Download Siemens SIMATIC TIWAY 1 Technical data
Transcript
Error Indications. If no error is detected, the ADAPTER GOOD LED will illuminate at the completion of the diagnostics, and will remain illuminated. All other LEDs will be extinguished. If a failure is detected during RESET diagnostics, the ADAPTER GOOD LED flashes two times each second, and an Error Code is displayed on LEDs 2 through 6. For a list of these Error Codes, refer to Table 5-3. The RESET diagnostics will run each time the RESET switch is pressed. Table 5-3 RESET Diagnostic Tests and Error Codes LED PATTERN ERROR 2 3 4 5 6 No Errors 0 0 0 0 0 Diagnostics ROM Error 0 0 0 0 1 RAM Error 0 0 0 1 0 Communications Circuit Error 0 0 1 1 1 PIM Missing or PIM ROM Error 0 1 0 0 0 CPU Error 0 1 0 0 1 –5 V Power Supply Error 0 1 0 1 0 Watchdog Timer Error 0 1 0 1 1 1 = LED Illuminated If your PIM is not installed and the Adapter passes all its diagnostics. Error Code 01000 (PIM Not Installed) will be returned. TIWAY 1 Unilink Adapter Installation and Operation Manual Diagnostic Tests 5-15