Download The ZetaBeam - Zeta Alarm Systems

Transcript
The ZetaBeam
Protection System Plus
User Guide
The ZetaBeam
Reflective optical beam smoke detector user guide
1 Distance and position guidelines
These guidelines are recommendations only and it is important that you refer
to your appropriate governing standards at all times.
When positioning your ZetaBeam there are important factors that you should consider, mainly what
distance you are covering and the optimal position in the building.
What distance?
The standard ZetaBeam is suitable for distances of 5m to 40m to the reflector. If you require 40m to
80m you will need to use the mid range reflector extension kit. For ranges of 80m to 100m you will
require the long range reflector extension kit.
5 to 40 metres the standard zetabeam
The standard ZetaBeam comes boxed with the head unit, low level controller, one reflector, 3mm allen
key and quick start installation guide, this should be used for distances over 5m and up to 40m.
Standard ZetaBeam covers 5m and up to 40m
40 to 80 metres - the standard zetabeam + mid range 40 to 80m kit
For distances of 40 to 80 metres you will need to use the standard
ZetaBeam and a mid range extension kit (the mid range kit comes
with a backing plate and 3 extra reflectors, you will need to add the
reflector from the standard kit to the mid range kit with the screws
provided).
80 to 100 metres - the standard zetabeam + long
range 80 to 100m kit
For distances of 80 to 100 metres you will need to use the standard
ZetaBeam and a long range extension kit (the long range kit
comes with a backing plate and 8 extra reflectors, you will need to
add the reflector from the standard kit to the long range kit with
the screws provided).
What position?
A roof is considered flat unless the height of the apex is greater then 0.6m. If the roof is flat the
ZetaBeam system can be placed anywhere under the roof between 0.3m and 0.6m below the roof, up to
a maximum height of 40m from the floor. The ZetaBeam has a detection area of 7.5m either side of the
beam. If the roof is considered to have an apex, place the ZetaBeam system 0.3m to 0.6m down from
the top of the apex, up to a maximum height of 40m from the floor. The maximum protected area either
side of the beam can be extended by 1% for every degree of roof pitch, see the example below:
0.3m - 0.6m
40m max
2.7m min
Field of view should be a 50cm radius from
the centre or the beam
Flat roof
0.3 -0.6m
15m detection area
Extra coverage due to apex angle
10°
0.3 -0.6m
15 + (15 x 10%) = 15m + 1.5m = 16.5m
8.25m
8.25m
16.5m detection area
Wall
Wall
Min 0.5m
You should always position the beam at least 0.5m away from any protrusion
Note. Careful design consideration should be made when positioning beams and reflectors in
environments that can be susceptible to condensation i.e. warehouses near to water that have areas
open to the outside environment or that are exposed to quick extreme changes in temperature. To assist
with this problem that can affect all beam detectors we produce an anti-fog kit comprising of a specially
coated reflector and lens cover. Individual reflectors are also available. The standard ZetaBeam and
range kits can be supplied as anti-fog sets as a special order.
2 Installing, commissioning and testing
step 1 mounting the head
Screw the head backing plate to the wall - always try to use as sturdy a location as possible, such
as brick or major structural steels (avoid mounting to outer metal cladding etc). Avoid mounting the
head where direct sunlight can shine directly into the ‘eyes’ of the beam (care should be taken when
mounting in glass atriums). Ambient sunlight will not affect the beam.
Also available - unistrut adapter plate
Use this accessory for easy mounting to unistrut fabrication. Holes are predrilled to the correct pitch of the head and conveniently positioned for use
with unistrut.
2 knock-outs are provided on
Wire into system as required (see
both sides. Take care when using
generic wiring diagram on the
drills not to damage the circuit
following page). Ensure that all
board.
wiring is below the level of the
front edge of the box.
Wire to low level controller using
Screw in through holes provided
bottom colour coded terminals.
outside of the rubber seal.
