IPE200 Engineering drive inverter
Detailed function description
It is shown as following figure:
Figure 6-5
Function
Name
Description
Action when
0: Running at the lower
Code
P1.14
FWD/REV dead time diagram.
running frequency frequency limit
is less than lower
frequency limit
1: Stop
Setting
Factory
Range
Setting
0~2
0
2: Stand-by
0: Running at the lower frequency limit (P0.09): The inverter runs at P0.09 when the running
frequency is less than P0.09.
1: Stop: This parameter is used to prevent motor running at low speed for a long time.
2: Stand-by: Inverter will stand-by when the running frequency is less than P0.09. When the
reference frequency is higher than or equal to P0.09 again, the inverter will start to run
automatically.
Function
Name
Code
P1.15
P1.16
Description
Restart after
0: Disabled
power off
1: Enabled
Delay time for
restart
0.0~3600.0s
Setting
Factory
Range
Setting
0~1
0
0.0~3600.0
0.0s
0: Disabled: Inverter will not automatically restart when power on again until run command
takes effect.
1: Enabled: When inverter is running, after power off and power on again, if run command
source is keypad control (P0.01=0) or communication control (P0.01=2), inverter will
automatically restart after delay time determined by P1.16; if run command source is terminal
control (P0.01=1), inverter will automatically restart after delay time determined by P1.16 only if
FWD or REV is active.
.42.