Download Siemens ITE Specifications
Transcript
MD and ND-Frame Trip Adjustments Figure 1 In = Maximum circuit breaker ampere rating. Ir = Current Rating—a function of continuous ampere adjustment setting expressed in % of In Ig = Ground Fault Pickup—a function of adjustment setting expressed in % of In. Adjustable Continuous Amps Switch Adjustable Long Time Delay Ir = %In Seconds @ 6 x Ir All SMD-SND solid state molded case circuit breakers have an adjustable continuous amps rating switch. Adjustments made to this switch can change the continuous amps rating of the breaker to 20, 30, 40, 50, 60, 70, 80 or 90% of the maximum continuous amps rating (In) of the circuit breaker. See Figure 1 for the possible settings for this switch. SMD/SND models with an adjustable long time delay switch allow for selection of long time delays of fixed time intervals at six times the continuous amps setting (1,). See Figure 1 for the possible settings for this switch. 7