Connect the head
to the base plate by
Screw the head screws
first plugging in the
down with the 3mm
connector. Do not force
allen key provided. Your
in, whitewires should be
wiring should be flush
uppermost. Should you
and not flattened by
forget to connect this
tightening down screws.
the controller screen
will read ERROR.
step 2 mounting the controller
Important mount the controller at eye level and ensure easy access.
Screw in through holes provided outside of the
rubber seal. Wire to head using colour coded
terminals. If this connection is not made ERROR
will appear on the controller, this connection can
be checked by reading the resistance across the
black and grey terminals, they will read 110 ohm if
OK or 220 ohm if not connected properly.
Generic wiring configurations
the zetabeam is a conventional device, below are suggested wiring configurations for single and multi
heads on a zone. the zetabeam can easily be made addressable with the use of a manufacturers
interface and in some cases can also be powered from the loop, ie with the Apollo XP95 switch monitor
with isolator. Most wiring diagrams can be found on our website in more detail and in PDF format, go to
www.zetaalarmsystems.com.
Brown
+ supply (10.2 - 30Vdc)
Blue
- supply (return)
Black
zone +
Grey
zone -
Green
earth (screen)
Supply voltage
12Vdc to 24Vdc + 25% -15%
Quiescent current
3.5mA
Alarm current
3.5mA
Aligning current Normal 3.5mA Fast 17mA
Fault/Alarm relay
2A @ 30Vdc
contact rating
FIRE and EOL components as supplied by the panel
manufacturer
Single head on zone
To fire panel
no
c
nc
no
fault
c
nc
fire
FIRE
EOL
manufactured by
technical support
+44 (0)1582 608000
Lemtronics Sdn. Bhd.
Phase 2, Bayan Lepas
Free Industrial Zone
11900 Penang, Malaysia
Fire LED Auxiliary no relay
contact 2A > 30Vdc used
for External LED switching
fire
controller interface
To controller
external
reset
To controller
To fire panel
fault
c
no
fire
c
nc
fire
external
reset
Lemtronics Sdn. Bhd.
Phase 2, Bayan Lepas
Free Industrial Zone
11900 Penang, Malaysia
FIREmanufactured by
nc
Beams 1,2,3...
controller interface
technical support
+44 (0)1582 608000
no
To controller
Schottky barrier diode 1A 60V
MBR160TR (RS 469-0714 or MBR160RGL (farnel 9556761
fault
c
no
fire
c
nc
fire
external
reset
Lemtronics Sdn. Bhd.
Phase 2, Bayan Lepas
Free Industrial Zone
11900 Penang, Malaysia
FIREmanufactured by
nc
...end of line beam
controller interface
technical support
+44 (0)1582 608000
no
EOL
Multiple beams on a zone
Other wiring
diagrams
See our website for further
diagrams including interfacing
with manufacturers protocols
www.zetaalarmsystems.com
step 3 commissioning
Commissioning the ZetaBeam is a simple procedure outlined in the following step by step explanation.
stage one, language and commissioning speed
1. Important. Do NOT put the reflector up or COVER it if already in place.
2. Power up the unit and you will see
the ZetaBeam PLUS
ver 1.01
3. Access the menu by pressing enter
4. The first screen you see
the screen will default to
Air Quality 0%
Status Fault
or
Air Quality 0%
Status Fire
enter
English
is if you need to change this use the right and left
hand keys to scroll through languages, when you have found your language press enter or if you are
happy with English press the down key to continue. If you have changed the language the system will
continue in your chosen language.
5. Press enter and you will now see the commissioning speed screen. In most cases it is recommended
to use fast mode (in normal mode the system uses 3.5mA, in fast mode it uses 17mA) - if you are
commissioning more than one beam at a time and the system cannot support the extra draw it may
be necessary to use normal mode to prevent excessive current draw. Fast mode allows x4 times
faster motor response and it may be quicker to commission each beam in turn. Once commissioning is
complete the ZetaBeam will automatically revert to normal low power mode - (3.5mA).
