Download Initialization Parameters Technical Bulletin
Transcript
28 Initialization Parameters Technical Bulletin Parameter with Defaults (Cont.) Purpose/Description Modification Method [Metasys] Section (Cont.) FNStyle7=0 Specifies whether FireNet Style 7 wiring is used. If not, Style 4 is used. The default is No. Options are: 0=No 1=Yes AllowBlockAck=0 Specifies whether Fire Alarm Block Acknowledge is used. The default is No. Options are: 0=No 1=Yes Note: U.S. fire systems can use Block Acknowledge for normal, daily operation within a Local Fire Alarm System. Block Acknowledge cannot be used for normal, daily operation within a Proprietary Signaling System; it can only be used for maintenance or commissioning purposes. Refer to the Operator Workstation User’s Manual for details on the Block Acknowledge mode. For information on other countries, check with the Authority Having Jurisdiction (AHJ). ULFireRemindMinutes=30 Specifies the time the Fire System Reminder box waits before moving in front of all windows. The default is 30. HideStartBar=0 Specifies whether the Taskbar and Start button on the Windows main screen are hidden. When the Taskbar and Start button are hidden, the user can continually monitor the Fire OWS system. The default is 0. Options are: 1=Hidden 0=Not Hidden This parameter is automatically set to 1 during Fire OWS installation and should remain at 1 during normal operation. This function is available only on Windows 98 Second Edition (SE) workstation. ULFireWatchdogPort=888 Added manually on the FIREOWS-PC-02 only, for use with Metasys PMI Release 9.01 or later software with PMI patches and Fire OWS Release 9.03 or later. This parameter is added in the event of a complete software reload. Continued on next page . . . These parameters are added automatically when you load FireNet OWS software.