as the 28 Sec. Kerosene nozzle (e.g. 0.560°ES may be replaced with a 0.560°S).
3