6. Use the left and right keys to toggle between fast and normal, the * indicates which mode is
selected. Press the enter key to continue.
left
normal fast*
right
enter
stage two, pre-alignment
7. The next screen is
pre-alignment
this is probably the most important part of setting up your
beam. Pre-alignment sets up the amount of power you need for the distance you are covering and
can indicate if you are receiving unwanted reflections from anything else in the beam path.
8. Press enter to begin pre-alignment. Remember no reflector. You will see the screen below. Take a
moment to understand what the figures on the screen mean.
output signal strength
receiver sensitivity
10.0%
‘X’ - horizontal lense position in degrees
‘Y’ -vertical lense position in degrees
X+0.00°
5%
received signal strength
0% P
Y+0.00°
‘P’ indicates pre-alignment
Receiver sensitivity starts off at 5% and output power starts at 10%. The beam will start by raising its
sensitivity first and can rise all the way up to 100%, after this the output power will rise. The objective of
pre-alignment is to adjust the output power to the correct levels for the distance to be covered. As there
is no reflector we are looking for a reflection off the far wall. Power levels will rise until they reach a
maximum of anything up to 6 to 7% of received signal strength (nb. figures may fluctuate between these
values), once this is achieved the power level will automatically stop rising any further.
By looking at the table below you need to judge if you are receiving enough power to cover the required
distance.
5m.........5%
30m......20%
60m......40%
90m......65%
10m.......10%
40m......25%
70m......50%
100m....75%
20m.......15%
50m......30%
80m.......60%
Note. Anything more than these levels is good and continue down to 9. If you are receiving noticeably
less read on below.
These figures are approximate but if you are receiving noticeably less than these figures you may be
receiving a reflection from an object nearby and not the far wall. By moving the beam (looking at the far
wall) left (x-) right (x+) up (y+) and down (y-) you can move the beam path away from the obstacle. By
doing this you will be able to achieve a suitable output power. In extreme cases it may be necessary to
physically move the beam head to obtain a clear line of sight.
Obstacle
Reflections from nearby objects will
limit the output power and prevent
ability of the beam to cover the
required distance
Roofline
Target wall
Sufficient power for distance
9. Once you are happy with your power readings press enter to accept pre-alignment and confirm
these settings by pressing the right key.
Note. It may be that no reflection is received and power and sensitivity levels rise to their maximum, if
this is the case pre-alignment will automatically register Pre-Align - Complete. Confirm these settings by
pressing the right key.
10.0%
100%
6% P
X+0.00° Y+0.00°
enter
OR If no reflection is seen
you will see this screen.
Press
(right)
to confirm
right
Manual Alignment
enter
Manual
AQ
6%
X+0.00° Y+0.00°
Pre-Align - Complete
(right)
Press
right
Manual Alignment
enter
Manual
AQ
6%
X+0.00° Y+0.00°
stage three, manual alignment
You will now see the manual alignment screen showing anything between 0 and 6%. This is the amount of
received signal with no reflector that the beam is picking up from the environment.
10.NOW place or uncover the reflector on the blank wall directly opposite the beam head ensuring there
is a clear path through any obstructions such as structural steels etc.
It is important that there is a clear line of sight between the reflector and beam head. The beam must
see at least 200mm of clear space around the reflector to enable the beam to see the edges of the
reflector to allow successful auto alignment in the following stage.
200mm of clear space from
the edges of the reflector
Once the reflector is in place and visible there should be a big jump in the received signal (AQ). This
means that the head is seeing and receiving a signal back from the reflector. In most cases this will result
in a received signal of over 100%.
Manual
X+0.00°
AQ
136%
Manual
Y+0.00°
X+0.00°
AQ
13%
Y+0.00°
As long as there is a received signal of over 40% you can move onto the next stage: Auto Alignment,
No.11.If the AQ reading is below 40% it means the head is not seeing the reflector and will abort Auto
Alignment. The next stage is to manually move the beam to achieve an AQ reading of over 40%, ideally
over 100%. The higher the AQ the quicker it will auto align. This is done by manually moving the x and y
motors to obtain a received signal from the reflector.
