Zones: Parameters Quick Keys Parameter NOTE: See Wiring diagram in Chapter 2, Wiring the hardwire Zone , page 2-9. Zone Loop Response: The Loop Response menu enables you to set the different times for which a zone 33 violation must exist before the zone will trigger an alarm condition. The following option are available: 1) Normal: 400 ms (milliseconds) 2) Long: 1 second 3) Fast: 10 ms (milliseconds) 4) 0.5 hours 5) 1 hour 6) 1.5 hours 2 2 2 7) 2 hours 8) 2.5 hours 9) 3 hours 10) 3.5 hours 11) 4 hours Zone Labels The Zone Label menu enables you to create and/or edit up to 15 characters to describe each of the system's zones. Default: Zone 01, Zone 02, Zone 03, Zone 04 and so on for each zone Range: Any characters 1. From the Parameters menu, press [2] to access the Labels menu options. The following display appears: Zone label: Zone:01 (01-33) 2. Press to label Zone 01 (or enter another zone number). The following display appears: Zone label: Zone 01 01 Refer to page 4-16, for details about how to enter a label. 2 2 3 Range: Partition 1-3 Zone Partitions The Partitions menu contains parameters that enable you to program the partition assignment for each zone. 1. From the Parameters menu, press [3] to access the Partitions menu options. The following display appears: Zone partition: Zone:01 (01-33) 2. Specify a two-digit zone number and press appears: P=123 Y.. . The following display Z=XX NOTE: The XX in the Z=XX designation refers the zone number. In a multi-partitioned system, a zone can be assigned to more than one partition. A system without partitions is regarded as having a single partition (meaning Partition 1). 4-24 WisDom Installation and Programming Manual