Transcript
-40 °C ... +70 °C
Storage/shipping
Relative humidity
IEC 60068-2-30
Air pressure
From 10 to 95 % no condensation
795 ... 1080 hPa
Pollutants
IEC 60068-2-42
SO 2 10 cm 3 /m 3,
IEC 60068-2-43
4 days
H2S 1 cm 3 /m 3 ,
4 days
Criterion
Tested in accordance
Values
with
Ambient mechanical conditions
Protection mode
IP20
Vibrations:
IEC 60068-2-6
5 ... 9 Hz (constant
amplitude 3.5 mm)
9 ... 150 Hz (constant
acceleration 1 g)
Shock
IEC 60068-2-27
18 shocks
(half-sine wave 15g/11 ms)
Drop
IEC 60068-2-31
Drop height 50 mm
Free fall (packaged)
IEC 60068-2-32
1m
Emission(Conducted Emission)
EN 55022
Class B
Emission(Radiated Emission)
EN 55022
Class B
Harmonics(Current Harmonics)
EN 61000-3-2
Flicker(Voltage Fluctuation)
EN 61000-3-3
ESD(Electrostatic Discharge)
EN 61000-4-2
8 kV air discharge
Severity 3
6 kV contact discharge
RF-Field(Radiated Immunity)
EN 61000-4-3
3V/m
Burst(Electrical Fast Transients)
EN 61 000-4-4
1 kV (supply and signal lines)
Surge(Transients comm.&diff.mode)
EN 51000-4-5
0.5kV
Electro-magnetic compatibility (EMC)
(applies only to ELC-AC types)
RF-com.mode(RF
continues
EN 61000-4-6
conducted)
V-dips(Voltage
dips
and
EN 61000-4-11
Interruption)
Cycle time
Cycle time per
<0.01ms
function
320