In the example below we can see that the reflector is below the eye line of the beam head, so in this
case you would need to lower the angle of the beam (-Y) until you receive an AQ of over 40%.
Reflector is lower than the beam head... use -Y to bring the beam onto the reflector
Beam head
Reflector
The beam can be moved on both X and Y axis to a maximum 5 degrees using the left (x-), right (x+),
up (y+) and down (y-) keys. Looking at the reflector this will move the beam across
y+
the reflector like so...Holding the keys down will quickly scroll through to your desired
position, on release of the button the screen will revert to the actual beam position and
can be seen stepping toward the requested position.To confirm the beam is seeing the
x-
x+
reflector covering the reflector at any time should drop the AQ and prove the beam
is on the reflector.
y-
In the example above moving the y axis
Try and achieve as high an AQ as possible, it must be over
down (y-) results in a greater AQ.
40% to auto align. The higher the AQ the quicker the auto
align, above 100% is good.
Manual
X+0.00°
AQ 6%
Y+0.00°
down
Manual AQ 110%
X+0.00° Y-2.26°
down
stage four, auto-alignment
11.Having received an AQ reading of over 40% in manual mode press enter to exit manual and enter
again to go into auto alignment mode.
Auto Alignment
enter
8.7%
67% 103% A
X+0.00°
Y+0.00°
First you will see the sensitivity and power readings drop if the received signal is over 100%. Once at
100% or if the reading is under 100% the ZetaBeam will automatically move its y and x axis until it
centres itself onto the middle of the reflector. It does this by seeing highs and lows as it falls on and off
the reflector (seeing the edges of the reflector) once it has found all the edges it will then calculate and
move to the centre of the reflector.
output signal strength
receiver sensitivity
12.0%
‘X’ - horizontal lense position in degrees
X+3.60°
25%
received signal strength
112% A
‘A’ indicates auto-alignment
Y+4.26°
‘Y’ -vertical lense position in degrees
Auto alignment in ‘fast’ mode will take, on average, 3 minutes and in normal mode up to 30 minutes the
better the beam is aligned before auto alignment (high AQ readings) the shorter the align time. Once
finished Align Complete will appear on the screen, simply press left back to OK and exit.
You will now see this screen AQ may fluctuate a couple of % above and below 100%
Air Quality 100%
Status - NORMAL
Now proceed to step 4 - testing - the final stage of commissioning.
step 4 testing
1. Fault test This is done to confirm that the returned signal is from the reflector. Cover the entire
reflector within one second. If the beam is correctly targeted onto the reflector the AQ will
drop to 0% (max 10%) and will fall into a ‘fault’ condition (after 10 seconds). Amber LEDs
will flash on both the controller and the beam head, the word FAULT will appear on the
display. If the AQ is still above 10% reflections are also being returned from something else
other than the reflector. This should be rectified and a fault test performed again until AQ
drops below 10%.
2. Fire test Having completed the fault test the fire test confirms the functionality of
the beam. Having just covered the reflector completely for the fault test now let the
beam recover to its normal state and then cover half the reflector, in effect restricting the
returned signal to 50%, the beam should then fall into a ‘fire’ condition (after 10 seconds).
Once you have successfully completed both tests your ZetaBeam is
commissioned.
You can now fine tune your beam to suit the environment if needed. Look through the following menus to
see adjustments that can be made.
3 Screen and menu systems
Home screen
Air Quality 100%
Status - NORMAL
This is the screen you would normally see when the beam is commissioned.
Other screens you may see are:
Air Quality 29%
Status - FIRE
FIRE
The air quality level has fallen below the fire threshold setting.
If alarm is set to latching and you need to reset from fire press enter enter to
see this screen:
Alarm Reset
and press enter enter again to reset and return to the
normal screen.
This can also be reset by dropping the power to the beam for 5 seconds. If set
to auto reset it will reset to normal automatically.
