Part 4 - Commissioning CPU configuration G200 long range communication settings The following menu are used to set the long range communication parameters (between the G200 and the remote control system) : Host baud rate: • Data-communication speed between SCADA and G200. • Adjustable from 200 to 9,600 bps. • Default value: 9,600 bps. DIRECT RS232 Version Direct RS232 : Note : for test purpose, it is better to select a low speed so that it is easier to see exchanged messages between SCADA and G200 (see DNP3 analyser below) Communication Parameters Host baud rate : 9600 Handle DSR : no Handle CD : no Modem : Direct RS 232 Handle DSR: • Select <yes> if you want G200 to detect connection using DSR signal. • Default value: <no> bauds Handle CTS : CTS delay : RTS (or CTS) to message delay : Message to RTS delay : Handle CD: • To make G200 control reception with CD signal, select <yes> . • Default value: <no> Handle CTS: • To make G200 wait for CTS signal (after asserting RTS signal) before sending message, select <yes> • Default value: < no> MERLIN GERIN - Configuration and Diagnostic - ALT+F4=Exit no 20ms 20ms 20ms Escape=Exit CTS delay: • Delay G200 shall wait for CTS to appear (if handled). • Adjustable from 0 to 500 ms. • Default value: 20 ms. RTS (or CTS) to message delay: • delay G200 shall wait after RTS (or CTS if handled) appears before sending the message. • Adjustable from 0 to 500 ms. • Default value: 20 ms Message to RTS delay: • delay G200 shall wait after the end of message before asserting RTS low. • Adjustable from 0 to 500 ms. • Default value: 20 ms Schneider Electric - NT00089EN-04 (User's manual pour G200).doc Easergy G200 40