D2071A | Operations & Installation Guide | 2.0 2.0 Installation Installation Some terminals are wired differently for the stand-alone (Figure 2) and slave applications (Figure 3 on page 9). When you are using the D2071AC, mount the D4103R Enclosure and have a qualified electrician connect a 110 VAC or 120 VAC power source to the black and white leads on the transformer. Before beginning the D2071A installation, ensure the power source is turned off. Figure 2: Stand-Alone Installation S P 1 12 VAC, 20 VA, 60 Hz S P 2 12 VAC, 20 VA, 60 Hz 3 EARTH GND 1 - P 4 BATTERY – + P 5 BATTERY + P 6 INITIATING A1 – S 7 INITIATING A2 – P 8 INITIATING B1 + S 9 INITIATING B2 + 3 5 6 5 P S 10 P 10 11 S 11 P 10 SUPERVISORY HI S 11 SUPERVISORY LO 12 SUPERVISORY HI 13 TBL RELAY NC C 14 TBL RELAY COM NO 15 TBL RELAY NO NC 16 ALARM RELAY NC C 17 ALARM RELAY COM NO 18 ALARM RELAY NO P 11 1 2 3 4 5 6 7 8 4 8 9 10 2 11 NC 7 12 13 - 12 VAC, 20 VA transformer Maximum charging current 300 mA Battery backup (D126 [12 V, 7 Ah] or D1219 [12 V, 2.3 Ah]) Alarm initiating circuit Open = Trouble Short = Alarm Supervisory circuits Mode 3 (Alarm [short] = 0 VDC to 1.7 VDC; Normal [resistive] = 1.9 VDC to 5.8 VDC; Trouble [open] = 6.0 VDC to 10.2 VDC) 9 - Mode 2 (Normal = 0 VDC to 1.5 VDC; Alarm [resistive] = 1.8 VDC to 9.0 VDC; Trouble [open] = 9.3 VDC to 13.0 VDC) 10 - Mode 1 (Normal = 0 VDC to 1.5 VDC; Alarm [open] = 1.8 VDC to 13.0 VDC) 11 - 1.8 kΩ EOL resistor 12 - Phone Trouble Relay (maximum rating 2 A at 30 VDC) 13 - Initiating Circuit Alarm Relay (maximum rating 2A at 30 VDC) Note: 8 = Power limited; = Supervised Bosch | 09/04 | 74-06200-000-F