FAULT
Air Quality 0%
Status - FAULT
The beam path has been fully blocked within 1 second (used when
ERROR
Air Quality XX
Status - ERROR
No communication with the controller. This could be that the flying
fault testing in commissioning.
lead is not connected, or that the head is not connected to the
controller, this can be checked by reading the resistance across the
black and grey terminals, if connected it should read 110ohms if not
connected at one end this will read 220ohms.
This screen will appear when the beam is performing a self
ALIGN
Air Quality 89%
Status - ALIGN
DIRT
COMP
Status - Dirt Comp
alignment, normally because of building movement.
This is due to the compensation for dirt build up reaching its
maximum - FAULT or FIRE LED may be flashing.
How to use the menu system
Press enter enter to go into the menu system, then press down down to go through the main menu options:
English
Commission
Mode Change
Beam Maintenance
Diagnostics
enter enter here to change languages.
enter enter here to commission ZetaBeam.
enter enter here to make all changes and adjustments to the beam.
enter enter here as part of your routine maintenance.
enter enter here to access power and temperature headings.
Individual menu items
Language
Commissioning
1. The language is factory set to English if this is okay press enter enter to continue
to commissioning or arrow up to return to the home screen. To
change
the language use the right and left keys to change to your preferred language and
press enter to confirm your choice – you will then continue in the language of your
choice. Languages currently available are: English, Dutch, Italian, French, Spanish,
Czechoslovakian and German.
2. Press enter enter to go into commissioning.
enter
Normal
Fast*
enter
Pre-Alignment
enter
X
Y
Pressing right or left changes between normal and fast. It is recommended in most
cases to use fast mode (in normal mode the system uses 3.5mA, in fast mode it uses
17mA) - if you are commissioning more than one beam at a time and the system
cannot support the extra draw it may be necessary to use normal mode to prevent
excessive current draw. Fast mode allows x4 times faster motor response and it may
be quicker to commission each beam in turn. Once commissioning is complete the
ZetaBeam will automatically revert to normal low power mode - (3.5mA).
Press enter enter to start pre-alignment. In pre-alignment you should ALWAYS
COVER THE
REFLECTOR. Starting at 10% power and 10% receiver sensitivity,
the receiver sensitivity will automatically increase to a maximum of 100% then the
output power will increase. These settings will automatically stop when a received
signal strength reaches 6% - this received signal is the returned strength of the output
signal without a reflector (if no return signal is received the beam will reach full
power and the screen will say Pre-Align - complete). If you don’t receive high enough
output power and receiver sensitivity readings this will usually be because you are
receiving a reflection from an object nearby - use the left, right, up and down keys
to avoid the obstruction. When happy with your readings press enter and confirm by
pressing the right button, this will take you to manual alignment - if you wish to abort
Pre-Align press the left button.
enter
Manual Alignment
enter
X
Y
Press enter enter to go into manual alignment - NOW THE REFLECTOR CAN BE
PLACED
OR THE COVER CAN BE REMOVED. You should see a large jump in
signal strength. If no jump is seen use the X and Y keys to locate the reflector (the
better the single strength the better the beam is aligned) try to achieve a figure of
around 100% or over for optimum auto alignment times - you must achieve a signal
strength over 40% to start auto alignment. Press enter to okay this and go to auto
alignment.
enter
Auto Alignment
Press enter enter to start auto-alignment. The beam will calibrate its power and
search for
the edges of the reflector – adjusting its power as it aligns itself
onto the reflector. Once it has found all four edges twice it will then centre itself
on the middle of the reflector and the screen will say align complete. Press enter to
return to the home screen. If you see align aborted this means something has crossed
the beam path of the received signal and the signal has dropped out. Press back / left
to return to auto alignment.
Mode Change
3. Here we can make changes to how the beam behaves. Press enter enter to go into
mode change and the sub menus.
enter
Threshold
Time to fire
Time to fault
Auto reset
Align On/Off
Align Time
Threshold. Use the right and left keys to increase or decrease the beams sensitivity.
