Chapter 6 - Parameter Description [APP]
1st Functions
[Stall Level]
FU1-61
[ETH 1min]
FU1-62
[ETH cont]
FU2-43
Motor rated current
[Rated-Curr]
Description
level
ETH level for 1
minute
ETH level for
continuous
Note: Sleep function is not operated if the Sleep
Delay Time (APP-29) set to ‘0’.
Actual
quantity
Wakeup level
(APP-29)
Tartget
Time
The 1st functions are applied if the assigned
multifunction terminal is not defined as ‘2nd Func’
nor ON. The 2nd function parameters are applied
when the multifunction input terminal set to ‘2nd
Func’ is ON. Parameters not listed on the table above
are same as the 1st function.
Freq.
t<APP-27
Sleep delay
(APP-27)
Sleep freq
(APP-28)
Time
Main
motor
Stop
☞ Caution: Exchange the motor connection from
the 1st motor to the 2nd motor or the opposite when
the motor is stopped. Over voltage or over current
fault may occur when the motor is exchanged during
operation.
Start
[Sleep Operation]
APP-30 ~ APP-39: 2nd Functions
APP►2nd Acc time
30
5.0 sec
Factory Default:
31
10.0 sec
Acceleration time
Deceleration time
Base Frequency
Volts/Hz mode
Forward torque
boost
Reverse torque
boost
Stall prevention
1st Functions
DRV-01
[Acc. time]
DRV-02
[Dec. time]
FU1-31
[Base freq]
FU1-40
[V/F Pattern]
FU2-68
[Fwd Boost]
FU2-69
[Rev Boost]
FU1-60
APP-40: Number of Running Aux. Motor Display
APP-40~APP-72: MMC Operation Control
10.0
10.0
These functions APP-30 ~ APP-39 are displayed only
when one of the multifunction inputs in codes I/O-20
to I/O-27 is set at ‘2nd func’.
When an inverter is controlling two motors by
exchanging, different values can be set for the 2nd
motor by using the multifunction input terminal.
Following a cross reference table shows the 2nd
functions corresponding to the 1st functions.
Description
Note: The ‘User V/F’ function of FU1-40 [V/F
Pattern] is commonly used for the 1st and the 2nd
motor.
5.0
5.0
5.0 sec
APP►2nd Dec time
31
10.0 sec
Factory Default:
30
2nd Functions
[2nd Stall]
APP-37
[2nd ETH 1min]
APP-38
[2nd ETH cont]
APP-39
[2nd R-Curr]
APP► Aux Mot Run
40
0
Factory Default:
0
40
0
0
This code shows how many auxiliary motors are run
by MMC control.
[MMC]: The ‘PID’ control should be selected in
APP-02 to use this function.
 One inverter can control multiple motors. This
function is often used when controlling the rate and
pressure of flow in fans or pumps. Built-in PI
controller controlsa main motor after receiving
process control feedback value and keeps the control
value constant by connecting auxiliary motors to
commercial line when needed.
2nd Functions
APP-30
[2nd Acc time]
APP-31
[2nd Dec time]
APP-32
[2nd BaseFreq]
APP-33
[2nd V/F]
APP-34
[2nd F-boost]
APP-35
[2nd R-boost]
APP-36
 In case that flow rate or flow pressure is beyond or
below the reference so the main motor cannot control
by itself, auxiliary motors are automatically turned
on/off. Maximum four (Aux.1-4 output) auxiliary
6-60