5 Troubleshooting
Meaning
Level
Event code
Event name
Assumed cause
10070000 hex
SD Memory
Card Access
Power OFF
Error
The power supply
• The Controller power supply
to the Controller
was turned OFF while the SD
was interrupted durBUSY indicator was lit.
ing access to the
• The power supply to the ConSD Memory Card.
troller was interrupted momentarily while the SD BUSY
indicator was lit.
S
page 5-39
10310000 hex
Incorrect SD
Memory Card
Removal
SD Memory Card
removal processing failed.
S
page 5-40
Maj
Prt
Min
• The SD Memory Card was
removed while the SD PWR
indicator was lit.
Obs
Info
Reference
Errors Related to Controller Operation
Event code
Event name
10200000 hex
User Program/Controller
Configurations and
Setup Transfer Error
Meaning
The user program
or Controller Configurations and
Setup were not
transferred correctly.
Level
Assumed cause
Maj
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during a download
of the user program or the Controller Configurations and
Setup.
Prt
Min
Obs
Info
Reference
S
page 5-41
S
page 5-42
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during online editing.
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during a Clear All
Memory operation.
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during a restore
operation.
• Non-volatile memory failed.
10210000 hex
Illegal User
Program
Execution ID
The user program
execution IDs set in
the user program
and in the CPU Unit
do not match.
• The user program execution
IDs set in the user program and
in the CPU Unit do not match.
• A user program execution ID is
set in the CPU Unit but not in
the user program.
10240000 hex
Illegal User
Program
The user program
is not correct.
• The limit to the number of nesting levels for functions or function blocks was exceeded.
S
page 5-42
10250000 hex
Illegal User
Program/Controller
Configurations and
Setup
The upper limit of
the usable memory
was exceeded or
the user program or
Controller Configurations and Setup is
corrupted.
• The upper limit of the data size
was exceeded.
S
page 5-43
5 - 16
• The main memory capacity was
exceeded.
• Non-volatile memory is deteriorating or has failed.
NX-series CPU Unit Hardware User’s Manual (W535)