It is factory set at 35% (meaning the received signal has to drop by 35% to trigger
the fire relay. This sensitivity can be adjusted between 25% (sensitive) and 50% (less
sensitive) (press enter to return to mode change or down to go to time to fire).
Time to fire. Here we can adjust how long the beam has to be in fire before the fire
relay is triggered. This is factory set at 10s, you may want to increase this if there is
something that may momentarily obscure the beam path (birds / forklift truck) this
can be adjusted between 2 and 30 seconds by using the right and left keys (press
enter to return to mode change or down to go to time to fault).
Time to fault. Here we can adjust the time to fault between 2 and 60 seconds
(factory set at 10 seconds). For a beam to go into fault the beam path must be totally
blocked within ONE second. By using the right and left keys (press enter to return to
mode change or down to go to auto reset).
Auto reset. The beam is factory set to auto reset when the received signal raises
above the fire threshold hysteresis. This can be set to latching if your system requires
this. Change by using the right and left keys (press enter to return to mode change or
down to go to align on / off).
Align on / off. You may want to turn the auto alignment function off, for example,
in an environment that often gets filled with welding smoke, the auto align function
kicks in when the received signal drops below 90%, the point that the beam
automatically checks for building movement. The beam will try to align through the
smoke which could be a problem if it is unable to see the edges of the reflector. Use
the right and left keys to turn off and on. When turning this function off extra care
should be taken to ensure that the beam head is on a sturdy fixing ie., brick wall or
major structural steel. Auto alignment will still function in commissioning (press enter
to return to mode change or down to go to align time).
Align time. This is factory set to 4hrs, you can adjust this, by using the right and left
keys, between 0 to 12 hours depending on your environment (press enter to return to
mode change or down to go to green flashing light).
Green Flashing
Light On/Off
Phase
Hysteresis
Beam Maintenance
Green flashing light on / off. By using the right and left keys you can turn the green
flashing LED, located on the head and controller, on or off. This is a useful way of
identifying the beam head you are working with (press enter to return to mode
change or down to go to phase).
Phase. When using multiple beams that face each other the beam output signals could
phase together and can cause unreliable readings, by setting each beam to phase
differently alleviates this problem. Use the right and left keys to give each beam a
different phase pattern (length between output beam sample times) you can choose
between 0 (default setting) and 6 (press enter to return to mode change or down to
go to hysteresis).
Hysteresis. Changing the hysteresis will change the delay in returning from a fire state
back to a normal state, for example, the beam is factory set at 15% so if the beam
falls into fire at 65% (35% threshold) it has to recover 15% to 80% before it returns
to normal. This action prevents small fluctuations in returned signal causing the
beam to fall in and out of a fire state. This can be adjusted between 1% and 40% by
using the right and left keys (press enter to return to mode change or down to go to
compensation fire / fault).
4. Press enter to go into beam maintenance.
enter
Dirt Comp
Dirt Comp. This screen shows how much the beam has compensated for dust buildup on the beam head and reflectors, ALWAYS take a note of this value as part of your
routine maintenance to see any build-up pattern, if you see figures above +50% you
should clean both the lens face and the reflectors (once cleaned you should instigate
an auto alignment to re-calibrate the beams settings).
It is possible that you may see a negative number here, this can happen when the
ZetaBeam has been commissioned in a ‘dirty’ atmosphere such as builders dust which,
once cleared, the beam then compensates for. To reset, perform an auto alignment to
re-calibrate the beam (press enter to return to beam maintenance or down to go to
event counts).
Alarm & Fault
Event Counts
Event counts. Here we can see how many times the beam has gone into fire or fault
since the beam was commissioned or since the event log was last cleared.
Press enter enter to clear events.
Press left/back left/
back to return to beam maintenance or down to go to self test.
Self Test
Self test.
Press enter enter to perform a fire test, this works by running a test algorithm to
lower the
output power, the receiver sees this as obscuration. When the
received signal drops below the threshold point the beam will trip the fire relay – this
relay will not trip until the time to fire has passed which could be anything between 2
and 30 seconds.
