Heat
These detectors use two networked thermistors in
a bridge configuration to provide a fast response,
that depends both on absolute
temperature and notes the
change of temperature. The rate
of rise/fixed temperature heat
detectors can be used in areas
where smoke sensors are
unsuitable due to environmental
conditions (smoke, dust etc,).
Such areas include kitchens,
locker rooms, canteens,
garages, loading bays etc.
The integral electronics emulate
conventional fire detector's response curves and
transmit the state to a controller as an alarm
condition.
Rate of Rise
Product Codes Approval
516.052.001.A
LPCB
516.052.001.T
LPCB
516.052.001.Y
LPCB
516.052.013.W
VdS
515453
UL
516.052.031
UL
Branded
ADT
Thorn
Tyco
Wormald
Grinnell
Thorn
Fixed Temperature 60°C
Product Codes Approval
516.052.011.A
LPCB
516.052.011.T
LPCB
516.052.011.Y
LPCB
516.052.033.W
VdS
Branded
ADT
Thorn
Tyco
Wormald
Fixed Temperature 90°C
Product Codes Approval
515455
UL
516.052.022
UL
Branded Model
Grinnell 632H
Thorn
632H
Model
MD601
MD601
MD601
MD613
612H
612H
Model
MD611
MD611
MD611
MD623
Datasheet - Product Code PSF84 “M600/900 Low
Profile Fire Detector Range”
Manual - Vol01B-04-D5 “Detectors Fire Manual”
Ion Chamber Smoke
These detectors react to the visible
and invisible fire aerosols
(products of combustion) and are
therefore capable of detecting the
early presence of hot smouldering
and flaming fires, such as wood,
paper etc.
They are particularly suitable for general
applications in all areas and use a dual ionisation
chamber in which the air is ionised by a single
radioactive source (33k Bq Americium 241). The
presence of smoke in the sampling chamber
causes a change in the balance voltage, between
the two chambers. This is then compared against
an alarm level.
Product CodesApproval
516.050.001.A
LPCB
516.050.001.T
LPCB
516.050.041.W
VdS
516.050.031
UL
515456
UL
516.050.401
Marine
Branded Model
ADT
MF601
Thorn MF601
Wormald MF613
Thorn
612I
Grinnell 612I
Thorn MF601M
Datasheet - Product Code PSF84 “M600/900 Low
Profile Fire Detector Range”
Manual - Vol01B-04-D3 “Detectors Fire Manual”
Technical Specification
Typical Dimensions of Standard 4” Detector
Technical Specification - M601 Series
MF
Weight
134g
Material
Operating Temp.
-20 to +70 oC
Storage Temp.
-25 to +80 oC
Relative Humidity
Quiescent Current(typ)
70µA
Alarm Current(typ)
40mA
Operating Voltage
18-32Vd.c.
*Short Term (<3min) -40 to +120oC
MR
122g
MD
MU
114g
137g
FR 110 Bayblend
-20 to +70 oC
-20 to +70 oC* -20 to +50 oC
-25 to +80 oC
-20 to +70 oC -25 to +70 oC
95% Non-Condensing
60µA
50µA
50µA
36mA
40mA
40mA
18-32Vd.c.
18-32Vd.c.
18-32Vd.c.
Page 45