Download User`s Manual - Fuji Electric
Transcript
6 TROUBLESHOOTING Symptom Possible cause 7. Reaction is slow. Input filter is too large. (Measurement value changes very slowly.) 8. Reading does (1) Input is short-circuited. not change although output (2) Connection with operation terminal is turned is off. ON/OFF. (3) Power for the operation terminal is OFF. (4) Output signal and input signal of the operation unit do not coincide. 9. Key operation Parameter LOC is set to 1, 2, 4, or 5. cannot be performed. Parameter value cannot be changed. 10. SV cannot be (1) Parameter LOC is set to 1 or 4. changed. (2) Setting of values outside the measurement range (parameters Sh1 to SL1) was attempted. 11. Parameter to be Setting has been made to skip the checked or parameters in question with parameters changed does ds00 to ds43. not appear. 12. Auto tuning (1) After auto tuning was started, input cannot be done was set to UUUU. properly. Remedy Decrease the setting of parameter P1TF. When PV2 or AI1 is used, decrease the setting of P2TF or A1TF. Remove the short-circuited part. Connect properly. Set the power to ON. Provide a thermoregulator appropriate for the operation terminal, or provide operation terminal appropriate for the signals from the thermoregulator. Set LOC to 0 or 3. (If LOC is set to 3, setting cannot be made by communication.) Set LOC to 0, 2, 3, or 5. Extend the range of Sh1 and SL1. (Do not extend the range exceeding the values listed in input range table.) Change the setting of the parameter in question in ds00 to ds43. Expand the range of parameters PV1d, PV1F, and PV1B when TPLT =53, 54, and expand the range of parameters UCD1, UCF1, and UCB1 when TPLT = 50, 51, and then do auto tuning again. Restore the SV value to be controlled and then do auto tuning again. Make connections with peripheral devices properly. Set parameter rEV1 properly. (2) After auto tuning was done, SV was changed. (3) Peripheral devices or connections with those devices are faulty. (4) Forward/reverse operation of thermoregulator and the system of control target do not coincide. (5) Control target runs out of time in a Do tuning manually. (Set P1 or PC1 to 0, and perform ON/OFF control.) very slow process (about 17 hours or longer). 13. Overshoot is too - (1) Do auto tuning at ATP1 = LPV large in auto (low PV type AT). tuning. (2) Do tuning manually. - 14. Decimal point TPLT has been set to 50 or 51. Set TPLT to 53 or 54, or change the cannot be decimal point of UCd1. changed. Digital Controller User's Manual 154 See (page) 90 ― 159 ― ― 98 98 54 123 27 55 ― 49 93 55 ― 21 or 27 INP-TN514557-E