Press left / back left/
back to end test, the fire test should show on the panel. Press left
/ back to return
to beam maintenance or down to go to on / off.
On / Off
On / off. If something needs to be maintained in the beam path use the right and left
keys to turn the system on and off.
This will show as a fault on the panel.
Press enter enter to return to beam maintenance.
Diagnostics
5. Press enter enter to go into diagnostics.
enter
IR Power
RX Sensitivity
Temperature
Temp Comp XX%
IR power. This screen shows the amount of output power that is being transmitted. It
can be increased or decreased by using the right and left keys (press enter to return
to diagnostics or down to go to RX sensitivity).
RX sensitivity. This screen shows the receiver sensitivity and can be changed by
using the right and left keys (press enter to return to diagnostics or down to go to
temperature).
Temperature. Here we can see the temperature at the beam head and the amount of
compensation being made for temperature (no adjustments can be made here).
Press enter enter to return to diagnostics.
technical specifications
Electrical Specifications:
Supply Voltage. 10.2 to 40 VDC
Supply Current. 3.5mA (constant current)
in all operational states
Constant Current. 17mA (constant current)
in fast commissioning
Environmental Specifications:
Temperature. -10°C to +55°C
Humidity. 10 to 95% RH Non-condensing
Protection Index. IP65 when suitably
mounted and terminated
Mechanical Specifications:
Beam Head.
180mmH x 155mmW x137mmD
Weight 1.1Kg
Controller.
185mmH x 120mmW x 62mmD
Weight 0.55g
40KIT80 Mid-Range Reflector.
293mmH x293mmW x 5mmD
Weight 0.8Kg
80KIT100 Long Range Reflector.
394mmH x 394mmW x 5mmD
Weight 1.8Kg
Adapter.
270mmH x 250mmW x 5mmD
Weight 0.6g
(mounts the Beam Head onto unistrut)
Optical Specifications:
Optical Wavelength. 870nm
Maximum Angular Alignment. ±5°
Maximum Angular Misalignment.
(static not auto-aligning)
Beam Head ±0.3° Reflector ±2°
Operational Specifications:
Protection Range:
ZetaBeam.
Standard Product 5 to 40 metres
40KIT80.
Mid-Range Reflector Kit 40 to 80 metres
80KIT100.
Long Range Reflector Kit 80 to 100 metres
Alarm Sensitivity Levels:
25%(1.25dB) to 50%(3dB) in 1%(0.05dB)
increments (default 35% (1.87dB))
Alarm Condition:
Obscuration drops to below pre-defined
sensitivity level.
Time to Alarm Condition adjustable
2 to 30 seconds in 1 second increments
(default 10 seconds)
Alarm Indication:
Controller Status – FIRE
Controller Red Flashing LED
Head Red Flashing LED
Alarm Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
Test/Reset Features:
Beam test function by controller
Alarm latching/auto-reset selectable
(default auto-reset)
Alarm reset in latching mode by controller reset
function, removing power for >5 seconds, apply 12 to 24
VDC to reset connections in Beam Head.
Fault Sensitivity Level:
90%
Fault Condition:
Obscuration drops to below the fault
sensitivity level within 1 second
Power Down or Supply Voltage < 9 VDC
Commissioning modes, Pre-Alignment
and Auto Alignment
Beam turned off during Beam Maintenance Time to Fault
Condition adjustable,
2 to 60 seconds in 1 second increments
(default 10 seconds)
Fault Indication:
Controller Status – FAULT
Controller Yellow Flashing LED 1 Second
Head Yellow Flashing LED 1 Second
Fault Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
Normal Condition:
Obscuration level is above the
Alarm sensitivity level
Controller Status – NORMAL
Controller Green Flashing LED
Programmable on/off
Head Green Flashing LED
Programmable on/off
Auto-align/Beam Contamination
Compensation:
Auto-align during normal operation if obscuration drops
below 90% for the duration of the align time set (doesn’t
effect normal operating mode).
Beam Contamination Compensation 4 hour monitoring.
Compensation data available at the controller