Download Vector VEC12B Installation manual
Transcript
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 23 EXPLANATION OF PARAMETERS (1/7). • Address 000 : V0, V0. At this address is programmed V0 which can also be used as a relevelling speed. Units : Mini : metres per second (m/s) 0,001 m/s Maxi : 0,199 m/s 1/10 of V2 Factory value : • Address 001 : ISO, Relevelling speed. At this address is programmed the relevelling speed. Unit : Mini : metres per second (m/s) 0,000 m/s < V0 Maxi : 0,020 m/s Factory value : • Address 002 : INS, Inspection speed. At this address is programmed the Inspection speed which can also be used as an intermediate speed if V1 is not used. This speed is taken into account when the inspection input (INS/ on K30) is activated (VINS Led lit). Unit : Mini : metres per second (m/s) 0,20 m/s Maxi : 0,60 m/s 0,50 m/s Factory value : • Address 003 : V1, Intermediate speed V1. At this address is programmed the Intermediate speed V1. Unit : Mini : Factory value : metres per second (m/s) 0,61 m/s Maxi : 0,61 m/s < V2