Part 2 – FLITE
Timing Diagram
Application
FLITE 116-SA
DI/DT
IMAX
FLITE 116
OFF- 6-12-24-30-40-60-80 A
100-150-200-250-300-400-500-600- 800
A
ON (3, 30 or 60 s) or OFF
ON (70 s) or OFF
ON (3, 30 or 70 s) or OFF
2-4-8 or 16 hours
25 ms (60 hz.) 30 ms (50 hz)
INRUSH RESTRAINT
FAULT CONFIRMATION
AUTOMATIC VOLTAGE RESET
AUTOMATIC TIMER RESET
FAULT DELAY TRIP
6-12-24-30-40-60-80-100 A
OFF-100-150-200-250-300-400-500 or
600A
ON (3, 30 or 60 s) or OFF
ON (5 s) or OFF
ON (3, 30 or 60 s) or OFF
2-4-8 or 16 hours
25 ms (60 hz.) 30 ms (50 hz)
Waiting for a MV fault
Waiting for events
Flash On.
FLITEs located UPSTREAM the fault
FLITEs located DOWNSTREAM the fault
U
MV Fault
No reclosing cycles
Automatic voltage reset
U
0.1
I
I
1hour
1hour
T
T
Flite
Flite
di/dt fault
IMAX fault
End of di/dt fault
End of IMAX fault
Voltage presence (return)
End of voltage presence (loss)
O
O
O
O
O
O
O
O
FLITEs located UPSTREAM the fault
FLITEs located DOWNSTREAM the fault
U
MV fault
with reclosing cycles
U
0.1
0.3
0.3
I
I
0.3
0.5
30
0.5
T
Flite
0.3
30
T
Flite
O,1
di/dt fault
IMAX fault
End of di/dt fault
End of IMAX fault
Voltage presence (return)
End of voltage presence (loss)
O
O
O
Schneider Electric - NT00089EN-04 (User's manual
pour G200).doc
O
Easergy G200