Download Vector VEC12B Installation manual
Transcript
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter I - page 25 FUNCTION OF THE SW1, SW2, SW4-SW5, SW7, SW9-SW10SW11 & SW12 JUMPERS OF THE BG15 BOARD SW1 SW2 SW3 3 3 2 2 1 1 SW4 SW5 3 3 2 2 1 1 SW4 SW5 When the jumper is present, 24V increase the mass relays. When the jumper is present, 0V increases the mass relays. DOES NOT EXIST. When the jumpers are in the lower (position 1-2) the controller is programmed for use with the P202U tape-head. When the jumpers are in the upper (position 2-3) the controller is programmed for use with the O03 tape-head or the I.L.S proximity switches. SW6 DOES NOT EXIST. 3 2 1 SW7 When the jumper is in the lower (position HYDR) the controller is programmed for use as a HYDRAULIC. 3 2 1 SW7 When the jumper is in the upper (position TRAC) the controller is programmed for use as a TRACTION. SW8 DOES NOT EXIST. 1 2 3 SW9 SW10 Place the jumper to the right (position 2-3) for a single button - 2 to 8 floors using on the BG15 board only. SW11 SW12 1 2 3 SW9 SW10 SW11 SW12 Place the jumper to the left (position 1-2) for all other situations.