Using the PhaseManager Tool Chapter 11 Table 43 - PhaseManager Transitions Type of Transition Description Command A command tells the equipment to do something. For example, the operator pushes the start button to begin production and the stop button to halt production. The PhaseManager tool uses these commands: Reset Stop Restart Start Hold Abort Done Equipment goes to a waiting state when it is finished with what it is doing. You do not give the equipment a command. Instead, you configure your code to signal when the phase state is finished. Fault A fault tells you that something out of the ordinary has happened. You configure your code to look for faults and act if it finds any. If you want to shut down your equipment as quickly as possible when it detects a fault, configure your code to look for that fault and give the abort command if it finds it. Manually Change States You can manually change an equipment phase. To change a PhaseManager state, perform this procedure. 1. Open the Equipment Phase Monitor. 2. Take ownership of the equipment phase by clicking Owners and clicking Yes. 3. Click the command that initiates the state you need (for example, Start or Reset). 4. After you have finished manually changing the state, click Owners to release your ownership. Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 173