D9412GV4/D7412GV4/D7212GV4
Panel and Area Wide Parameters | en 121
A# Duress Relay
Default:
Selection:
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when a Duress alarm is generated from a keypad assigned to the specified area.
NOTICE!
Burg Time needs a bell period programmed and A# Duress Enable must be Yes. This relay
activates when the Burg Bell starts and deactivates when the Burg Bell time ends. The Burg
Bell pattern has no effect on this relay function.
A# Perimeter Fault
Default:
Selection:
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when a Controlled Perimeter point (P## Type 1) assigned to the specified area is
faulted, regardless of the armed state of the area. This relay provides a steady output until all
Perimeter points in the area return to normal.
NOTICE!
This relay does not activate on interior faults. To detect all area point faults, program all
points as Perimeter points in the area where this relay is assigned.
A# Silent Alarm
Default:
Selection:
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This relay activates when a point assigned to the specified area and programmed for P##
Silent Bell goes into alarm.
NOTICE!
This relay does not activate on interior faults. To detect all area point faults, program all
points as Perimeter points in the area where this relay is assigned.
3.14.2
Panel-Wide Relays
The following eleven relay options activate when they occur anywhere in the control panel.
They are not restricted by area boundaries.
AC Failure
Default:
Selection:
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when the control panel responds to an AC power failure as programmed in AC Fail
Time in Section 3.6 Power Supervision, page 50. This relay automatically resets when AC power
restores.
Bosch Security Systems, Inc.
Program Entry Guide
F.01U.218.312 | 04 | 2012.03